Plan Review Details - Permit 15080653
Plan Review Stops For Permit 15080653
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-11-07 Cont ID  
Sent By jwitmer Date 2015-11-07 Time 06;59 Rev Time 0.00
Received By jwitmer Date 2015-11-07 Time 06:18 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-14 Cont ID  
Sent By jwitmer Date 2015-10-14 Time 11:02 Rev Time 0.00
Received By jwitmer Date 2015-10-14 Time 07:31 Sent To  
Notes
2015-10-14 11:02:19BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080653
 ADD: 1819 OKEECHOBEE RD.
 CONT: GLOBAL CONSTRUCTION ASSOCIATES
 TEL: (954)971-1810
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. OCT. 14/2015
 ACTION: DENIED
  
 1) COVERSHEET ?T:
  
 1) COMPLIED.
  
 2) SHEET A1.1:
  
 2A) COMPLIED.
  
 2B) 2ND REQUEST. PLEASE PROVIDE A LIFE SAFETY PLAN FOR
 THIS TENANT, IN THE TRAINING ROOM WITH A OCCUPANT LOAD
 OF 72 REQUIRES (2) MEANS OF EGRESS.2014 FBC-B TABLE
 1015.1 BUSINESS OCCUPANCY MAXIMUM OCCUPANTS WITH ONE
 EXIT IS 49. THE RESPONSE THE 2ND MEANS OF EGRESS IS
 THROUGH THE SMALL PARTS ROOM 100, THROUGH A RATED WALL.
 THE SMALL PARTS ROOM # 100 IS A S2 OCCUPANCY, THIS IS
 THE REASON FOR THE FIRE RATING OF THE WALL PER TABLE
 508.4. 2014 FBC-B 1014.2 1014.2.1 EGRESS THROUGH
 INTERVENING SPACES. EXCEPTIION: MEANS OF EGRESS ARE NOT
 PROHIBITED THROUGH ADJOINING OR INTERVENING ROOMS OR
 SPACES IN A GROUP H, S OR F OCCUPANCY WHEN THE
 ADJOINING OR INTERVENING ROOMS OR SPACES ARE THE SAME
 OR A LESSER HAZARD OCCUPANCY GROUP. TABLE 508.4 DOES
 NOT REQUIRE OCCUPANCY SEPARATION BETWEEN B, F-1, M & S1
 OCCUPANCIES. THE PARTS ROOM IT APPEARS WOULD FALL INTO
 THE S-2 CATEGORY REQUIRING THE 1 HOUR SEPARATION WHEN
 FIRE SPRINKLERED.
  
  
 2C) COMPLIED.
  
 2D) SEMI-COMPLIED. DISCREPANCY IN PLANS SHEET A1.1
 VERSES A2.1. THE LIFE SAFETY PLANS SHOWS THERE IS NO
 LONGER A RATING BETWEEN ROOMS 103 & 104, WHERE AS A1.1
 STILL SHOWS A RATED WALL. THE MATERIAL LEGEND FOUND ON
 A1.1 UNDER THE HEAING EXISTING FIRE RATED WALLS :
 EXISTING FIRE RATED WALLS & REPAIR AS REQUIREDTO
 MAINTAIN FIRE RATING. 107.2.1.3. ADDITIONAL INFORMATION
 IS REQUIRED.
  
 COMMENT FROM 1ST REVIEW. THE EXISTING (1) HOUR FIRE
 RATED WALL BETWEEN WARE HOUSE 102 & 104 THE PLANS
 INDICATE A NEW 12?-0? WIDE OPENING IN NOTE # 5 FOUND ON
 THIS PLAN. THERE IS NO INFORMATION ON THIS OPENING IN
 THE DOOR SCHEDULE ON SHEET A3.1. NOTE SHEET A1.1 WALL
 LEGEND INDICATES THIS WALL TO BE A (1) HOUR FIRE RATED
 WALL.
  
 3) COMPLIED. WELDING CERTIFICATE FOR DAVID ORTIGOZA.
  
 4)SEMI-COMPLIED. NOA 15-0218.11 NOT REVIEWED BY THE
 DESIGNER OF RECORD, BEWARE OF ISSUE. SHEET SHEET 5 OF 5
 INDICATES THE RESTRAINT BRACKET FROM THE ROOF CURB TO
 ATTACH TO THE RTU. SHEET 2 OF 5, INDICATES THE USE OF
 (7) # 10 TEK SCREWS PER RETRAIN BRAKET.
 NOTE: WHERE THE NOA SHOWS THE # 10 TEK SCREWS THE
 RESTRAINT BRAKET DOES NOT ATTACH!!! IF THE TEK SCREWS
 ARE INSTALLED ON TOP OF THE CURB AS DEPICTED ON SHEET 5
 OF 5 THE VALUE FOR PULL OUT WILL BE LESS BECAUSE THEY
 ARE NO LONGER IN SHEER!!!! PLEASE EXAMINE CLOSELY.
  
 COMMENT FROM 1ST REVIEW. SHEET A3.2 DETAIL # A6 & M6.1
 BOTH SHOW NEW OR REPOSITIONED ROOF TOP CURBS BEING
 INSTALLED ON THE ROOF. PLEASE SUBMIT PRODUCT APPROVALS
 FOR THE NEW CURBS. 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES/ ROOF TOP CURBS
  
 5) SECOND REQUEST. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS.
  
 6) COMPLIED. 2014 FBC-B 1603.1.4 WIND DESIGN CRITERIA.
  
 7) SEMI -COMPLIED. NO PRODUCT APPROVALS WERE SUBMITTED
 FOR THE EXHAUST FAN NOR CURB. SHEET M6.1.THE PLANS WILL
 NEED TO SUPPLY THE CONNECTION OF THE RTU UNITS AND
 EXHAUST FANS TO THE ROOF TOP CURBING, TO RESIST THE
 EFFECTS OF UPLIFT, SLIDING AND OR OVERTURNING MOMENT.
 2014 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-01 Cont ID  
Sent By jwitmer Date 2015-09-01 Time 07:28 Rev Time 0.00
Received By jwitmer Date 2015-09-01 Time 06:25 Sent To  
Notes
2015-09-01 07:23:55 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080653
 ADD: 1819 OKEECHOBEE RD.
 CONT: GLOBAL CONSTRUCTION ASSOCIATES
 TEL: (954)971-1810
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 01/2015
 ACTION: DENIED
  
 1) COVERSHEET ?T:
  
 1A) INDICATES THE PLANS WERE DESIGNED TO THE 2010 FBC,
 PLEASE NOTE THE 2014, 5TH EDITION WAS ADOPTED STATEWIDE
 JUNE 30/ 2015. PLEASE UPDATE PLANS.
  
 1B) THE CONSTRUCTION TYPE IS LISTED AS A BLDG TYPE IV
 THE ORIGINAL BUILDING WAS BUILT UNDER THE 2001 FBC-B.
 THAT CODE AND BUILDING TYPE IS THE EQUAL TO UNDER THE
 2014 FBC-B IIB. PLEASE UPDATE PLANS.
  
 2) SHEET A1.1:
  
 2A) THE TRAINING ROOM IS APPROXIMATELY 1430 SQ. FT./ 20
 SQ. FT. NET= 72 OCCUPANT LOAD. SEE THE 2014 FBC-B TABLE
 1014.1.2.
  
 2B) PLEASE PROVIDE A LIFE SAFETY PLAN FOR THIS TENANT,
 IN THE TRAINING ROOM WITH A OCCUPANT LOAD OF 72
 REQUIRES (2) MEANS OF EGRESS.
 2014 FBC-B TABLE 1015.1 BUSINESS OCCUPANCY MAXIMUM
 OCCUPANTS WITH ONE EXIT IS 49.
 2014 FBC-B TABLE 1016.2 EXIT ACCESS TRAVEL
  
 2C) THE EXISTING (1) HOUR FIRE RATED WALL BETWEEN WARE
 HOUSES 103 & 104 INDICATES IN THE WALL LEGEND A (1)
 HOUR FIRE RATED WALL TO REMAIN. IN THIS WALL THERE IS A
 DOOR IDENTIFIED AS ER1, THE DOOR SCHEDULE FOUND ON
 SHEET A3.1 INDICATES IN THE DOOR NOTES THIS DOOR IS TO
 BE RELOCATED. WHAT IS GOING TO HAPPEN IN THIS OPENING
 IN THE RATED WALL, IS IT TO BE CLOSED UP? 2014 FBC-B
 716.5/ TABLE 716.5 FIRE DOOR AND SHUTTER ASSEMBLIES.
  
 2D) THE EXISTING (1) HOUR FIRE RATED WALL BETWEEN WARE
 HOUSE 102 & 104 THE PLANS INDICATE A NEW 12?-0? WIDE
 OPENING IN NOTE # 5 FOUND ON THIS PLAN. THERE IS NO
 INFORMATION ON THIS OPENING IN THE DOOR SCHEDULE ON
 SHEET A3.1. NOTE SHEET A1.1 WALL LEGEND INDICATES THIS
 WALL TO BE A (1) HOUR FIRE RATED WALL.
  
 3) SHEET A3.2 DETAIL # A6 INDICATES IN ROOF TOP A/C
 CURB INSTALLATIONS? WITH NEW STEEL FRAMING MEMBERS
 BEING WELDED INTO PLACE. PLEASE NOTE THE FRAMING AND
 WELDED CONNECTIONS WILL REQUIRE A 3RD PARTY TO CERTIFY
 WORK COMPLETED IN THIS AREA OR A RESIDENT INSPECTOR
 ONSITE WITH PAPERWORK FILED WITH CITY BEFORE PERMIT
 ISSUANCE, PLEASE INDICATE IN WRITING YOUR CHOICE.
 RESIDENT INSPECTOR FORMS MUST BE FILED OUT AND RETURNED
 FOR REVIEW.
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 110.3.9.
 SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES
 WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE
 BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED
 ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER
 CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH
 INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS
 INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
  
 3A) 110.4 INSPECTION AGENCIES. THE BUILDING OFFICIAL IS
 AUTHORIZED TO ACCEPT REPORTS OF APPROVED INSPECTION
 AGENCIES, PROVIDED SUCH AGENCIES SATISFY THE
 REQUIREMENTS AS TO QUALIFICATIONS AND RELIABILITY.
  
 3B) 110.5 INSPECTION REQUESTS. IT SHALL BE THE DUTY OF
 THE HOLDER OF THE BUILDING PERMIT OR THEIR DULY
 AUTHORIZED AGENT TO NOTIFY THE BUILDING OFFICIAL WHEN
 WORK IS READY FOR INSPECTION. IT SHALL BE THE DUTY OF
 THE PERMIT HOLDER TO PROVIDE ACCESS TO AND MEANS FOR
 INSPECTIONS OF SUCH WORK THAT ARE REQUIRED
 BY THIS CODE.
  
 3C) 110.6 APPROVAL REQUIRED. WORK SHALL NOT BE DONE
 BEYOND THE POINT INDICATED IN EACH SUCCESSIVE
 INSPECTION WITHOUT FIRST OBTAINING THE APPROVAL OF THE
 BUILDING INSPECTOR. THE BUILDING OFFICIAL, UPON
 NOTIFICATION, SHALL MAKE THE REQUESTED INSPECTIONS AND
 SHALL EITHER INDICATE THE PORTION OF THE CONSTRUCTION
 THAT IS SATISFACTORY AS COMPLETED, OR NOTIFY THE PERMIT
 HOLDER OR HIS OR HER AGENT WHEREIN THE SAME FAILS TO
 COMPLY WITH THIS CODE. ANY PORTIONS THAT DO NOT COMPLY
 SHALL BE CORRECTED AND SUCH PORTION SHALL NOT BE
 COVERED OR CONCEALED UNTIL AUTHORIZED BY THE BUILDING
 OFFICIAL.
  
 4) SHEET A3.2 DETAIL # A6 & M6.1 BOTH SHOW NEW OR
 REPOSITIONED ROOF TOP CURBS BEING INSTALLED ON THE
 ROOF. PLEASE SUBMIT PRODUCT APPROVALS FOR THE NEW
 CURBS. 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES/ ROOF TOP CURBS
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS.
  
 6) THE PLANS DO NOT PROVIDE THE WIND DESIGN CRITERIA
 FOR THE ROOF TOP CURBS. 2014 FBC-B 1603.1.4 WIND DESIGN
 DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 6.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 6.2. RISK CATEGORY.
  
 6.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 6.. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 6.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 7) THE PLANS WILL NEED TO SUPPLY THE CONNECTION OF THE
 RTU UNITS AND EXHAUST FANS TO THE ROOF TOP CURBING, TO
 RESIST THE EFFECTS OF UPLIFT, SLIDING AND OR
 OVERTURNING MOMENT. 2014 FBC-B 1609.6.4.4.1 COMPONENTS
 & CLADDING
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-09-21 Cont ID  
Sent By skennedy Date 2015-09-21 Time 12:15 Rev Time 0.00
Received By skennedy Date 2015-09-21 Time 12:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-24 Cont ID  
Sent By fstal Date 2015-08-24 Time 08:47 Rev Time 0.00
Received By fstal Date 2015-08-24 Time 08:38 Sent To  
Notes
2015-08-24 08:44:36FIRE ALARM CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR
 APPROVAL.
 FIRE SPRINKLER CONTRACTOR SHALL SUBMIT SHOP DRAWINGS
 FOR APPROVAL. (NOTE RACK SYSTEM INDICATED ON DRAWINGS.)

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-11-09 Cont ID  
Sent By ccole Date 2015-11-09 Time 09:04 Rev Time 0.00
Received By ccole Date 2015-11-06 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-19 Cont ID  
Sent By skennedy Date 2015-10-19 Time 12:15 Rev Time 0.00
Received By skennedy Date 2015-10-06 Time 15:53 Sent To  
Notes
2015-10-06 15:53:16C11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-21 Cont ID  
Sent By skennedy Date 2015-09-21 Time 12:15 Rev Time 0.00
Received By skennedy Date 2015-08-18 Time 16:07 Sent To  
Notes
2015-08-18 16:07:17C27

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-11-09 Cont ID  
Sent By ccole Date 2015-11-09 Time 09:04 Rev Time 0.00
Received By ccole Date 2015-11-09 Time 09:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-10-19 Cont ID  
Sent By ccole Date 2015-10-19 Time 09:46 Rev Time 0.00
Received By ccole Date 2015-10-19 Time 09:46 Sent To  
Notes
2015-10-19 10:16:532ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080653
 10/19/15
  
 1) THE 5600 SF CONDITIONED AREA LISTED ON ENERGY FORM
 506-2014 DOES NOT APPEAR TO MATCH THE SQUARE FOOT AREA
 SHOWN ON SHEET M6.1 AS MEASURED BY SCALE. PLEASE
 PROVIDE COMPLETE FLOOR PLAN DIMENSIONS ON THE PLAN.
 2) THE WIND LOAD DESIGN CRITERIA ON SHEET A3.1
 INDICATES -72.5 PSF DESIGN PRESSURE AT THE ROOF. PLEASE
 CLARIFY WHICH RTU THIS PRESSURE IS APPLICABLE TO- THE
 RELOCATED RTU # 1-1 OR THE NEW RTU-3.
 3) THE SUBMITTED N0A #15-0218.11 (STEEL CURB FOR
 CARRIER RTU'S) INDICATES ON SHEET 1 OF 5 THAT IT IS
 "ACCEPTABLE FOR ALL CARRIER UNITS WITH THE FOLLOWING
 MODEL NUMBERS- 48/50XXYY". IT APPEARS THAT THE NOA MAY
 BE APPLICABLE FOR THE NEW RTU-3 (50TC*D12-6), HOWEVER
 EVIDENCE MUST BE PROVIDED TO VERIFY THE CURB CAN BE
 USED FOR THE RELOCATED RTU #1-1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-27 Cont ID  
Sent By ccole Date 2015-08-27 Time 08:01 Rev Time 0.00
Received By ccole Date 2015-08-27 Time 08:01 Sent To  
Notes
2015-08-27 08:23:351ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 CODES
 PERMIT #15080653
 8/27/15
  
 1) COVER SHEET T: PLEASE UPDATE ALL 2010 CODE
 REFERENCES LISTED UNDER PROJECT DATA- THE 2014 FIFTH
 EDITION OF THE FLORIDA BUILDING CODES WENT INTO EFFECT
 ON JUNE 30, 2015.
 2) REFER TO SECTION 809 FBC-14 EXISITING BUILDING CODE-
 TWO WAREHOUSE/OFFICE SUITES ARE NOW BEING COMBINED
 (SUITE NUMBERS NOT SHOWN ON PLANS) AND NEW ENLARGED
 CONDITIONED SPACES ARE BEING CONSTRUCTED. PLEASE
 PROVIDE THE FOLLOWING COMPLIANCE INFORMATION AS
 REQUIRED BY THE FLORIDA ENERGY CONSERVATION CODE:
 A) SUBMIT TWO SETS OF AC LOAD CALCULATIONS FOR THE NEW
 SPACES BEING CONDITIONED BY RTU'S 1, 1-1, 2, & 3. REFER
 TO SECTION C403.2.1 CALCULATION OF HEATING AND COOLING
 LOADS.
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAEHVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 B) SUBMIT TWO SETS OF ENERGY CALCULATIONS PER THE
 FOLLOWING CODE SECTIONS: C101.4.4 CHANGE IN OCCUPANCY
 OR USE.
 SPACES UNDERGOING A CHANGE IN OCCUPANCY THAT WOULD
 RESULT IN AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL
 OR ELECTRICAL ENERGY SHALL COMPLY WITH THIS CODE. WHERE
 THE USE IN A SPACE CHANGES FROM ONE USE IN TABLE
 C405.5.2(1) OR (2) TO ANOTHER USE IN TABLE C405.5.2(1)
 OR (2), THE INSTALLED LIGHTING WATTAGE SHALL COMPLY
 WITH SECTION C405.5.
 C101.4.5 CHANGE IN SPACE CONDITIONING.
 ANY NONCONDITIONED SPACE THAT IS ALTERED TO BECOME
 CONDITIONED SPACE SHALL BE REQUIRED TO BE BROUGHT INTO
 FULL COMPLIANCE WITH THIS CODE.
 3) SHEET M6.1: PLEASE CLARIFY THE SEQUENCE OF OPERATION
 RELATING TO FAN SHUT DOWN OF THE AC SYSTEMS. WILL THE
 SYSTEMS ALLL BE LINKED TOGETHER?
 4) SHEETS A6 & M7.1: PROVIDE THE WIND LOAD DESIGN
 CRITERIA FOR INSTALLATION OF THE RTU'S, RTU CURBS, AND
 EF-1-1. REVIEW SECTIONS 301.5 FBC-14 MECHANICAL, AND
 SECTION 1609 FBC-14 BUILDING. PROVIDE DESIGN PRESSURES
 ON THE PLAN -LATERAL AND UPLIFT- AND COMPLETE
 INSTALLATION DETAILS.
 5) SHUTOFF DAMPER CONTROLS FOR ALL RTU- O/A SUPPLIES IS
 REQUIRED IN ACCORDANCE WITH C403.2.4.4. VERIFY
 COMPLIANCE FOR ALL UNITS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-08-31 Cont ID  
Sent By gjohnson Date 2015-08-31 Time 09:32 Rev Time 0.00
Received By gjohnson Date 2015-08-31 Time 09:32 Sent To  
Notes
***NONE***