| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15080631 |
| | ADD: 7320 S. DIXIE HWY |
| | CONT: CAL DEVELOPMENT |
| | TEL: (954)564-0655 |
| | E-MAIL:[email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W |
| | * 2014WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. AUGUST 31/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A02.01: |
| | |
| | 1A) DOOR # 100BA NOTE # 2 INDICATES TO INSTALL A NEW |
| | DOOR IN OPENING. NOTE THIS IS NOT CLEAR IF THE DOOR |
| | ONLY IS BEING REPLACED OR IF DOOR AND FRAME. DOOR AND |
| | DOOR FRAME TYPE E2. IF THE DOOR AND FRAME ARE BEING |
| | REPLACED THE N COMPLIANCE WITH: 2014 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | |
| | 1B) 2014 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 1C) EXTERIOR DOOR # 100BA IS BEING REPLACED THEN THE |
| | WIND DESIGN CRITERIA IS REQUIRED. |
| | 2014 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 1C)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 1C)(2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE |
| | 7-10. |
| | |
| | 1C)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 1C)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 1C)(5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| | NEGATIVE TABLE 1609.2(2) . |
| | |
| | 1D) NOTE # 07 INDICATES WALL FINISHES COVE BASE, IS |
| | THIS A NEW WALL? FOR THIS FLOOR THERE IS AREAS LABELED |
| | UNOCCUPIED OFFICES, THERE STILL SHOULD BE A OCCUPANT |
| | LOAD ASSIGNED TO THESE AREAS. IN DOING SUCH PLEASE |
| | PROVIDE WHAT THE OCCUPANT LOAD IS FOR THE SECOND FLOOR. |
| | 2014 FBC-B 302.1. |
| | ALSO SEE 2014 FBC-B TABLE 1018.1. BUSINESS OCCUPANCY |
| | >30 NON-SPRINKLERED 1 HR FIRE RATING. |
| | |
| | 1E) NOTE # 4 INDICATES A NEW PARTITION IN STAIRWELL, |
| | WALL IDENTIFICATION TAG A3A BUT THERE IS NO SUCH WALL |
| | TAG FOUND ON SHEET A00.30. NOTE THIS SHOULD BE A FIRE |
| | RATED PARTITION, STAIRWELLS, 2014 FBC- 1022.2 |
| | CONSTRUCTION. |
| | |
| | 2) IN STAIRWELL DOOR # 100C THE DOOR SCHEDULE INDICATES |
| | NOT FIRE RATED. 2014 FBC-B 1022.2 SEE FIRE RATING |
| | REQUIREMENTS. PLEASE NOTE THIS DOOR SHOULD NOT BE IN |
| | THE STAIRWELL BUT ACCESSED THROUGH FROM THE EXTERIOR |
| | SINCE THIS A DOOR TO A STORAQGE ROOM. SEE 1022.5 |
| | PENETRATIONS. |
| | |
| | 3) NOTE # 8 INDICATES THE USE OF A NEW GUARDRAILS ON |
| | THE UNENCLOSED STAIR A. PLEASE NOTE THIS GUARDRAIL |
| | NEEDED TO BE UPDATED BY ONSITE FIRE INSPECTION. |
| | COMPLIANCE WITH THE 2014 EXISTING BUILDING CODE |
| | 805.10.1 AND 805.10.2. THE DESIGN SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE. PLEASE |
| | REVIEW SECTION 1013.3 & 1013.4 OPENING LIMITATIONS. |
| | THIS AREA IS A BUSINESS OCCUPANCY AN WILL NEED TO |
| | COMPLY WITH NOT ALLOWING A 4 INCH SPHERE NO TO PASS |
| | THROUGH. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |