| 2015-10-07 08:36:05 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 15080680 |
| | W. P. B. PERMIT: 13060638 |
| | ADD: 114 S. OLIVE AVE. |
| | CONT: DWYOR CONSTRUCTION & DEVELOPMENT |
| | TEL: (561)856-6655 |
| | E-MAIL: ????????????????????? |
| | |
| | 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. OCT. 07/2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1.1. THE FRONT ENTRY INDICATES THAT THERE IS |
| | NO A SLOPED PORTION OF THE FLOOR LESS THAN OR EQUAL TO |
| | 1:20. THE PLANS DO NOT PROVIDE WHAT THE ELEVATION |
| | CHANGE FROM THE STREET TO THE FLAT FINISH FLOOR AND AT |
| | WHAT DISTANCE THIS SLOPED AREA OF THE FLOOR IS TO |
| | DETERMINE IF THIS IS A RAMP OR JUST A SLOPED SURFACE OF |
| | THE FLOOR. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED |
| | TO DETERMINE CODE COMPLIANCE WITH EITHER GRADE OR RAMP. |
| | 2010 FBC-ACCESSIBLITY DEFITIONS 106 RAMP : RUNNING |
| | SLOPE STEEPER THAN 1:20. |
| | |
| | 2) SHEET A1.1. NEW FIRE SPRINKLER ROOM 106 DOES NOT |
| | INDICATE WALL TAGS IDENTIFYING THE TYPE OF WALL |
| | CONSTRUCTION FOR THIS SPACE. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED FOR CODE COMPLIANCE. |
| | |
| | 3) SHEET A1.1 THE SECOND FLOOR PLAN WITH THE NEW FLOOR |
| | PLAN AND SEATING ARRANGEMENT AND COLUMN LAYOUT PLEASE |
| | SHOW COMPLIANCE WITH 2010 FBC-B 1014.3 EXCEPTION #5. |
| | WHERE A TENANT SPACE IN A GROUP A OCCUPANCY HAS AN |
| | OCCUPANT LOAD OF MORETHAN 50, THE LENGTH OF A COMMON |
| | PATH OF TRAVEL SHALL NOT BE MORE THAN 20 FT. NOTE ALSO |
| | PROVIDE THE ACCESS AISLES SHOWING COMPLIANCE WITH |
| | 1017.4.3 AISLES ACCESSWAYS SHALL NOT EXCEED 30 FT FROM |
| | ANY SEAT TO THE POINT WHERE A PERSON HAS 2 OR MORE |
| | PATHS OF EGRESS TRAVEL TO SEPARATE EXITS. |
| | |
| | 4) SHEET A1.1 THE 3RD FLOOR PLAN THE NORTH EAST CORNER |
| | OF THE SEATING AREA SHOW COMPLIANCE WITH 1017.4.3 |
| | AISLES ACCESSWAYS SHALL NOT EXCEED 30 FT FROM ANY SEAT |
| | TO THE POINT WHERE A PERSON HAS 2 OR MORE PATHS OF |
| | EGRESS TRAVEL TO SEPARATE EXITS. |
| | |
| | 5) SHEET A1.2. ROOM 209 THE ELEVAOR EQUIPMENT ROOM DOES |
| | NOT HAVE WALL TAGS IDENTIFYING THE TYPE OF WALL |
| | CONSTRUCTION IN ACCORDANCE WITH 2010 FBC-B 3006.4 |
| | MACHINE ROOMS 1 HOUR FIRE BARRIER. |
| | |
| | 6) SHEET A1.2 ROOM # 208 THE UNISEX RESTROOM DOOR # |
| | 208.01 THE WAY THIS DOOR SWINGS REQUIRES 42 INCHES OF |
| | WALL ON THE LATCH SIDE OF THE DOOR. PLEASE REVIEW 2010 |
| | ACCESSIBILITY CODE FIGURE 404.2.4.1 (E). |
| | |
| | 7) SHEET A1.3, DOOR 304.01 DOES NOT HAVE THE REQUIRED |
| | 18 INCHES CLEAR WIDTH ON THE LATCH SIDE OF THE DOOR. |
| | 2010 FBC-ACCESSIBLITY CODE. 404.2.4 MAEUVERING |
| | CLEARENCES, AND FIGURE 404.2.4.1( A) . |
| | |
| | 8) SHEET A1.1 THE 3RD FLOOR. THE STANDING ROOM ONLY |
| | NEXT TO THE PROPERTY LINE WALL. SHEET A5.2 NOTE CON A. |
| | CONCRETE BLOCK RAILING TO 48 INCHES AFF. PLEASE NOTE |
| | THIS IS A REVISION FROM WHAT IS SHOWN ON A7.1.1 |
| | SECTIONS 02 & 03. THE DETAILS 02 & 03 SHOW A BLOCK WALL |
| | 2 FOOT 3 INCHES ABOVE THE 3RD FLOOR WITH A GLASS |
| | RAILING TO THE HEIGTH OF 3 FOOT 8 INCHES. PLEASE UPDATE |
| | SHEET A7.1.1. |
| | |
| | NOTE THE 3 FOOT 8 INCHES BLOCK WALL/ GUARDRAIL IS MORE |
| | RESTRICTIVE THAN THE REQUIRED 42 INCHES, SHEET A1.1 THE |
| | 3RD FLOOR PLAN SHOWS THE SOFA SEATING 4 FOOT 6 INCHES |
| | AWAY FROM THE BLOCK WALL/ GUARD RAIL, THERE IS NO |
| | ADJACENT FIXED SEATING FBC-B 1013.2) TO BE COMPLIED |
| | WITH!!!!!!! |
| | |
| | 9A) SHEET A5.1 THE SOUTH ELEVATION DOES NOT SHOW |
| | WINDOWS ON THE 3RD OR 4 THE FLOORS IN THE ADJACENT |
| | BUILDING, JUST A BLANK WALL. INSPECTORS ON THE JOBSITE |
| | HAVE VERIFIED THERE ARE WINDOWS IN THESE WALLS. PLEASE |
| | SHOW HOW COMPLIANCE WITH STEPPED BUILDING 2010 FBC-B |
| | 706.6.1. WHERE A FIRE WALL SERVES AS AN EXTERIOR WALL |
| | FOR A BUILDING AND SEPARATES BUILDINGS HAVING DIFFERENT |
| | ROOF LEVELS, SUCH WALL SHALL TERMINATE AT A POINT NOT |
| | LESS THAN 30 INCHES (762 MM) ABOVE THE LOWER ROOF |
| | LEVEL, PROVIDED THE EXTERIOR WALL FOR A HEIGHT OF 15 |
| | FEET (4572 MM) ABOVE THE LOWER ROOF IS NOT LESS THAN |
| | 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION FROM BOTH |
| | SIDES WITH OPENINGS PROTECTED BY FIRE ASSEMBLIES HAVING |
| | A FIRE PROTECTION RATING OF NOT LESS THAN 3/4 HOUR. |
| | EXCEPTION: WHERE THE FIRE WALL TERMINATES AT THE |
| | UNDERSIDE OF THE ROOF SHEATHING, DECK OR SLAB OF THE |
| | LOWER ROOF, PROVIDED: 1. THE LOWER ROOF ASSEMBLY WITHIN |
| | 10 FEET (3048 MM) OF THE WALL HAS NOT LESS THAN A |
| | 1-HOUR FIRE-RESISTANCE RATING AND THE ENTIRE LENGTH AND |
| | SPAN OF SUPPORTING ELEMENTS FOR THE RATED ROOF ASSEMBLY |
| | HAS A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR. |
| | 2. OPENINGS IN THE LOWER ROOF SHALL NOT BE LOCATED |
| | WITHIN 10 FEET (3048 MM) OF THE FIRE WALL. |
| | |
| | 9B) 2010 FBC-B 706.8 OPENINGS. EACH OPENING THROUGH A |
| | FIRE WALL SHALL BE PROTECTED IN ACCORDANCE WITH SECTION |
| | 716.5 AND SHALL NOT EXCEED 156 SQUARE FEET (15 M2). THE |
| | AGGREGATE WIDTH OF OPENINGS AT ANY FLOOR LEVEL SHALL |
| | NOT EXCEED 25 PERCENT OF THE LENGTH OF THE WALL. |
| | EXCEPTIONS: |
| | 1. OPENINGS ARE NOT PERMITTED IN PARTY WALLS |
| | CONSTRUCTED IN ACCORDANCE WITH SECTION 706.1.1. |
| | 2. OPENINGS SHALL NOT BE LIMITED TO 156 SQUARE FEET (15 |
| | M2) WHERE BOTH BUILDINGS ARE EQUIPPED THROUGHOUT WITH |
| | AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE |
| | WITH SECTION 903.3.1.1. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |