| 2015-10-07 10:44:49 | |
| | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT TWO SETS OF FLOOR PLANS THAT SHOW THE WINDOW |
| | TYPES AND SIZES. THE PLANS THAT WERE SUBMITTED ONLY |
| | HAVE THE REQUIRED WIND LOAD PRESSURES. FBC 107.2.1 |
| | |
| | 2) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE |
| | SINGLE HUNG WINDOWS (FL14604.3) HAS A MAXIMUM DESIGN |
| | PRESSURE OF +50, -50 PSF. THE REQUIRED DESIGN WIND LOAD |
| | PRESSURES LISTED ON SHEET A1 OF THE PLANS IS HIGHER, |
| | THEREFORE THESE WINDOWS CAN NOT BE USED. FBC - R301.2.1 |
| | |
| | 3) FBC-R301.2.1.2 REQUIRES GLAZED OPENING TO BE |
| | PROTECTED FROM WINDBORNE DEBRIS. SUBMIT TWO SETS OF |
| | PRODUCT APPROVALS, KEY PLANS AND INSTALLATION SCHEDULES |
| | FOR THE STORM PANELS. |
| | |
| | 4) IF ANY OF THE OPENINGS HAVE TWO OR MORE WINDOWS THAT |
| | ARE CONNECTED WITH STRUCTURAL MULLIONS, THEN SUBMIT TWO |
| | SETS OF THE PRODUCT APPROVALS FOR THE MULLIONS THAT |
| | WILL BE USED. DCA RULE 9N-3 |
| | |
| | 5) WINDOWS THAT ARE LOCATED IN HAZARDOUS LOCATIONS, |
| | SUCH AS BATHROOMS, REQUIRE SAFETY GLAZING. SPECIFY |
| | THESE WINDOWS ON THE PLANS. FBC-R 308.4 |
| | |
| | 6) THE VALUE SPECIFIED ON THE APPLICATION OF $2,700.00 |
| | IS TOO LOW FOR THE REPLACEMENT OF WINDOWS IN 23 |
| | OPENINGS. FBC 109.3 |
| | |
| | 7) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE |
| | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER |
| | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN |
| | ADDRESSED. |