Plan Review Details - Permit 15080670
Plan Review Stops For Permit 15080670
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-11-23 Cont ID  
Sent By jwitmer Date 2015-11-23 Time 16:13 Rev Time 0.00
Received By destabro Date 2016-03-31 Time 11:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-09 Cont ID  
Sent By jwitmer Date 2015-09-09 Time 14:40 Rev Time  
Received By jwitmer Date 2015-09-09 Time 12:31 Sent To  
Notes
2015-09-09 14:40:53BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080670
 ADD: 1408 FLORIDA AVE.
 CONT: SENTINEL DEVELOPMENT
 TEL: (561)373-4056
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 09/2015
 ACTION: DENIED
  
 1) PLEASE NOTE THE PALM BEACH COUNTY PROPERTY
 APPRAISERS OFFICE HAS THE IMPROVEMENT VALUE OF THIS
 PROPERTY VALUED AT $184,135.00. THE PERMIT APPLICATION
 INDICATES THE VALUE OF WORK TO BE COMPLETED UNDER THIS
 PERMIT A VALUE OF $170,000.00. THIS DOLLOR VALUE MEETS
 THE DEFINITION OF
 A RENOVATED BUILDING. RENOVATED BUILDING. A RESIDENTIAL
 OR NONRESIDENTIAL BUILDING UNDERGOING ALTERATION THAT
 VARIES OR CHANGES INSULATION, HVAC SYSTEMS, WATER
 HEATING SYSTEMS, OR EXTERIOR ENVELOPE CONDITIONS,
 PROVIDED THE ESTIMATED COST OF RENOVATION EXCEEDS 30
 PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE.
  
 SHEET A1 THE INTERIOR -DEMO PLAN NOTES D-14 & D-15
 INDICATE THE REMOVAL OF THE AIR HANDLER IN THE ATTIC AS
 WELL AS THE DUCT WORK. SHEET A2 NOTE 18 INDICATES A NEW
 VERTICAL A/C HANDLIER AND NEW A/C CLOSET. NOTE THERE
 WAS A MECHANICAL EXACT CHANGE OUT PERMIT ISSUED
 15080568.
 NO DUCT WORK NO PLANS NO PLAN REVIEW.
  
 2014 ENERGY CODE. R101.4.7 BUILDING SYSTEMS AND
 COMPONENTS. THERMAL EFFICIENCY STANDARDS ARE SET FOR
 THE FOLLOWING BUILDING SYSTEMS AND COMPONENTS WHERE NEW
 PRODUCTS ARE INSTALLED OR REPLACED IN EXISTING
 BUILDINGS, AND FOR WHICH A PERMIT MUST BE OBTAINED. NEW
 PRODUCTS SHALL MEET THE MINIMUM EFFICIENCIES ALLOWED BY
 THIS CODE FOR THE FOLLOWING SYSTEMS AND COMPONENTS:
  
 HEATING, VENTILATING OR AIR CONDITIONING SYSTEMS.
 SERVICE WATER OR POOL HEATING SYSTEMS. LIGHTING
 SYSTEMS. REPLACEMENT FENESTRATION.
  
  
 2014 ENERGY CODE R101.5 COMPLIANCE. RESIDENTIAL
 BUILDINGS SHALL MEET THE RESIDENTIAL PROVISIONS OF THIS
 CODE.
  
 R101.5.1 COMPLIANCE MATERIALS. THE FLORIDA BUILDING
 COMMISSION SHALL APPROVE SPECIFIC COMPUTER SOFTWARE,
 WORKSHEETS, COMPLIANCE MANUALS AND OTHER SIMILAR
 MATERIALS THAT MEET THE INTENT OF THIS CODE. COMMISSION
 APPROVED CODE COMPLIANCE DEMONSTRATION FORMS CAN BE
 FOUND IN TABLE R101.5.1. PLEASE PROVIDE COMPLIANCE FOR
 THE ENERGY CODE BY EITHER PREFORMANCE BASED OR
 PRESCRIPTIVE BASED STANDARDS.
  
 2) THE PLANS INDICATE THEY WERE DESIGNED TO THE 2010
 FBC. PLEASE NOTE THE 2014 FBC- 5TH EDITION WAS ADOPTED
 STATEWIDE JUNE 30. 2015.
 NOTE THE PLANS WILL NEED TO BE REDESIGNED TO THE 2014
 FBC. PLEASE NOTE THE AMOUNT OF WORK INDICATED ON THE
 PLANS IS A LEVEL III ALTERATION .
  
 3) THE PLANS INDICATE THIS STRUCTURE TO BE A 3 UNIT R-2
 BUILDING WITH TENANT SEPARATION WALLS. PLEASE PROVIDE A
 SECTION THROUGH INDICATING CODE COMPLIANCE WITH FBC-B
 708.1(1) WALLS SEPARATING DWELLING UNITS.
  
 2014 FBC-B 420.2 SEPARATION WALLS. WALLS SEPARATING
 DWELLING UNITS IN THE SAME BUILDING, WALLS SEPARATING
 SLEEPING UNITS IN THE SAME BUILDING AND WALLS
 SEPARATING DWELLING OR SLEEPING UNITS FROM OTHER
 OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME BUILDING
 SHALL BE CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE
 WITH SECTION 708.
  
 2014 FBC-B 708.4 CONTINUITY. FIRE PARTITIONS SHALL
 EXTEND FROM THE TOP OF THE FOUNDATION OR FLOOR/CEILING
 ASSEMBLY BELOW TO THE UNDERSIDE OF THE FLOOR OR ROOF
 SHEATHING, SLAB OR DECK ABOVE OR TO THE
 FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING
 ASSEMBLY ABOVE, AND SHALL BE SECURELY ATTACHED THERETO.
 IN COMBUSTIBLE CONSTRUCTION WHERE THE FIRE PARTITIONS
 ARE NOT REQUIRED TO BE CONTINUOUS TO THE SHEATHING,
 DECK OR SLAB, THE SPACE BETWEEN THE CEILING AND THE
 SHEATHING, DECK OR SLAB ABOVE SHALL BE FIREBLOCKED OR
 DRAFTSTOPPED IN ACCORDANCE WITH SECTIONS 718.2 AND
 718.3 AT THE PARTITION LINE. PROVIDE THE FIRE RATED
 FIRE ASSEMBLY NUMBER UL GYPSUM ASSOCIATION ETC
  
 4) SHEET A2 DOES INDICATE THE WIND DESIGN CRITERIA, BUT
 THE PRESSURES ARE NOT PROVIDED FOR WINDOWS AND DOORS.
 PLEASE PROVIDE IN VASD TO COORESPOND TO THE PRESSURES
 IN THE PRODUCT APPROVALS. 2014 FBC-B 1603.1.4 WIND
 DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE: 5. DESIGN WIND PRESSURES TO BE USED FOR
 EXTERIOR COMPONENT AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL RESPONSIBLE FOR THE DESIGN OF THE
 STRUCTURE, PSF (KN/ M2).
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-12-02 Cont ID  
Sent By albarran Date 2015-12-02 Time 19:42 Rev Time 0.00
Received By albarran Date 2015-12-02 Time 19:33 Sent To I
Notes
2015-12-02 19:43:22ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-02 Cont ID  
Sent By albarran Date 2015-11-02 Time 16:38 Rev Time 0.00
Received By albarran Date 2015-11-02 Time 15:48 Sent To I
Notes
2015-11-02 16:38:18THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION
 OF THE FBC, (FLORIDA BUILDING CODE) AS APPLICABLE AND
 BELOW ARE THE DEFICIENCIES NOTED.
 THOUGH THE PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 ADDRESSED, THE NEW PLANS HAVE A COUPLE OF ITEMS NEEDING
 CORRECTION:
 1. THE APPLICABLE CODES IN EFFECT FOR THIS JOB ARE THE
 5TH EDITION OF THE FBC 2014, & THE 2011 EDITION OF THE
 NEC. CODES ARE INCORRECTLY REFERENCED THROUGHOUT.
 2. THE MINIMUM WORKING SPACE ABOUT ELECTRICAL EQUIPMENT
 REQUIRED BY NEC 110.26 IS ENCROACHED AT THE ELECTRIC
 WATER HEATER. IT DOES NOT APPEAR THAT THE REQUIRED
 SPACING CAN BE OBTAINED IF PLACED ADJACENT TO THE
 STACKABLE WASHER/DRYER.
 3. RECEPTACLE SPACING SHALL BE AS DEFINED BY NEC
 210.52; THEREFORE THERE IS A MISSING RECEPTACLE IN THE
 LIVING ROOM ON THE WALL BENEATH THE ELECTRICAL SWITCHES
 AND IN THE BEDROOM ON THE OUTSIDE OF THE HVAC CLOSET.
 4. OUTDOOR RECEPTACLES IN ADDITION TO REQUIRING AN
 IN-USE TYPE COVER, PER NEC 406.8 THE DEVICE SHALL BE
 LISTED AS WEATHER-RESISTANT ?WR?.
 5. NEC 314.27 HAS SPECIFIC WEIGHT REQUIREMENTS FOR
 LUMINAIRE OUTLETS IN CEILING. OUTLET BOXES SHALL BE
 LISTED SUPPORT A MINIMUM OF 50# AND PADDLE FAN BOXES BE
 LISTED FOR THE PURPOSE.
 6. CONDUCTOR INSULATION WHEN INSIDE AN UNDERGROUND
 RACEWAY SHALL BE RATED FOR WET LOCATION.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-09-04 Cont ID  
Sent By fmittner Date 2015-09-04 Time 10:01 Rev Time 0.00
Received By fmittner Date 2015-09-04 Time 10:01 Sent To  
Notes
2015-09-04 10:02:09WINDOWS SHALL BE WHITE FRAMES, CLEAR OR LOW E GLASS.
2015-08-24 10:50:088/24/15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-02 Cont ID  
Sent By albarran Date 2015-12-02 Time 19:43 Rev Time 0.00
Received By albarran Date 2015-11-17 Time 09:21 Sent To  
Notes
2015-12-02 19:46:5012/2/15 PASSED ELECTRICAL REVIEW AND IS READY FOR
 ISSUANCE. SAK NOTIFIED VIA EMAIL. SENT TO LARGE READY
 BIN "S". MA
2015-11-18 09:22:13B19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-02 Cont ID  
Sent By albarran Date 2015-11-02 Time 16:42 Rev Time 0.00
Received By albarran Date 2015-08-19 Time 13:16 Sent To  
Notes
2015-11-02 16:43:1611/2/15 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT FILE TO SMALL DENIED BIN "S".
 MA
2015-08-19 13:16:36B19

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-10-16 Cont ID  
Sent By ccole Date 2015-10-16 Time 16:15 Rev Time 0.00
Received By ccole Date 2015-10-16 Time 16:15 Sent To  
Notes
2015-10-14 13:43:40MID CYCLE SINGLE TRADE RE-RUB, OK SAK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-09-11 Cont ID  
Sent By ccole Date 2015-09-11 Time 07:40 Rev Time 0.00
Received By ccole Date 2015-09-11 Time 07:27 Sent To  
Notes
2015-09-11 08:43:211ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #15080670
 9/11/15
  
 1) REFER TO SECTION 809 FBC EXISTING BUILDING AND
 PROVIDE MECHANICAL PLANS, DETAILS, AND SPECIFICATIONS
 INCLUDING:
 A) MINIMUM VENTILATION CALCULATIONS FOR THE RENOVATED
 UNITS IN COMPLIANCE WITH TABLE 403.3 FBC-14 MECHANICAL.
 B) AC EQUIPMENT SCHEDULES.
 C) AC COOLING AND HEATING CALCULATIONS- SEE SECTION
 403.6.1 FBC-14 ENERGY CONSERVATION.
 D) ENERGY COMPLIANCE CALCULATIONS- SEE SECTION R101.4.3
 & TABLE R101.5.1 FBC-14 ENERGY CONSERVATION.
 E) AHRI CERTIFICATES.
 F) AC DUCT LAYOUT PLANS FOR EACH UNIT INDICATING THE
 TYPE AND SIZE OF DUCTS, SUPPLY CFM'S AT EACH DIFFUSER,
 MEANS OF RETURN AIR INCLUDING DIMENSIONS OF RETURN AIR
 GRILLS.
 G) AIR DISTRIBUTION SCHEDULE INDICATING THE TYPES AND
 SIZES OF DIFFUSERS AND GRILLS.
 H) CONDENSATE DISPOSAL PLANS- PRIMARY AND SECONDARY FOR
 EACH NEW AIR HANDLER- SEE SECTION 307 FBC-14
 MECHANICAL.
 I) WIND LOAD TIE DOWN ENGINEERING FOR MOUNTING THE AC
 CONDENSERS TO THE NEW PADS- SEE SECTION 301.15 FBC-14
 MECHANICAL.
 2) INDICATE ON THE PLANS HOW OUTSIDE AIR WILL BE
 PROVIDED TO EACH OF THE NEW AIR HANDLERS.- SEE SECTION
 R403.5.2 FBC ENERGY CONSERVATION.
 3) REFER TO SECTION 602 FBC-14 MECHANICAL AND SHOW
 COMPLIANCE FOR MATERIALS USED INSIDE THE AIR HANDLER
 CLOSETS INCLUDING THE TYPES OF CLOSET DOORS TO BE
 INSTALLED.
 4) REFER TO SECTION 603.1.1 AND PROVIDE A DIMENSIONED
 SECTION VIEW TO VERIFY ADEQUATE SPACE WILL BE PROVIDED
 IN THE AIR HANDLER CLOSETS.
 5) PROVIDE BATHROOM EXHAUST DETAILS: EXHAUST FAN
 EQUIPMENT SCHEDULES, EXHAUST DUCT RUNS AND TERMINATION
 LOCATIONS.
 6) PROVIDE DRYER EXHAUST AND MAKEUP AIR PLANS PER
 SECTION 504: SHOW THE TYPE AND SIZE OF EXHAUST DUCT,
 EXHAUST DUCT RUN AND TERMINATION LOCATION, AND INDICATE
 HOW MAKEUP AIR WILL BE SUPPLIED TO EACH DRYER.
 7) REFER TO SECTION 505 FBC-14 MECHANICAL AND PROVIDE
 KITCHEN EXHAUST VENTILATION PLANS.
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE AC
 SYSTEMS AND THE DRYERS.
 PLEASE NOTE ADDITIONAL COMMENTS MAY FOLLOW SUBMITTAL OF
 REVISED PLANS AND RESPONSES TO ALL BUILDING DEPARTMENT
 COMMENTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-11-21 Cont ID  
Sent By tklarge Date 2015-11-21 Time 06:54 Rev Time 0.00
Received By tklarge Date 2015-11-21 Time 06:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-09-14 Cont ID  
Sent By tklarge Date 2015-09-14 Time 06:52 Rev Time 0.00
Received By tklarge Date 2015-09-14 Time 06:41 Sent To  
Notes
2015-09-14 06:52:511) SHT. A-1 REFERS TO THE 2010 FBC. TTHE CODE IN EFFECT
 IS THE 2014 FBC. REVISE THE NOTE.
 2) SHT. A-2/P-1 - SANITARY RISER DIAGRAM - THE WASHING
 MACHINES SHALL CONNECT TO A MINIMUM 3 INCH FIXTURE
 BRANCH OR STACK. THE RISER DIAGRAM SHOWS THE WASHING
 MACHINE DISCHARGING TO A 2 INCH FIXTURE BRANCH. 2014
 FBC-PLUMBING SEC. 406.2.
 3) SUBMIT MANUF. SPECIFICATIONS FOR THE TANKLESS WATER
 HEATERS. WPB AMEND. TO FBC SEC. 107.2.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  