Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-09-28 Cont ID  
Sent By skennedy Date 2015-09-28 Time 07:33 Rev Time 0.00
Received By skennedy Date 2015-09-28 Time 07:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-25 Cont ID  
Sent By skennedy Date 2015-09-25 Time 11:21 Rev Time 0.00
Received By skennedy Date 2015-09-25 Time 09:35 Sent To  
Notes
2015-09-25 11:58:202ND REVIEW: FBC 2014 5TH ED.
  
 THE RE-SUBMITTED TEST ARE FOR A CONDITION THAT MAY NOT
 EXIST IN THE PROPOSED LOCATION. SHOW THAT THE EXISTING
 CONDITION IS THE SAME AS DESCRIBED IN THE SOUND TESTS,
 OR PROVIDE A PRODUCT WITH TESTING CONDITIONS EQUIVALENT
 TO THE PROPOSED INSTALLATION.
  
 PLEASE SUBMIT PRODUCT TEST REPORTS TO DEMONSTRATE
 COMPLIANCE WITH THE FOLLOWING:
  
 FBC 603.1 FLAME SPREAD
  
 FBC 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 FOR YOU CONVENIENCE, YOU MAY E-MAIL REPORTS TO ME.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-09 Cont ID  
Sent By skennedy Date 2015-09-09 Time 16:10 Rev Time 0.00
Received By skennedy Date 2015-09-09 Time 16:10 Sent To  
Notes
2015-09-09 16:14:181ST REVIEW: FBC 2014 5TH ED.
  
 PLEASE SUBMIT PRODUCT TEST REPORTS TO DEMONSTRATE
 COMPLIANCE WITH THE FOLLOWING:
  
 FBC 603.1 FLAME SPREAD
  
 FBC 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 FOR YOU CONVENIENCE, YOU MAY E-MAIL REPORTS TO ME.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-25 Cont ID  
Sent By skennedy Date 2015-09-25 Time 11:23 Rev Time 0.00
Received By skennedy Date 2015-09-23 Time 10:01 Sent To  
Notes
2015-09-24 10:01:57ROUTED TO SKENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-09 Cont ID  
Sent By skennedy Date 2015-09-09 Time 16:10 Rev Time 0.00
Received By skennedy Date 2015-08-19 Time 14:22 Sent To  
Notes
2015-08-19 14:23:02BLDG MISC 1


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved