Plan Review Details - Permit 15080727
Plan Review Stops For Permit 15080727
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-10-13 Cont ID  
Sent By skennedy Date 2015-10-13 Time 10:06 Rev Time 0.00
Received By skennedy Date 2015-10-13 Time 10:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-11 Cont ID  
Sent By skennedy Date 2015-09-11 Time 09:37 Rev Time 0.00
Received By skennedy Date 2015-09-11 Time 09:44 Sent To  
Notes
2015-09-11 09:57:361ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 THE DESIGN CRITERIA LISTED ON THE PLAN IS OUTDATED,
 PLEASE NOTE THE CODE IN EFFECT ABOVE.
  
 SEE MECHANICAL REVIEW FOR ENERGY SUBMOTTAL
 REQUIREMENTS.
  
 PROVIDE ADDITIONAL INFORMATION AS FOLLOWS: PRODUCT
 APPROVALS AS FOLLOWS:
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, AND WINDOW SUBMITTALS.
  
 ADDITIONALLY, PLEASE NOTE THE PLAN CALL FOR CASEMENT
 EGRESS WINDOWS. THE SUBMITTED WINDOW PRODUUCTS ARE
 SINGLE HUNG & FIXED ONLY.
  
 TYPICAL WALL SECTION: PLEASE SHOW PROPOSED VAPOR
 BARRIER.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-09-11 Cont ID  
Sent By skennedy Date 2015-09-11 Time 09:40 Rev Time 0.00
Received By skennedy Date 2015-09-11 Time 09:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-13 Cont ID  
Sent By skennedy Date 2015-10-13 Time 10:06 Rev Time 0.00
Received By skennedy Date 2015-10-01 Time 13:23 Sent To  
Notes
2015-10-02 13:23:49SKENNEDY'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-11 Cont ID  
Sent By skennedy Date 2015-09-11 Time 09:58 Rev Time 0.00
Received By skennedy Date 2015-08-20 Time 09:41 Sent To  
Notes
2015-08-20 09:41:20R22

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-10-13 Cont ID  
Sent By skennedy Date 2015-10-13 Time 10:06 Rev Time 0.00
Received By skennedy Date 2015-10-13 Time 09:59 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-09-11 Cont ID  
Sent By skennedy Date 2015-09-11 Time 09:38 Rev Time 0.00
Received By skennedy Date 2015-09-11 Time 09:38 Sent To  
Notes
2015-09-11 09:39:14PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-10-13 Cont ID  
Sent By skennedy Date 2015-10-13 Time 10:05 Rev Time 0.00
Received By skennedy Date 2015-10-13 Time 10:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-09-11 Cont ID  
Sent By skennedy Date 2015-09-11 Time 09:37 Rev Time 0.00
Received By skennedy Date 2015-09-11 Time 09:37 Sent To  
Notes
2015-09-11 09:44:071ST REVIEW: FBC 2014 5TH ED.
  
 PROVIDE AN ENERGY SUBMITTAL AND PLAN AS FOLLOWS:
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW
 SUPPLY DUCTS PER FBC-R M16.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-09-05 Cont ID  
Sent By tklarge Date 2015-09-05 Time 06:18 Rev Time 0.00
Received By tklarge Date 2015-09-05 Time 06:03 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2015-10-13 Cont ID  
Sent By swurafti Date 2015-10-13 Time 14:11 Rev Time 0.00
Received By swurafti Date 2015-10-13 Time 14:11 Sent To  
Notes
2015-10-13 16:34:40OKAY PER SKENNEDY

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-09-11 Cont ID  
Sent By skennedy Date 2015-09-11 Time 09:57 Rev Time 0.00
Received By skennedy Date 2015-09-11 Time 09:57 Sent To  
Notes
2015-09-11 09:58:17SEE BUILDING REVIEW FOR REQUIRED PRODUCT SUBMITTAL.

Review Stop Z ZONING
Rev No 2 Status P Date 2015-09-03 Cont ID  
Sent By sgraham Date 2015-09-03 Time 10:49 Rev Time 0.00
Received By sgraham Date 2015-09-03 Time 10:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-08-25 Cont ID  
Sent By sgraham Date 2015-08-25 Time 08:32 Rev Time 0.00
Received By sgraham Date 2015-08-25 Time 08:32 Sent To  
Notes
2015-08-25 08:33:488/25/15 ZONING FAILED
  
  
  
 1. SUBMIT TWO COPIES OF AN UP TO DATE SURVEY, SHOWING
 THE LOCATION OF THE EXISTING GARAGE.
2015-08-24 11:10:418/24/15