Plan Review Details - Permit 15080826
Plan Review Stops For Permit 15080826
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2015-10-14 Cont ID  
Sent By shill Date 2015-10-14 Time 15:51 Rev Time 0.00
Received By shill Date 2015-10-14 Time 15:51 Sent To  
Notes
2015-10-14 15:52:14PROVISO - PLUMBING PERMIT APPLICATION REQUIRED TO BE
 SUBMITTED PRIOR TO ISSUANCE
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-10-01 Cont ID  
Sent By shill Date 2015-10-01 Time 10:11 Rev Time 0.00
Received By shill Date 2015-10-01 Time 10:11 Sent To  
Notes
2015-10-01 10:15:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
  
 1. VALUE WILL BE DETERMINED WHEN SCOPE OF WORK HAS BEEN
 ESTABLISHED, FBC 109.
  
 2. ELECTRICAL PERMIT REQUIRED, FBC 107. PROVIDE AN
 ELECTRICAL PERMIT APPLICATION.
  
 3. PLUMBING PERMIT REQUIRED. PROVIDE PLANS (SEE
 PLUMBING REVIEW) AND SUBMIT A PLUMBING PERMIT
 APPLICATION.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-09-29 Cont ID  
Sent By shill Date 2015-09-29 Time 17:46 Rev Time 0.00
Received By shill Date 2015-09-29 Time 17:46 Sent To  
Notes
2015-09-29 17:53:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST, SAME PLAN SUBMITTED:
  
 1. PLAN HAS BEEN REVISED BUT IT DOES NOT APPEAR THAT
 ALL ITEMS INCLUDED ON THE VIOLATION / STOP WORK ORDER
 ISSUED ARE INCLUDED IN THE PLAN, FBC 105, FBC 107. WORK
 WILL BE CONFIRMED BY THE INSPECTOR WHO ISSUED THE
 VIOLATION.
  
 2. VALUE WILL BE DETERMINED WHEN SCOPE OF WORK HAS BEEN
 ESTABLISHED, FBC 109.
  
 3. ELECTRICAL PERMIT REQUIRED, FBC 107. PROVIDE AN
 ELECTRICAL PERMIT APPLICATION. THE RESPONSE LETTER
 STATES THAT "NO ELECTRICAL WORK INCLUDED IN OUR SCOPE
 OF WORK."
  
 A RENOVATION WHICH INCLUDED BUILDING, PLUMBING, AND
 ELECTRICAL WAS STARTED WITHOUT A PERMIT. PLEASE SEE FBC
 5TH EDITION EXISTING BUILDING CODE SECTIN 301.1; A
 METHOD OF COMPLIANCE IS TO BE SELECTED. UNTIL ENTIRE
 SCOPE OF WORK IS DETERMINED, LEVEL OF ALTERATION OR
 OTHER METHOD OF COMPLIANCE CANNOT BE DETERMINED (AND
 HAS NOT BEEN STATED BY UNKNOWN DESIGNER WHO PREPARED
 THE PLAN).
  
 IF THIS CONTRACTOR WILL NOT TAKE RESPONSIBILITY FOR THE
 WORK DONE AND WORK PROPOSED, ANOTHER CONTRACTOR
 LICENSED TO DO SO IS REQUIRED.
  
 4. THE PRINTED NAME AND SIGNATURE OF THE INDIVIDUAL
 TAKING RESPONSIBILITY FOR THE DESIGN IS TO BE ON THE
 PLAN, FBC 107.
  
 NEW COMMENT:
  
 VIOLATION INCLUDED PLUMBING. NO PLUMBING WORK IS SHOWN
 ON THE PLAN.
 BE ADVISED THAT, AFTER THE ABOVE COMMENTS ARE
 ADDRESSED, THE PLAN WILL BE SHOWN TO THE INSPECTOR WHO
 ISSUED THE VIOLATION. IF THE PLAN IS NOT CONSISTENT
 WITH THE WORK SEEN, THE PERMIT WILL NOT BE ISSUED.
  
 SEE FBC 107.2:
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS
 107.2.1 THROUGH 107.2.5.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES
 AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
 PLAN PROVIDED IS NOT ARCHITECTURAL QUALITY, NOT TO
 SCALE, IS DIFFICULT TO READ. PROVIDE A PLAN WHICH
 CONFORMS TO 107.2.
  
 DO NOT RESUBMIT UNLESS AN ELECTRICAL APPLICATION AND A
 PLUMBING APPLICATION ARE INCLUDED IN THE SUBMITTAL. DO
 NOT RESUBMIT UNLESS THE PLAN SHOWS ALL WORK WHICH WAS
 DONE WITHOUT PERMIT. PLUMBING WORK WAS DONE, THEREFORE
 A PLUMBING PERMIT IS REQUIRED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-08 Cont ID  
Sent By shill Date 2015-09-09 Time 07:52 Rev Time 0.00
Received By shill Date 2015-09-08 Time 07:52 Sent To  
Notes
2015-09-08 07:54:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLAN HAS BEEN REVISED BUT IT DOES NOT APPEAR THAT
 ALL ITEMS INCLUDED ON THE VIOLATION / STOP WORK ORDER
 ISSUED ARE INCLUDED IN THE PLAN, FBC 105, FBC 107. WORK
 WILL BE CONFIRMED BY THE INSPECTOR WHO ISSUED THE
 VIOLATION.
  
 2. VALUE WILL BE DETERMINED WHEN SCOPE OF WORK HAS BEEN
 ESTABLISHED, FBC 109.
  
 3. ELECTRICAL PERMIT REQUIRED, FBC 107. PROVIDE AN
 ELECTRICAL PERMIT APPLICATION. THE RESPONSE LETTER
 STATES THAT "NO ELECTRICAL WORK INCLUDED IN OUR SCOPE
 OF WORK."
  
 A RENOVATION WHICH INCLUDED BUILDING, PLUMBING, AND
 ELECTRICAL WAS STARTED WITHOUT A PERMIT. PLEASE SEE FBC
 5TH EDITION EXISTING BUILDING CODE SECTIN 301.1; A
 METHOD OF COMPLIANCE IS TO BE SELECTED. UNTIL ENTIRE
 SCOPE OF WORK IS DETERMINED, LEVEL OF ALTERATION OR
 OTHER METHOD OF COMPLIANCE CANNOT BE DETERMINED (AND
 HAS NOT BEEN STATED BY UNKNOWN DESIGNER WHO PREPARED
 THE PLAN).
  
 IF THIS CONTRACTOR WILL NOT TAKE RESPONSIBILITY FOR THE
 WORK DONE AND WORK PROPOSED, ANOTHER CONTRACTOR
 LICENSED TO DO SO IS REQUIRED.
  
 4. THE PRINTED NAME AND SIGNATURE OF THE INDIVIDUAL
 TAKING RESPONSIBILITY FOR THE DESIGN IS TO BE ON THE
 PLAN, FBC 107.
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-25 Cont ID  
Sent By shill Date 2015-08-25 Time 15:21 Rev Time 0.00
Received By shill Date 2015-08-25 Time 15:21 Sent To E
Notes
2015-08-25 15:24:37****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SCOPE NOT CLEAR. SCOPE STATES "DRYWALL REPAIR
 THROUGHOUT." SQUARE FOOT AREA, LOCATIONS, CEILING OR
 WALLS? SEE FBC 107; PLANS SHOULD BE CLEAR AS TO SCOPE
 AND NATURE OF PROPOSED WORK.
  
 2. VALUE ($2400) APPEARS TOO LOW. VALUE TO INCLUDE THE
 VALUE OF LABOR, MATERIALS, OVERHEAD, PROFIT. PROVIDE A
 COST BREAKDOWN FOR THIS JOB.
  
 3. ELECTRICAL PERMIT REQUIRED, FBC 107.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-08-26 Cont ID  
Sent By ppetty Date 2015-08-26 Time 10:25 Rev Time 0.00
Received By ppetty Date 2015-08-26 Time 10:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-10-14 Cont ID  
Sent By shill Date 2015-10-14 Time 15:52 Rev Time 0.00
Received By shill Date 2015-10-06 Time 10:52 Sent To  
Notes
2015-10-08 10:52:24TIM LARGE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-10-02 Cont ID  
Sent By tklarge Date 2015-10-02 Time 05:01 Rev Time 0.00
Received By tklarge Date 2015-10-01 Time 10:16 Sent To  
Notes
2015-10-01 10:17:289/30 ADDED PLUMBING STOP, ROUTED TO TL DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-09-29 Cont ID  
Sent By shill Date 2015-09-29 Time 18:00 Rev Time 0.00
Received By shill Date 2015-09-21 Time 08:48 Sent To  
Notes
2015-09-22 08:49:10RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-08 Cont ID  
Sent By shill Date 2015-09-08 Time 07:54 Rev Time 0.00
Received By shill Date 2015-09-01 Time 15:20 Sent To  
Notes
2015-09-01 15:21:03RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-26 Cont ID  
Sent By shill Date 2015-08-26 Time 10:57 Rev Time 0.00
Received By shill Date 2015-08-21 Time 16:22 Sent To  
Notes
2015-08-25 15:24:598/25 TO ELEC BOX
  
2015-08-21 16:22:30BLDG MISC 2

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-10-19 Cont ID  
Sent By gjohnson Date 2015-10-08 Time 17:18 Rev Time 0.00
Received By gjohnson Date 2015-10-08 Time 17:18 Sent To  
Notes
2015-10-08 17:30:48 
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
 1.PHOTOS SHOW WORK DONE ON DRAIN AND WATER FOR WASHING
 MACHINE MUST BE SHOWN ON SCOPE OF WORK.
 PER WPB AMED. 107.2.1
 2.PIPING FOR WASHING MACHINE NOT TO CODE PROVIDE RISER
 DIAGRAM FOR SANITARY.
 PER. WPB AMEND. 107.3.5.3(11)
 3.PLUMBING SUB PERMIT REQUIRED.
 PER WPB AMEND. SEC 105.1
 4. ALL WORK WILL BE SUBJECT TO FIELD INSPECTORS
 APPROVAL.

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-10-02 Cont ID  
Sent By tklarge Date 2015-10-02 Time 05:01 Rev Time 0.00
Received By tklarge Date 2015-10-02 Time 04:42 Sent To  
Notes
2015-10-02 05:00:551)THERE ARE THREE SEPARATE FLOOR PLANS THAT HAVE BEEN
 SUBMITTED WITH THIS PERMIT. SUBMIT 2 COPIES OF THE
 FLOOR PLAN THAT IS TO BE USED FOR THIS PROJECT. WPB
 AMENDMENTS TO FBC SEC. 107.1.
 2) THE PHOTOS TAKEN SHOW PLUMBING PIPING IN THE WALL
 THAT IS NOT TO CODE. IF THIS AREA HAS BEEN COVERED
 WWITH DRYWALL IT SHALL BE REMOVED AND THE PIPING
 REPLACED TO MEET THE PLUMBING CODE.
 3) THE PHOTOS SHOW THAT WATER CLOSETS HAVE BEEN REMOVED
 YET THE WORK PROPOSAL ONLY STATES "REPLACE VANITIES".
 SUBMIT A REVISED WORK PROPOSAL THAT CLEARLY REFLECTS
 THE ENTIRE SCOPE OF PLUMBING WORK TO BE DONE. WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  