Plan Review Details - Permit 15080547
Plan Review Stops For Permit 15080547
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-09-26 Cont ID  
Sent By jwitmer Date 2015-09-26 Time 10:14 Rev Time 0.00
Received By jwitmer Date 2015-09-26 Time 09:17 Sent To  
Notes
2015-09-26 09:24:18BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080547
 ADD: 550 S. ROSEMARY AVE. #160
 CONT: DC GREEN, LLC
 TEL: (772)919-1412
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. SEPT. 26/2015
 ACTION: PROVISO/ RED LINED
  
 1A) S HEET A130.1 EXTERIOR WALLS SHOW A WALL TAG # 1.
 WALL IDENTIFICATION TAGS FOUND ON SHEET A020.1 AND
 REFERENCES DETAILS 3 & 4 SHEET A400.2. PLEASE NOTE
 THERE ARE 2 ISSUES WITH THIS DETAIL. THE BUILDING IS
 CLASSIFIED AS A BUILDING TYPE IB WHICH DOES NOT ALLOW
 EXTERIOR PLYWOOD. PLEASE REVIEW 2014 FBC-B 603.1.1.3.
 FIRE RETARDANT TREATED WOOD CAN BE USED IN NON-BEARING
 EXTERIOR WALLS.
  
 1B) DETAILS 3 & 4 ON SHEET A400.2 INDICATE THE USE OF
 30 LB. FELT. PLEASE SEE 2014 FBC-B SECTION 2510.6 WHERE
 APPLIED OVER WOOD-BASED SHEATHING, SHALL INCLUDE A
 WATER RESISTIVE VAPOR-PERMEABLE BARRIER WITH A
 PERFORMANCE AT LEAST EQUIVALENT TO TWO LAYERS OF GRADE
 D PAPER. THE INDIVIDUAL LAYERS SHALL BE INSTALLED
 INDEPENDENTLY SUCH THAT EACH LAYER PROVIDES A SEPARATE
 CONTINUOUS PLANE AND ANY FLASHING (INSTALLED IN
 ACCORDANCE WITH SECTION 1405.4) INTENDED TO DRAIN TO
 THE WATER-RESISTIVE BARRIER IS DIRECTED BETWEEN THE
 LAYERS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-09-23 Cont ID  
Sent By jwitmer Date 2015-09-23 Time 15:36 Rev Time 0.00
Received By jwitmer Date 2015-09-23 Time 12:01 Sent To  
Notes
2015-09-23 15:36:42 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080547
 ADD: 550 S. ROSEMARY AVE. #160
 CONT: DC GREEN, LLC
 TEL: (772)919-1412
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. SEPT. 23/2015
 ACTION: DENIED
  
 1) COMPLIED. PLANS WERE NOT STAMPED REVIEWED BY CITY
 PLACE MANAGEMENT THEY WERE REVIEWED AND APPROVED.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) COMPLIED. PERMIT # 15051261 INTERIOR- DEMO. THERE IS
 NO DEMOLISION PLANS INDICATING WHAT IS BEING DEMOED OR
 CHANGED, IS EVERYTHING TO BE CONSIDERED NEW?
 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS. FROM THE LAST KNOWN PERMIT 13010420 THERE IS
 ALOT OF INTERIOR CHANGES FROM THE LAST KNOWN USE AS FAR
 AS LAY OUT AND LIFE SAFETY PLAN. A THOROUGH REVIEW
 CANNOT BE MADE AT THIS TIME, AS A RESULT OF THE
 ADDITIONAL INFORMATION REQUESTED ADDITIONAL COMMENTS
 MAY APPEAR THAT WERE NOT PART OF THIS REVIEW.
  
 3) FOR THE AMOUNT OF CHANGES SEEN FROM THE LAST PERMIT
 (13010420) AND THE PROPOSED LAYOUT THE PERMIT VALUE
 ASSOCIATED WITH THIS DESIGN IS CONSIDERABLY
 LOW,EXTREMELY LOW. PERMIT FEES/ PLAN REVIEW:
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 4) 2ND REQUEST. SHEET A120.1THE MENS RESTROOM APPEARS
 TO HAVE BEEN RENOVATED WITH THE RELOCATION OF THE ENTRY
 WALL OF THE RESTROOM. THE NEW PLANS SHOW THE SAME
 ORIGINAL 4 LAVATORIES AND A LONGER COUNTER TOP. NO WALL
 TAG IDENTIFYING THE WALL TYPE IS PROVIDED ON THE PLANS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 5-6) COMPLIED.
  
 6A) 2ND REQUEST. RESPONSE INDICATES AREA TO BE
 REWORKED. PLEASE NOTE ON SHEET A130.1 EXTERIOR WALLS
 SHOW A WALL TAG # 1. WALL IDENTIFICATION TAGS FOUND ON
 SHEET A020.1 AND REFERENCES DETAILS 3 & 4 SHEET A400.2.
 PLEASE NOTE THERE ARE 2 ISSUES WITH THIS DETAIL. THE
 BUILDING IS CLASSIFIED AS A BUILDING TYPE IB WHICH DOES
 NOT ALLOW EXTERIOR PLYWOOD. PLEASE REVIEW 2014 FBC-B
 603.1.1.3. FIRE RETARDANT TREATED WOOD CAN BE USED IN
 NON-BEARING EXTERIOR WALLS.
  
 6B) DETAILS 3 & 4 ON SHEET A400.2 INDICATE THE US OF 30
 LB. FELT. PLEASE SEE 2014 FBC-B SECTION 2510.6 WHERE
 APPLIED OVER WOOD-BASED SHEATHING, SHALL INCLUDE A
 WATERRESISTIVE VAPOR-PERMEABLE BARRIER WITH A
 PERFORMANCE AT LEAST EQUIVALENT TO TWO LAYERS OF GRADE
 D PAPER. THE INDIVIDUAL LAYERS SHALL BE INSTALLED
 INDEPENDENTLY SUCH THAT EACH LAYER PROVIDES A SEPARATE
 CONTINUOUS PLANE AND ANY FLASHING (INSTALLED IN
 ACCORDANCE WITH SECTION 1405.4) INTENDED TO DRAIN TO
 THE WATER-RESISTIVE BARRIER IS DIRECTED BETWEEN THE
 LAYERS.
  
 1ST REVIEW COMMENT. PLEASE NOTE SHEET A120.1 THE
 PROPOSED PLANS SHOW WORK ON THE EAST AND SOUTH OUTSIDE
 DINING AREA WITH WALLS MOVED, DOORS OPENINGS BEING
 MODIFIED, A NEW OUTSIDE LOUNGE AREA WALLS REMOVED, THE
 KITCHEN NEW COOLERS, OLD ONES MOVED BAR LOCATIONS AND
 WALLS MOVED ETC....
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-08-26 Cont ID  
Sent By jwitmer Date 2015-08-26 Time 14:10 Rev Time 0.00
Received By jwitmer Date 2015-08-26 Time 06:32 Sent To  
Notes
2015-08-26 07:21:51 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080547
 ADD: 550 S. ROSEMARY AVE. #160
 CONT: DC GREEN, LLC
 TEL: (772)919-1412
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 26/2015
 ACTION: DENIED
  
 1) PLANS WERE NOT STAMPED REVIEWED BY CITY PLACE
 MANAGEMENT THEY WERE REVIEWED AND APPROVED. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) THERE IS NO DEMOLISION PLANS INDICATING WHAT IS
 BEING DEMOED OR CHANGED, IS EVERYTHING TO BE CONSIDERED
 NEW? 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR
 COMMERCIAL BUILDINGS. FROM THE LAST KNOWN PERMIT
 13010420 THERE IS ALOT OF INTERIOR CHANGES FROM THE
 LAST KNOWN USE AS FAR AS LAY OUT AND LIFE SAFETY PLAN.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 3) FOR THE AMOUNT OF CHANGES SEEN FROM THE LAST PERMIT
 (13010420) AND THE PROPOSED LAYOUT THE PERMIT VALUE
 ASSOCIATED WITH THIS DESIGN IS CONSIDERABLY
 LOW,EXTREMELY LOW. PERMIT FEES/ PLAN REVIEW:
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 4) SHEET A120.1THE MENS RESTROOM APPEARS TO HAVE BEEN
 RENOVATED WITH THE ADDITION OF A NEW LAV. THE ENTRY
 WALL HAS BEEN MOVED WITH THE ENTRY DOOR IN CONFLICT
 WITH THE UNISEX TOLIET ROOM NOT THE EXISTING STAFF
 RESTROOM. NOTE THE UNISEX TOLIET ROOM CAN HAVE A
 INSWING DOOR SO IT DOESN'T BLOCK THE MENS RESTROOM
 DOOR.
 2014 FBC-ACCESSIBILITY CODE 603.2.3 EXCEP. # 2. DOOR
 SWING.
 2014 FBC-P 403.5 UNISEX RESTROOMS SEE PLUMBING
 COMMENTS.
  
 5) SHEET A120.1 EXISTING BEER COOLER 121 HAS BEEN
 EXSPANDED THERE WAS A HALL 111 THAT LEAD TO THE BACK OF
 HOUSE EXIT PASSAGEWAY WITH RATED DOOR. THIS DOOR HAS
 BEEN ELIMINATED, THE PLANS DO NOT SHOW HOW THE FIRE
 RATING OF THE EXIT PASSAGEWAY WAS MAINTAINED. 2014
 FBC-B 1023.3.
  
 6) SHEET A120.1 LUMINARIES LOUNGE SHOWS A RAISED
 PLATFORM, UNDER PERMIT 13010420 THIS WAS A STAGE, IT
 APPEARS THERE IS NEW KNEE WALLS AND WHAT APPEARS TO BE
 STEPS. PLEASE PROVIDE AT WHAT ELEVATION THE PLATFORM IS
 ABOVE FINISH FLOOR. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 6A) SHEET A120.1 THE PROPOSED PLANS SHOW WORK ON THE
 EAST AND SOUTH OUTSIDE DINING AREA WITH WALLS MOVED,
 DOORS OPENINGS BEING MODIFIED, A NEW OUTSIDE LOUNGE
 AREA WALLS REMOVED, THE KITCHEN NEW COOLERS, OLD ONES
 MOVED BAR LOCATIONS AND WALLS MOVED ETC....
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-24 Cont ID  
Sent By gjohnson Date 2015-08-24 Time 15:54 Rev Time 0.00
Received By gjohnson Date 2015-08-24 Time 15:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-10-07 Cont ID  
Sent By albarran Date 2015-10-07 Time 18:05 Rev Time 0.00
Received By albarran Date 2015-10-07 Time 17:39 Sent To I
Notes
2015-10-07 18:07:03ALL PREVIOUSLY MENTIONED COMMENTS HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-09-29 Cont ID  
Sent By albarran Date 2015-09-29 Time 16:10 Rev Time 0.00
Received By albarran Date 2015-09-29 Time 15:25 Sent To  
Notes
2015-09-29 16:11:41TWO OF THE FOUR COMMENTS HAVE NOT BEEN PROPERLY
 ADDRESSED. I PLACED A CALL IN TO THE ARCHITECT. AFTER I
 TALK TO HIM I MAY APPROVE W/PROVISO. FILE IS ON MY DESK
 IN THE MEANTIME.
  
 1. ALL THAT WAS DONE WAS A TYPOGRAPHICAL CORRECTION TO
 NOTE 29, BUT NOTHING WAS CHANGED IN THE WORDING TO
 ADDRESS THE MATTER AT HAND.
 2. A NOTE AS TO THE SIGN CHANGEOUT WAS MADE. MY COMMENT
 HAS NOTHING TO DO WITH WHATEVER SIGNAGE IS THER NOW,
 BUT WITH THE SIGN OUTLETS REQUIRED BY CODE FOR THE NEW
 LOCATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-26 Cont ID  
Sent By albarran Date 2015-08-26 Time 17:36 Rev Time 0.00
Received By albarran Date 2015-08-26 Time 16:30 Sent To Z
Notes
2015-08-26 17:44:49PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. PAGE A400.2 DETAILS INDICATE THAT COMMUNICATING
 PARTITIONS ARE BEING USED, THEREFORE EVERY ELECTRICAL
 OUTLET BOX IN A FIRE RATED WALL SHALL BE PROTECTED WITH
 AN APPROVED FIRE STOPPING MATERIAL.
 2. PAGE E100 NOTE 29 SHALL BE CORRECTED TO ADDRESS THE
 ABOVE COMMENTS. THE WAY NOTE 29 IS STATED ONLY APPLIES
 WHEN USING NON-COMMUNICATING PARTITIONS.
 3. PAGE E120 REVISIT THE EMERGENCY LIGHTING ARRANGEMENT
 TO PROVIDE PROPER ILLUMINATION THROUGH OUT UNDER
 EMERGENCY CONDITIONS. WALK-IN COOLER & FREEZER SHOULD
 HAVE AN EMERGENCY LIGHT INSIDE AS WELL.
 4. PAGE E120 NEC 600.5(A) REQUIRES THAT THERE BE A
 DEDICATED SIGN OUTLET ADJACENT TO EVERY PEDESTRIAN
 DOOR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-14 Cont ID  
Sent By pleduc Date 2015-09-14 Time   Rev Time 0.00
Received By pleduc Date 2015-09-14 Time 14:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-20 Cont ID  
Sent By pleduc Date 2015-08-20 Time   Rev Time 0.00
Received By pleduc Date 2015-08-20 Time 10:33 Sent To  
Notes
2015-08-20 11:05:46THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) SHEET A 200.1, THERE IS AN INCORRECT REFERENCE TO
 THE FIRE CODE, FFPC (2010). THE CORRECT CODE REFERENCE
 IS 2012.
  
 2) SHEET A120.1, THE DOOR FROM ROOM 116 (BY THE OFFICE
 114) SHALL SWING IN THE PATH OF EXIT TRAVEL PER NFPA
 101, CHAPTER 7. THE OCCUPANCY OF THE ROOM 116 IS
 GREATER THAN 50.
  
 3) SHEET A 200.1, A LIGHTWEIGHT ROOF AND FLOOR TRUSS
 SIGN SHALL BE INSTALLED PER FL STATUTUE.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2015-10-08 Cont ID  
Sent By gjohnson Date 2015-10-07 Time 15:13 Rev Time 0.00
Received By tklarge Date 2015-10-07 Time 15:12 Sent To  
Notes
2015-10-07 15:20:531ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
 GAS PROVISO: SEPARATE PERMIT REQUIRED.
  
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-07 Cont ID  
Sent By albarran Date 2015-10-07 Time 18:35 Rev Time 0.00
Received By albarran Date 2015-10-06 Time 16:21 Sent To  
Notes
2015-10-07 18:37:0810/7/15 PASSED ELECTRICAL REVIEW. SEPARATE PERMIT IS
 REQUIRED FOR GAS, BUT AN F WAS ENTERED INSTEAD OF AN N.
 CONTRACTOR NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN
 "D". MA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date 2015-10-06 Cont ID  
Sent By cpuell Date 2015-09-29 Time 16:20 Rev Time 0.00
Received By cpuell Date 2015-09-09 Time 10:39 Sent To  
Notes
2015-09-09 10:39:50C33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-28 Cont ID  
Sent By albarran Date 2015-08-26 Time 17:45 Rev Time 0.00
Received By lmarchan Date 2015-08-14 Time 14:55 Sent To  
Notes
2015-08-14 14:56:14C32

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2015-09-15 Cont ID  
Sent By ccole Date 2015-09-15 Time 17:09 Rev Time 0.00
Received By ccole Date 2015-09-15 Time 17:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-18 Cont ID  
Sent By ccole Date 2015-08-18 Time 15:30 Rev Time 0.00
Received By ccole Date 2015-08-18 Time 15:29 Sent To  
Notes
2015-08-18 15:44:191ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080547
 8/18/15
  
 1) REFER TO SECTION 809.1 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE VENTILATION CALCULATIONS FOR ALL ROOMS AND
 SPACES IN ACCORDANCE WITH TABLE 403.3 FBC-14
 MECHANICAL. INDICATE THE REQUIRED O/A CFM'S AND THE
 AMOUNT OF CFM'S BEING PROVIDED BY THE EXISTING
 SYSTEM(S).
 2) THE CITY OF WEST PALM BEACH DEVELOPMENT SERVICES
 DEPARTMENT REQUIRES SEPARATE PERMITS FOR ALL KITCHEN
 HOOD, AND WALK-IN COOLER AND FREEZER INSTALLATIONS- THE
 PLAN IS INDICATING BOTH. PLEASE PLACE NOTES ON THE
 PLANS ACCORDINGLY.
 IN REFERENCE TO THIS PERMIT SET OF PLANS IT IS
 NECESSARY TO INDICATE HOW MAKE-UP AIR IS BEING PROVIDED
 FOR THE NEW EXHAUST HOOD TO VERIFY PROPER AIR BALANCING
 WITHIN THE ALTERED SPACE- REFER TO SECTION 508 FBC-14
 MECHANICAL.
 508.1 MAKEUP AIR.
 MAKEUP AIR SHALL BE SUPPLIED DURING THE OPERATION OF
 COMMERCIAL KITCHEN EXHAUST SYSTEMS THAT ARE PROVIDED
 FOR COMMERCIAL COOKING APPLIANCES. THE AMOUNT OF MAKEUP
 AIR SUPPLIED TO THE BUILDING FROM ALL SOURCES SHALL BE
 APPROXIMATELY EQUAL TO THE AMOUNT OF EXHAUST AIR FOR
 ALL EXHAUST SYSTEMS FOR THE BUILDING. THE MAKEUP AIR
 SHALL NOT REDUCE THE EFFECTIVENESS OF THE EXHAUST
 SYSTEM. MAKEUP AIR SHALL BE PROVIDED BY GRAVITY OR
 MECHANICAL MEANS OR BOTH. MECHANICAL MAKEUP AIR SYSTEMS
 SHALL BE AUTOMATICALLY CONTROLLED TO START AND OPERATE
 SIMULTANEOUSLY WITH THE EXHAUST SYSTEM. MAKEUP AIR
 INTAKE OPENING LOCATIONS SHALL COMPLY WITH SECTION
 401.4.
 508.1.1 MAKEUP AIR TEMPERATURE.
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10
 DEGREES F (6 DEGREES C) EXCEPT WHERE THE ADDED HEATING
 AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE
 CAPACITY OF THE HVAC SYSTEM.
 3) SHEET FS500.1: PLEASE PROVIDE DETQILS ON THE PLANS
 THAT CORRELATE WITH MECHANICAL NOTE 2.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-10-07 Cont ID  
Sent By gjohnson Date 2015-10-07 Time 15:12 Rev Time 0.00
Received By gjohnson Date 2015-10-07 Time 15:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-09-11 Cont ID  
Sent By gjohnson Date 2015-09-11 Time 16:18 Rev Time 0.00
Received By gjohnson Date 2015-09-11 Time 16:18 Sent To  
Notes
2015-09-11 16:41:18PLUMBING COMMENTS:
  
  
 1. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1
 1ST REVIEW: FBC 2014
 2.PLEASE PROVIDE SPEC SHEETS FOR WATER HEATER AND ALL
 KITCHEN EQUIPMENT.
 WPB AMEND . SEC. 107.2.1
 3.SHEET P220 KITCHEN EQUPMENT SCHDULE IS CALLING FOR
 140* HOT WATER FOR PRE RINSE FAUCETS1.1 -4.1 IT DOES
 NOT SHOW THAT ON WATER RISER DIAGRAM PLEASE SHOW.
 WPB AMEND . SEC. 107.2.1
 4.SHEET P222 ON THE WATER RISER THE FIXTURES ARE NOT
 LABALLED AND THERE IS NO STUB. FOR DISWASHER PLEASE
 CORRECT.
 WPB AMEND . SEC. 107.2.1
 5.SHEET P222 WATER RISER PIPING FOR THE PRE RINSE
 FAUCETS AND DISHWASHER APPEAR SMALL. SHOW FLOW RATE FOR
 ALL FAUCETS AND DISHWASHER.
 WPB AMEND . SEC. 107.2.1
 6.SHOW CALC. COMBUSTION AIR FOR GAS EQUIPMENT.
 WPB AMEND . SEC. 107.2.1
  
  
  
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-08-26 Cont ID  
Sent By gjohnson Date 2015-08-26 Time 06:50 Rev Time 0.00
Received By gjohnson Date 2015-08-26 Time 06:50 Sent To  
Notes
2015-08-26 06:50:221ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  
  
 COMMENTS:
  
 1. SCOPE OF WORK UNCLEAR PLEASE CLARIFY. ARE BATHROOMS
 EXISTING WITH NO CHANGES.IS THER ANY CHANGES TO GAS
 PIPING. ETC.
 PER WPB AMEND. TO FBC SEC. 107.2.1
 2. SHOW CALCULATIONS FOR GREASE TRAP TO DETERMINE IF
 EXISTING SIZE IS ADEQUATE FOR NEW FIXTURE DRAINAGE.
 PER WPB AMEND. TO FBC SEC. 107.2.1.,3
 3.SHEET INDEX SHOWS P222 AS PLUMBING ISOMETRICS SHEET
 P222 IS MISSING PLEASE PROVIDE, PLUMBING ISOMETRIC
 DRAWINGS.
 PER WPB AMEND. TO FBC SEC. 107.3.5.1.3(13)

Review Stop Z ZONING
Rev No 2 Status P Date 2015-09-14 Cont ID  
Sent By eschneid Date 2015-09-14 Time 16:26 Rev Time 0.50
Received By eschneid Date 2015-09-14 Time 16:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-08-27 Cont ID  
Sent By eschneid Date 2015-08-27 Time 14:50 Rev Time 0.50
Received By eschneid Date 2015-08-27 Time 14:50 Sent To  
Notes
2015-08-27 15:13:38FAILED
  
 1) THE CITYPLACE MANAGEMENT APPROVAL STAMP IS REQUIRED
 ON THE PLANS.
  
 2) PLEASE VERIFY THAT A MINIMUM 60 INCH (5 FOOT) WIDE
 PEDESTRIAN PATH REMAINS THROUGH THE OUTDOOR DINING AREA
 UNDER THE COVERED ARCADE. THIS DIMENSION SHALL BE SHOWN
 ON THE PLANS.
  
 3) THE LIFE SAFETY PLAN SHOWS TABLES AND CHAIRS
 EXTENDING PAST THE OUTDOOR DINING AREA. THIS IS THE
 PUBLIC RIGHT-OF-WAY AND MAY NOT INCLUDE TABLES AND
 CHAIRS WITHOUT THE APPROVAL OF A SIDEWALK CAFE PERMIT.
  
 4) THE RAILING SHOWN ALONG GARDENIA STREET REQUIRES A
 SEPARATE FENCE PERMIT, WITH PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2015-08-17 11:36:408/17/15