Plan Review Details - Permit 15080679
Plan Review Stops For Permit 15080679
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-11-20 Cont ID  
Sent By shill Date 2015-11-20 Time 17:43 Rev Time 0.00
Received By shill Date 2015-11-20 Time 17:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-11-10 Cont ID  
Sent By shill Date 2015-11-10 Time 15:42 Rev Time 0.00
Received By shill Date 2015-11-10 Time 15:42 Sent To  
Notes
2015-11-10 16:02:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9N-3, FBC 5TH EDITION RESIDENTIAL 301.
  
 2ND REVIEW, PROVIDE THE PRODUCT APPROVAL FOR THE PAN
 ROOF.
 3RD REVIEW, NOT ADDRESSED. THE PRODUCT APPROVAL IS
 AVAILABLE AT WWW.FLORIDABUILDING.ORG.
  
 2. SEE FBC 5TH ED. RESIDENTIAL TABLE 302.1(1), SHOW
 DISTANCE FROM PROPOSED PAN ROOF TO PROPERTY LINE. IF
 ANY PART OF THE PAN ROOF IS WITHIN 5' OF THE PROPERTY
 LINE, A 1 HOUR FIRE RESISTANCE RATING IS REQUIRED.
  
 2ND REVIEW, PLAN WAS REVISED TO STATE TO ADJUST TO
 SETBACK. SITE PLAN WAS NOT REVISED. REVISE THE SITE
 PLAN TO CLEARLY SHOW THE WIDTH OF THE PROPOSED ROOF AND
 THE DISTANCE TO THE PROPERTY LINE.
 3RD REVIEW, ONLY ONE SET OF THE REVISED SITE PLAN
 PROVIDED. SEE OTHER COMMENTS REGARDING PLAN SUBMISSION.
  
 3. WHEN RESUBMITTING, PROVIDE TWO COMPLETE COLLATED
 SETS OF PLANS FOR PERMIT ISSUANCE. OLD SHEETS SHOULD BE
 RETAINED IN THE PACKAGE BUT MARKED "VOID".
  
 3RD REVIEW, NOT ADDRESSED. THERE SHOULD BE TWO COMPLETE
 COLLATED SETS OF PLANS FOR PERMIT ISSUANCE, OLD SETS
 MARKED "VOID." AN ATTEMPT WAS MADE TO REDLINE THIS
 PLAN, BUT THERE ARE NOT TWO COMPLETE SETS AND THE
 PRODUCT APPROVAL WAS NOT PROVIDED. THE COLLATED SETS
 SHOULD BE IDENTICAL AND SHOULD NOT INCLUDE DUPLICATE
 PAGES. SOME SHEETS ARE STAPLED ON TWO SIDES SO THE
 PACKAGE CANNOT OPEN, OTHER SHEETS ARE UPSIDE DOWN. ONE
 SET HAS TWO SITE SPECIFIC PLANS WHICH ARE IDENTICAL. A
 LOOSE PAGE HAS HAND DRAWN CHANGES ON IT; IT IS NOT
 CLEAR WHY THIS WAS SUBMITTED.
  
 NEW COMMENTS:
  
 4. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS471.
  
 5. BASED ON THE PLANS PROVIDED, THE 3' DOOR ENCROACHES
 THE PROPERTY LINE (2' SETBACK). ALL WORK FOR THIS
 PERMIT IS TO BE CONTAINED IN THE PARCEL. WORK ON OTHER
 PARCELS REQUIRE A SEPARATE PERMIT APPLICATION, FBC 107.
 ALSO, THE SITE PLAN SHOWS A 4' GATE; NOT CLEAR WHAT
 THIS IS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-21 Cont ID  
Sent By shill Date 2015-10-21 Time 17:48 Rev Time 0.00
Received By shill Date 2015-10-21 Time 17:48 Sent To  
Notes
2015-10-21 17:50:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9N-3, FBC 5TH EDITION RESIDENTIAL 301.
  
 2ND REVIEW, PROVIDE THE PRODUCT APPROVAL FOR THE PAN
 ROOF.
  
 2. SEE FBC 5TH ED. RESIDENTIAL TABLE 302.1(1), SHOW
 DISTANCE FROM PROPOSED PAN ROOF TO PROPERTY LINE. IF
 ANY PART OF THE PAN ROOF IS WITHIN 5' OF THE PROPERTY
 LINE, A 1 HOUR FIRE RESISTANCE RATING IS REQUIRED.
  
 2ND REVIEW, PLAN WAS REVISED TO STATE TO ADJUST TO
 SETBACK. SITE PLAN WAS NOT REVISED. REVISE THE SITE
 PLAN TO CLEARLY SHOW THE WIDTH OF THE PROPOSED ROOF AND
 THE DISTANCE TO THE PROPERTY LINE.
  
 WHEN RESUBMITTING, PROVIDE TWO COMPLETE COLLATED SETS
 OF PLANS FOR PERMIT ISSUANCE. OLD SHEETS SHOULD BE
 RETAINED IN THE PACKAGE BUT MARKED "VOID".
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-15 Cont ID  
Sent By shill Date 2015-09-15 Time 12:24 Rev Time 0.00
Received By shill Date 2015-09-15 Time 12:24 Sent To  
Notes
2015-09-15 12:56:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9N-3, FBC 5TH EDITION RESIDENTIAL 301.
  
 2. SEE FBC 5TH ED. RESIDENTIAL TABLE 302.1(1), SHOW
 DISTANCE FROM PROPOSED PAN ROOF TO PROPERTY LINE. IF
 ANY PART OF THE PAN ROOF IS WITHIN 5' OF THE PROPERTY
 LINE, A 1 HOUR FIRE RESISTANCE RATING IS REQUIRED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-11-20 Cont ID  
Sent By shill Date 2015-11-20 Time 17:43 Rev Time 0.00
Received By shill Date 2015-11-16 Time 13:35 Sent To  
Notes
2015-11-16 13:36:08RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-11-10 Cont ID  
Sent By shill Date 2015-11-10 Time 16:02 Rev Time 0.00
Received By shill Date 2015-11-10 Time 10:31 Sent To  
Notes
2015-11-10 10:32:05FOUND IN DENIED DRAWER, ROUTED TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-21 Cont ID  
Sent By shill Date 2015-10-21 Time 17:50 Rev Time 0.00
Received By shill Date 2015-10-16 Time 07:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-15 Cont ID  
Sent By shill Date 2015-09-15 Time 13:35 Rev Time 0.00
Received By shill Date 2015-08-19 Time 11:46 Sent To B
Notes
2015-08-19 11:47:59ZONING
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-11-04 Cont ID  
Sent By sgraham Date 2015-11-04 Time   Rev Time 0.00
Received By   Date 2015-11-04 Time   Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-08-24 Cont ID  
Sent By sgraham Date 2015-08-24 Time 15:46 Rev Time 0.00
Received By sgraham Date 2015-08-24 Time 15:46 Sent To B
Notes
***NONE***