Plan Review Details - Permit 15080635
Plan Review Stops For Permit 15080635
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-10-29 Cont ID  
Sent By jwitmer Date 2015-10-29 Time 13:17 Rev Time 0.00
Received By jwitmer Date 2015-10-29 Time 12:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-10-08 Cont ID  
Sent By jwitmer Date 2015-10-08 Time 16:57 Rev Time 0.00
Received By jwitmer Date 2015-10-08 Time 16:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-01 Cont ID  
Sent By jwitmer Date 2015-09-01 Time 13:35 Rev Time  
Received By jwitmer Date 2015-09-01 Time 08:12 Sent To  
Notes
2015-09-01 08:25:54 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080635
 ADD: 312 CLEMATIS ST. / 1ST FLOOR
 CONT: COMPLETE HOME IMPROVEMENT
 TEL: (954)636-2238
 E-MAIL: ?????????????????????
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 01/ 2015
 ACTION: DENIED
  
 BUILDING BUILT IN 1919
  
 1) SHEET A1:
  
 1A) 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.5.1.1
 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS.
 MINIMUMTYPE OF CONSTRUCTION SHALL BE DETERNINED FBC-B
 TABLE 503. 3 STORIES + MEZANINE
  
 SPRINKLERED OR NOT, AREA OR HEIGHT INCREASE TAKEN?
  
 LIFE SAFETY PLANS TO INCLUDE;
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT PASSAGEWAY
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS RATED
 EMERGENCY LIGHTING AND EXIT SIGNS
 CONSTRUCTION REQUIREMENTS FIRE RATED EXIT ENCLOSURES
  
 FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE
 THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS EXTERIOR WALLS TABLE 601 &
 602
  
 1B) 2014 FBC-EXISITNG BUILDING CODE THE DESIGNER OF
 RECORD WILL NEED TO CLARIFY HOW THE PLANS WERE
 DEVELOPED FBC-EXST. BLDG. CODE 301.1 ALSO REVIEW
 1001.3.1 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION, SECTION 1012 SHALL APPLY.
  
  
 1012.1.2 FIRE PROTECTION AND INTERIOR FINISH.
 THE PROVISIONS OF SECTIONS 1012.2 AND 1012.3 FOR FIRE
 PROTECTION AND INTERIOR FINISH, RESPECTIVELY, SHALL
 APPLY TO ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION
  
 1012.2 FIRE PROTECTION SYSTEMS.
 FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTIONS 1012.2.1 AND 1012.2.2.
  
 1012.2.1 FIRE SPRINKLER SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
  
 1012.2.2 FIRE ALARM AND DETECTION SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES A FIRE ALARM AND DETECTION SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION
 APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT
 THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A
 FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL
 BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED.
  
  
 2A) SHEET A1 VERSES THE SHEET M1. THE MEZZANINE
 STAIRWELL MID LEVEL APPEARS TO HAVE MECHANICAL
 EQUIPMENT. PLEASE PROVIDE CODE COMPLIANCE OF 1 HOUR
 1009.9.3 ENCLOSURES UNDER INTERIOR STAIRWAYS. THE WALLS
 AND SOFFITS WITHIN ENCLOSED USABLE SPACES UNDER
 ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE PROTECTED BY
 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION OR THE
 FIRE-RESISTANCE RATING OF THE STAIRWAY ENCLOSURE,
 WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED SPACE
 SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR ENCLOSURE.
  
 2B) SHEET A1 VERSES THE SHEET M1. THE MEZZANINE
 STAIRWELL MID LEVEL APPEARS TO HAVE MECHANICAL
 EQUIPMENT.THE PLANS ARE NOT CLEAR AS TO THE EAST WALL
 MID LANDING WHERE THE MECHANICAL SHEETS SHOW VERTICAL
 A/C DUCTS. IS THIS A WALL SEPERATING THE MECHANICAL
 DUCTWORK FROM THE STIRWELL? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By albarran Date 2015-12-21 Time 19:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-11-02 Cont ID  
Sent By albarran Date 2015-11-02 Time 15:31 Rev Time 0.00
Received By albarran Date 2015-11-02 Time 15:13 Sent To I
Notes
2015-11-02 15:33:29FOLLOWED THE SUBMITTED NARRATIVE AND FOUND THAT ALL
 PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-10-14 Cont ID  
Sent By albarran Date 2015-10-14 Time 16:07 Rev Time 0.00
Received By albarran Date 2015-10-14 Time 13:15 Sent To I
Notes
2015-10-14 16:08:05PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. THE DRAWINGS AS SUBMITTED ARE MISSING SEVERAL EXIT
 LIGHTS AS MENTIONED BELOW: ROOM 102, 103, 105, AT THE
 SOUTH END OF THE WEST CORRIDOR, AT THE EGRESS DOOR OF
 STAIR 203
 2. THERE ARE MISSING EMERGENCY LIGHTS AS INDICATED
 BELOW: AN EXIT/EMERGENCY COMBO AT THE BOTTOM OF STAIR
 111, ROOM 200
 3. NEC 314.27 HAS SPECIFIC WEIGHT REQUIREMENTS FOR
 CEILING OUTLET AND FOR CEILING FAN OUTLETS.
 4. NEC 600.5 REQUIRES THAT THERE BE A DEDICATED OUTLET
 AT EVERY PEDESTRIAN DOOR TO EVERY COMMERCIAL
 ESTABLISHMENT FOR SIGN PURPOSES.
 5. NEC 422.52 REQUIRES THAT THE CIRCUIT FOR THE EWC
 (DRINKING FOUNTAIN) BE GFCI PROTECTED.
 6. ALL FIRE ALARM WORK SHALL BE PERFORMED UNDER A
 SEPARATE AND STAND ALONE PERMIT.
 WHEN RESUBMITTING, YOU SHALL PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH COMMENT ITEM ALONG WITH THE
 CITY?S RE-SUBMITTAL FORM. SEE LINK BELOW:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
 ADDITIONALLY, IT IS REQUIRED THAT YOU INSERT THE
 CORRECTED PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID
 THE PREVIOUSLY REVIEWED SHEETS AND LEAVE IN FOR
 COMPARATIVE REVIEW.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-09-17 Cont ID  
Sent By ppetty Date 2015-09-17 Time 11:10 Rev Time 0.00
Received By ppetty Date 2015-09-17 Time 09:48 Sent To  
Notes
2015-09-17 10:32:20ELECTRICAL NOTES ON SHEET A-3
 NOTE EXISTING ON PLAN
 PP

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-10-29 Cont ID  
Sent By pleduc Date 2015-10-29 Time   Rev Time 0.00
Received By pleduc Date 2015-10-29 Time 10:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-10-06 Cont ID  
Sent By pleduc Date 2015-10-06 Time   Rev Time 0.00
Received By pleduc Date 2015-10-06 Time 15:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-08-20 Cont ID  
Sent By pleduc Date 2015-08-20 Time   Rev Time 0.00
Received By pleduc Date 2015-08-20 Time 13:30 Sent To  
Notes
2015-08-20 14:36:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A1, THERE IS A NOTE INDICATING STEEL STAIR NOT
 AN EXIT, YET ON SHEET E1, THERE IS AND EXIT SIGN AT THE
 STAIR. PLEASE CLARIFY.
  
 2) SHEET A1 , DOUBLE DOORS 102A AND 103A INDICATE THEY
 OPEN INTO THE EXIT CORRIDOR, SHEET E1 SHOW SOME TYPE OF
 EQUIPMENT AND OTHER DOORS OPENING ALONG THE CORRIDOR
 WALL.
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 PLEASE PROVIDE ACCURATE DIMENSIONS ALONG THE CORRIDOR
 MEETING THE ABOVE REQUIREMENTS.
  
 3) SHEET A6, ON THE DOOR SCHEDULE IT INDICATES DOOR
 STOPS ON DOORS 102A AND 103A, BASED ON THE ABOVE DOOR
 STOPS SHALL NOT BE INSTALLED ON THESE DOORS. THEY SHALL
 ALSO OPEN FULLY TO WITHIN THE 7IN. NOTED ABOVE.
  
 4) SHEET A1, INDICATES AREA 203 AS EXISTING STAIR AND
 APPEARS TO BE THE REQUIRED EXIT FROM THE MEZZANINE. NO
 DETAIL IS PROVIDED FOR THIS EXIT STAIR AND NO EXIT
 DISCHARGE IS INDOCATED. PLEASE CLARIFY.
  
 5) SHEET A1, PROVIDE NOTE INDICATING THE PROPOSED
 PROJECT SHALL MEET THE REQUIREMENTS OF THE 5TH EDITION
 OF FLORIDA FIRE PREVENTION CODE INCLUDING THE 2012
 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER APPLICABLE
 CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 6) COMPLETE LIFE SAFETY PLANS SHALL BE PROVIDED THAT
 ILLUSTRATE OCCUPANT LOADS, TRAVEL DISTANCES, COMMON
 PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS,
 EMERGENCY LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-11-02 Cont ID  
Sent By albarran Date 2015-11-02 Time 15:34 Rev Time 0.00
Received By albarran Date 2015-10-23 Time 13:18 Sent To  
Notes
2015-11-02 15:37:3011/2/15 PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO LARGE READY BIN "C". MA
2015-10-23 13:18:46C15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-14 Cont ID  
Sent By albarran Date 2015-10-14 Time 16:24 Rev Time 0.00
Received By albarran Date 2015-09-30 Time 14:03 Sent To  
Notes
2015-10-14 16:23:5010/14/15 FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO LARGE DENIED BIN "C". MA
2015-09-30 14:04:14RESUB ROUTED TO C21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-17 Cont ID  
Sent By ppetty Date 2015-09-17 Time 11:11 Rev Time 0.00
Received By ppetty Date 2015-08-18 Time 12:58 Sent To  
Notes
2015-08-18 12:59:17C18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-10-08 Cont ID  
Sent By ccole Date 2015-10-08 Time 15:55 Rev Time 0.00
Received By ccole Date 2015-10-08 Time 15:55 Sent To  
Notes
2015-10-08 15:59:46PERMIT #15080635
 10/8/15
 MECHANICAL PROVISO:
  
 SITE SPECIFIC WIND LOAD ENGINEERING FOR TIE-DOWN OF ALL
 MECHANICAL APPLIANCES AND EQUIPMENT SHALL BE ON-SITE AT
 TIME OF INSPECTION, OR SHALL BE SUBMTTED TO THE
 BUILDING DEPARTMENT FOR REVIEW AND APPROVAL PRIOR TO
 1ST INSPECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-28 Cont ID  
Sent By ccole Date 2015-08-28 Time 11:17 Rev Time 0.00
Received By ccole Date 2015-08-28 Time 11:17 Sent To  
Notes
2015-08-28 12:44:371ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080635
 8/28/15
  
 1) SHEET A1 CODE DATA: PROVIDE THE CLASSIFICATION OF
 THE PROPOSED WORK IN ACCORDANCE WITH THE FLORIDA
 EXISTING BUILDING CODE FIFTH EDITION 2014. REFER TO
 CHAPTER 5 AND INDICATE LEVEL 1, 2, 3, OR CHANGE OF
 OCCUPANCY ON THE PLANS.
 2) REFER TO SECTION C101.4.4 FBC-14 ENERGY
 CONSERVATION: CHANGE IN OCCUPANCY OR USE.
 SPACES UNDERGOING A CHANGE IN OCCUPANCY THAT WOULD
 RESULT IN AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL
 OR ELECTRICAL ENERGY SHALL COMPLY WITH THIS CODE. WHERE
 THE USE IN A SPACE CHANGES FROM ONE USE IN TABLE
 C405.5.2(1) OR (2) TO ANOTHER USE IN TABLE C405.5.2(1)
 OR (2), THE INSTALLED LIGHTING WATTAGE SHALL COMPLY
 WITH SECTION C405.5.
 PLEASE PROVIDE ENERGY CALCULATIONS USING COMPLIANCE
 MATERIALS SPECIFIED IN SECTION C101.5.1.
 3) REFER TO SECTION 809.1 FBC-14 EXISTING BUILDING AND
 PROVIDE AC LOAD CALCULATIONS FOR THE AC SYSTEMS.
 C403.2.1 FBC-14 CALCULATION OF HEATING AND COOLING
 LOADS.
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAEHVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 4) M1: INDICATE HOW ACCESS TO AHU-1 & AHU-2 IS BEING
 PROVIDED. REFER TO THE FOLLOWING CODE SECTIONS AND
 PROVIDE DRAWINGS AND DETAILS VERIFYING COMPLIANCE:
 SECTION 306.1, AND 603.1.1 FBC-14 MECHANICAL.
 5) M1: DUCT SMOKE DETECTORS SHALL BE LOCATED IN THE
 RETURN AIR SYSTEMS OF AHU-1 AND AHU-2 IN COMPLIANCE
 WITH SECTIONS 606.2.1 AND 606.2.2 FBC-14 MECHANICAL.
 PROVIDE A NARRATIVE AND DIAGRAM DESCRIBING CONTROLS
 OPERATION AND SUPERVISION OF THE DETECTORS PER SECTIONS
 606.4 & 606.4.1.
 6) M1: PROVIDE A MEANS OF RETURN AIR FROM THE
 STRETCHING ROOM AND HALLWAY TO AHU-2. SEE SECTION 601.5
 MECHANICAL.
 7) M1: PLEASE CLARIFY WHY AIR FROM THE AHU-1 SUPPLY IN
 THE SYNERGY ROOM IS BEING RETURNED TO AHU-2. SEE
 SECTION 601.5.
 8) M2: PROVIDE SUPPORT AND HANGER DETAILS FOR THE
 FIBROUS DUCTS, THE VAV BOXES, AND THE EXHAUST FANS.
 9) M1 & M2: PROVIDE CONDENSATE DISPOSAL PLANS FOR AHU-1
 & 2, AND THE RTU : SEE SECTION 307.2- 307.2.3 FBC-14
 MECHANICAL.
 10) THE EXHAUST FAN IN THE TOILET/SHOWER ROOM 112 SHALL
 BE MINIMUM 100 CFM PER TABLE 403.3
 11) PROVIDE STRUCTURAL DETAILS, AND THE WIND DESIGN
 CRITERIA AND PRESSURES FOR INSTALLATION OF THE NEW RTU
 ROOF OPENING, THE RTU CURB, AND MOUNTING OF THE RTU-
 REFER TO SECTION 301.15 FBC-14 MECHANICAL.
 12) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE TRANE
 RTU/O/A UNITS, AND THE VAV BOXES.
 13) PROVIDE A FLORIDA PRODUCT APPROVAL OR MIAMI-DADE
 NOA FOR THE EXTERIOR WALL LOUVER- FL. DEPT. OF
 COMMUNITY AFFAIRS RULE 9N-3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-10-29 Cont ID  
Sent By gjohnson Date 2015-10-29 Time 17:06 Rev Time 0.00
Received By gjohnson Date 2015-10-29 Time 17:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-10-08 Cont ID  
Sent By tklarge Date 2015-10-08 Time 12:09 Rev Time 0.00
Received By tklarge Date 2015-10-08 Time 11:28 Sent To  
Notes
2015-10-08 11:47:121) SUBMIT TWO COPIES OF A PLUMBING PLAN, WATER RISER,
 AND SANITARY RISER THAT REFLECTS THE ENTIRE SCOPE OF
 PLUMBING WORK TO BE DONE. WPB AMEND. TO FBC SEC. 107.1.
 THERE WAS NO PLUMBING PLAN IN THE RESUBMITTED SET OF
 PLANS.
 2) SINCE THIS IS A CHANGE OF OCCUPANCY, A MINIMUM OF 2
 DRINKING FOUNTAINS SHALL BE PROVIDED PER THE 2014 FBC-
 ACCESSIBILITY SEC. 211.2.
 3) THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE, NOT TO CENTER AS SHOWN PER THE FBC
 -ACCESS. SEC.609.4.
 4) THE SHOWER CONTROLS SHALL BE LOCATED ON THE SIDE
 WALL OPPOSITE THE SEAT AND SHALL BE LOCATED ON THE
 CONTROL WALL 15 INCHES MAXIMUM FROM THE CENTERLINE OF
 THE SEAT TOWARD THE SHOWER OPENING PER THE 2014
 FBC-ACCESS. SEC.608.5.1. CLEARLY SHOW THIS ON THE
 PLANS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-08-28 Cont ID  
Sent By gjohnson Date 2015-08-28 Time 15:54 Rev Time 0.00
Received By gjohnson Date 2015-08-28 Time 15:54 Sent To  
Notes
2015-08-28 16:03:111ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  
  
 COMMENTS:
  
 1. SHEET A1 INDICATE LEVEL OF ALTERATION PER THE FBC
 EXISTING BUILDING 2014 CHAPTER 5.
 2.AT THIS TIME A COMPLETE REVIEW CAN NOT BE ACCURATELY
 DONE A UNTIL ALTERATION LEVEL IS DETERMENT.