| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-08-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-08-24 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-08-24 |
Time |
07:29 |
Sent To |
|
|
| Notes |
| 2015-08-24 09:40:44 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE SELF | | | ADHERED UNDERLAYMENT FOR THE FOAM APPLIED CLAY ROOF | | | TILE (FL11602-R3) IS NOT ACCEPTABLE WITHOUT ADDITIONAL | | | CALCULATIONS. THE MAXIMUM DESIGN PRESSURE OF THE | | | UNDERLAYMENT IS -45 PSF, WHICH IS INADEQUATE FOR THE | | | PERIMETER AND CORNER AREAS OF THE SLOPED ROOF. SEE | | | 5.6.3 ON PAGE 3 AND 5.6.3.5 ON PAGE 4 OF THE PRODUCT | | | APPROVAL. FBC-R301.2.1 | | | |
|
|
|