| Plan Review Stops For Permit 15080518 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2015-08-20 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2015-08-20 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2015-08-17 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2015-08-17 16:12:18 | SEPARATE PERMIT REQUIRED FOR COMMUNICATION CONNECTION | | | TO ENERGY MANAGEMENT SYSTE, PER THE NOTE ON THE PLAN. | | | | | | | | | EQUIPMENT GROUND WIRE SIZES AND GROUNDING ELECTRODE | | | CONDUCTOR ARE TO SIZED PER 250.66 AND 250.122. THE | | | DRAWING SHOWS EGC AND GES CONDUCTORS WITHOUT THE | | | BENEFIT OF PHASE CONDUCTORS OR OCP. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2015-08-17 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2015-08-17 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2015-08-14 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2015-08-17 14:36:56 | PASS PROVISO | | | PRECISION INROW A/C SCHEDULE PAGE M-3 | | | TOTAL SUPPLY CFM IS 2290. REFER TO SECTION 606.2.1 | | | RETURN AIR SYSTEM 2014 FBC (M) | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805- 6732 | | | FAX 561-805-6676 |
|
|
|