Plan Review Details - Permit 15080487
Plan Review Stops For Permit 15080487
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-10-01 Cont ID  
Sent By jwitmer Date 2015-10-01 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2015-10-01 Time 07:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-28 Cont ID  
Sent By jwitmer Date 2015-08-28 Time 15:43 Rev Time  
Received By jwitmer Date 2015-08-28 Time 07:30 Sent To  
Notes
2015-08-28 14:49:22 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080487
 ADD: 2749 EXCHANGE CT.
 CONT: RPM & M GENERAL CONTRACTORS
 TEL: (954)649-5304
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY AUGUST 28/ 2015
 ACTION: DENIED
  
 1) THE PLANS NEED TO IDENTIFY TO WHAT CODE THEY WERE
 DESIGNED TOO? NOTE JUNE 30/ 2015 WAS THE 1ST DAY THE
 2014 FBC-B WAS ADOPTED STATEWIDE.
  
 2) THE DESIGNER OF RECORD WILL NEED TO SHOW TO WHICH
 COMPLIANCE METHOD THE PLANS WERE DESIGNED TO UNDER THE
 2014 EBC-EXISTING BUILDING CODE. 301.1.
  
 3) THE PLANS ARE MISSING THE 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS,
 107.3.5.1.1 COMMERCIAL BUILDINGS
 OCCUPANCY
 MINIMUM BUILDING TYPE
 SQUARE FEET OF BUILDING PER FLOOR
 FIRE SPRINKLERED OR NOT/ REQUIRED OR NOT
 OCCUPANCY LOAD
  
 3) THE PLANS SHOW ALL NEW WINDOWS AND DOORS ARE BEING
 INSTALLED IN THE EXISSTING OPENINGS. PLEASE SHOW
 COMPLIANCE WITH 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (G) PRE-ENGINEERED A/C STANDS
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) THE PLANS ARE MISSING THE WIND DESIGN CRITERIA. 2014
 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 5.2. RISK CATEGORY.
  
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 6) SHEET # 2 INDICATES THE USE OF 2 INCH MOVEABLE
 PARTITIONS. NOTE THERE IS NO HEIGTH GIVEN FOR THESE
 PARTITIONS. COMPLIANCE WITH FBC-B TABLE 1604.3 FOOTNOTE
 B, CODE COMPLIANCE CAN NOT BE DETERMINED, IF REQUIRED.
  
 7) THE NEW RESTROOMS DO NOT MEET THE REQUIREMENTS OF
 2014 FBC-ACCESSIBILITY 604.3.1 AND FIGURE 604.3.1.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-10-15 Cont ID  
Sent By albarran Date 2015-10-15 Time 19:16 Rev Time 0.00
Received By albarran Date 2015-10-15 Time 18:46 Sent To  
Notes
2015-10-15 19:27:07I HAVE REVIEWED AND APPROVED (SEE MY GREEN STAMP ON
 PLANS) THE FOUR SHEETS. I EMAILED THEM BACK TO THE
 ENGINEER FOR HIM TO PRINT WITH MY STAMP AND SIGN AND
 SEAL THE DRAWINGS. HE WILL BRING IN THE APPROVED
 DRAWINGS DIGITALLY SIGNED BY ME. PERMIT CAN BE ISSUED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-10-15 Cont ID  
Sent By albarran Date 2015-10-15 Time 11:43 Rev Time 0.00
Received By albarran Date 2015-10-15 Time 10:49 Sent To I
Notes
2015-10-15 11:44:05PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN
 OUTLET AT EVERY PEDESTRIAN DOOR, NOT JUST THE FRONT
 DOOR. A LACK OF THE REQUESTED SITE PLAN MAKES IT
 DIFFICULT TO VERIFY OR CONFIRM WHICH DOOR MAY LEAD TO A
 SERVICE CORRIDOR THUS NOT REQUIRING SIGNAGE.
 2. NEC 406.9(B) REQUIRES THAT IN ADDITION TO THE IN-USE
 TYPE COVER, ALL OUTLETS IN WET LOCATIONS TO BE LISTED
 OR RATED AS WEATHER RESISTANT "WR".
 3. FBC-ENERGY CONSERVATION SECTION C405 HAS SPECIFIC
 LIGHTING CONTROL REQUIREMENTS WHICH SHALL BE ADHERED
 TO.
 4. NEC 408.4(A) REQUIRES A SITE SPECIFIC/ACCURATE
 CIRCUIT DIRECTORY. THIS DIRECTORY HAS TO MATCH THE
 FLOOR PLAN.
 5. NEC 408.4(B) REQUIRES THAT THE PANEL BE MARKED WITH
 THE LOCATION OF THE SOURCE OF POWER.
 6. NEC 2154.5 REQUIRES THAT YOU PROVIDE A FEEDER
 DIAGRAM SHOWING CONDUCTOR SIZING AND LOAD CALCS. THESE
 LOAD CALCS ARE BASED ON THE CONNECTED LOADS TO EACH
 PANEL, THUS THE NEED FOR ACCURATE PANEL SCHEDULES.
  
 CORRECT THE ITEMS DESCRIBED ABOVE AS INSTRUCTED AND
 RE-SUBMIT THE DRAWINGS FOR ANOTHER REVIEW.
  
 WHEN RESUBMITTING, YOU SHALL PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH COMMENT ITEM ALONG WITH THE
 CITY?S RE-SUBMITTAL FORM. SEE LINK BELOW:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
 ADDITIONALLY, IT IS REQUIRED THAT YOU INSERT THE
 CORRECTED PAGES INTO THE DENIED SUBMITTAL PACKAGE. MARK
 VOID ON THE PREVIOUSLY REVIEWED SHEETS AND LEAVE THEM
 IN FOR COMPARATIVE REVIEW.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-09-29 Cont ID  
Sent By albarran Date 2015-09-29 Time 11:14 Rev Time 0.00
Received By albarran Date 2015-09-29 Time 09:11 Sent To I
Notes
2015-09-29 11:14:53PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE
 ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
 1. YOU SHALL PROVIDE A SITE PLAN INDICATING IF THIS
 STRUCTURE IS STAND ALONE, OR AN INTERIOR PORTION OF A
 LARGER AREA.
 2. THE WALL HUNG WATER HEATER REQUIRES A DISCONNECT AS
 INDICATED BY NEC 422.30.
 3. THE ELECTRIC WATER COOLER SHALL BE ON A GFCI
 PROTECTED CIRCUIT AS PER NEC 422.52
 4. A DEDICATED SIGN OUTLET ABOVE EVERY PEDESTRIAN ENTRY
 DOOR IS REQUIRED PER NEC 600.5.
 5. MISSING EXIT LIGHT IN ENG. 4 OFFICE PER FBC 5TH
 EDITION 2014.
 6. CEILING LUMINAIRES OUTLET BOXES SHALL BE LISTED TO
 SUPPORT A MINIMUM OF 50# PER NEC 314.27.
 7. THE FLOOR PLAN REFLECTS THREE PANELS W/O ANY
 INDICATION AS TO THEIR RESPECTIVE OCCUPANCY AND NO
 METERS, YET THE ELECTRICAL RISER DIAGRAM SHOWS
 SOMETHING DIFFERENT. YOU SHALL SUBMIT A SITE SPECIFIC
 RISER DIAGRAM SHOWING CONDUCTOR SIZING AND INSULATION
 AS WELL THE SERVICE GROUNDING SYSTEM AS PER NEC 215.5
 8. YOU SHALL SUBMIT SITE SPECIFIC LOAD CALCS AS
 INDICATED IN NEC 220.16
 9. YOU SHALL IDENTIFY ALL PANELS ON THIS SERVICE AND
 INDICATE THEIR RESPECTIVE LOCATIONS ON THE FLOOR PLAN.
 PROVIDE A PANEL SCHEDULE FOR EVERY PANEL WITHIN YOUR
 PREMISES AS REQUIRED BY NEC 408.4
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-10-08 Cont ID  
Sent By pleduc Date 2015-10-08 Time   Rev Time 0.00
Received By pleduc Date 2015-10-08 Time 15:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-08-18 Cont ID  
Sent By pleduc Date 2015-08-18 Time   Rev Time 0.00
Received By pleduc Date 2015-08-18 Time 15:18 Sent To  
Notes
2015-08-18 15:50:49THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET 2 INDICATES FOUR DOORS OPENING INTO AN EXIT
 CORRIDOR.
  
 NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 THE DOORS SHALL SWING INTO THE ROOMS.
  
 2) FIRE EXTINGUISHERS SHALL BE PLACED EVERY 75FT OF
 WALKING DISTANCE IN THE PATH OF TRAVEL.
  
 3) THE NATURE OF THE REMODEL MAY REQUIRE AN EVALUATION
 OF THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE
 COVERAGE AND COMPLIANCE. ANY REMOVAL AND/OR
 CONSTRUCTION OF WALLS REQUIRES AN EVALUATION.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 4) PLEASE PROVIDE A DOOR SCHEDULE INDICATING EXIT
 HARDWARE AND/OR LOCKING DEVICES.
  
 5) PROVIDE AN OCCUPANCY AND AN OCCUPANCY LOAD.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-15 Cont ID  
Sent By albarran Date 2015-10-15 Time 11:46 Rev Time 0.00
Received By albarran Date 2015-09-29 Time 15:52 Sent To  
Notes
2015-10-15 11:46:4610/15/15 FAILED BOTH MECHANICAL AND ELECTRICAL REVIEWS.
 CONTRACTOR NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN
 "R". MA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-29 Cont ID  
Sent By albarran Date 2015-09-29 Time 11:15 Rev Time 0.00
Received By albarran Date 2015-08-13 Time 08:56 Sent To  
Notes
2015-09-29 11:15:30HANDED TO MSCOTT.
2015-08-14 08:58:49B03

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-10-14 Cont ID  
Sent By ccole Date 2015-10-14 Time 14:00 Rev Time 0.00
Received By ccole Date 2015-10-14 Time 14:00 Sent To  
Notes
2015-10-13 08:38:28MID CYCLE RE-SUB OF SHEET M-1 ONLY.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-10-07 Cont ID  
Sent By ccole Date 2015-10-07 Time 11:24 Rev Time 0.00
Received By ccole Date 2015-10-07 Time 11:24 Sent To  
Notes
2015-10-07 11:34:082ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080487
 10/7/15
  
 1) PLEASE REVIEW COMMENT #10 FROM THE1ST REVIEW
 REGARDING THE TRANSFER GRILLES RETURNING AIR INTO THE
 CORRIDORS. THE PLAN IS NOT IN COMPLIANCE WITH SECTION
 601.2 FBC-14 MECHANICAL: AIR MOVEMENT IN EGRESS
 ELEMENTS-
 CORRIDORS SHALL NOT SERVE AS SUPPLY, RETURN, EXHAUST,
 RELIEF OR VENTILATION AIR DUCTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-20 Cont ID  
Sent By ccole Date 2015-08-20 Time 07:56 Rev Time 0.00
Received By ccole Date 2015-08-20 Time 07:56 Sent To  
Notes
2015-08-20 09:13:581ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080487
 8/20/15
  
 1) DESIGN CRITERIA: PROVIDE A LIST OF CURRENT CODES AND
 STANDARDS USED IN THE DESIGN OF THE PROPOSED PROJECT.
 2) PROVIDE THE LEVEL OF ALTERATION ON THE PLAN IN
 COMPLIANCE WITH SECTION 501 FBC-14 EXISTING BUILDING
 CODE. THE SUBMITTED PLANS APPEAR TO INDICATE A LEVEL II
 ALTERATION THEREFORE MY REVIEW WILL BE IN ACCORDANCE
 WITH CHAPTER 8, AND THE FBC-14 MECHANICAL CODE.
 3) REFER TO SECTION 809 FBC-14 FBC-14 EXISTING BUILDING
 CODE:
 809.1 RECONFIGURED OR CONVERTED SPACES.
 ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY AND ALL
 SPACES CONVERTED TO HABITABLE OR OCCUPIABLE SPACE IN
 ANY WORK AREA SHALL BE PROVIDED WITH NATURAL OR
 MECHANICAL VENTILATION IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL.
 EXCEPTION: EXISTING MECHANICAL VENTILATION SYSTEMS
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 809.2.
  
 809.2 ALTERED EXISTING SYSTEMS.
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62.
  
 IN REFERENCE TO THE ABOVE SECTIONS PROVIDE VENITLATION
 CALCULATIONS FOR ALL ROOMS AND SPACES- INCLUDING A
 SCHEDULE THAT SHOWS THE REQUIRED AND PROVIDED CFM'S OF
 O/A AIR.
  
 4) SHEET 5: PROVIDE A SCOPE OF WORK FOR MECHANICAL
 DEMOLITION AND MECHANICAL ALTERATIONS WITH KEY NOTES
 AND CORRESPONDING DETAILS ON THE PLAN. CLARIFY IF THE
 ENTIRE AC SYSTEMS ARE BEING REPLACED, OR IF THE AIR
 HANDLERS ALONE ARE BEING RELOCATED- NO INFORMATION IS
 PROVIDED. PROVIDE AC EQUIPMENT SCHEDULES ON THE PLANS
 AND LABEL THE UNITS AS NEW OR EXISTING. PLEASE NOTE
 THAT COOLING AND HEATING LOAD CALCULATIONS ARE REQUIRED
 FOR NEW SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1
 FBC-14 ENERGY CONSERVATION.
 5) SHEET 5: REFER TO SECTION 603.1.1 FBC-14 MECHANICAL
 CODE AND SHOW COMPLIANCE:
 603.1.1 SPACE PROVIDED.
 SUFFICIENT SPACE SHALL BE PROVIDED ADJACENT TO ALL
 MECHANICAL COMPONENTS LOCATED IN OR FORMING A PART OF
 THE AIR DISTRIBUTION SYSTEM TO ASSURE ADEQUATE ACCESS
 FOR (1) CONSTRUCTION AND SEALING IN ACCORDANCE WITH THE
 REQUIREMENTS OF SECTION 603.1 OF THIS CODE; (2)
 INSPECTION; AND (3) CLEANING AND MAINTENANCE. A MINIMUM
 OF 4 INCHES (102 MM) IS CONSIDERED SUFFICIENT SPACE
 AROUND AIR HANDLING UNITS.
 EXCEPTION: RETROFIT OR REPLACEMENT UNITS NOT PART OF A
 RENOVATION ARE EXEMPT FROM THE MINIMUM CLEARANCE
 REQUIREMENT.
 6) SHEET 5: REFER TO SECTION 602 AND PROVIDE NOTES AND
 DETAILS INCDICATING COMPLIANCE FOR ALL MATERIALS
 FORMING THE PLENUM CLOSET AND ALL MATERIALS CONTAINED
 WITHIN IT INCLUDING THE CLOSET DOORS, WALLS, CEILING,
 AND ALL COMPONENTS OF THE AIR HANDLERS INCLUDING
 ELECTRICAL WIRING, PLUMBING PIPING, AND INSULATIONS.
 7) SHEET 5: PROVIDE AN AIR DISTRIBUTION SCHEDULE
 LISTING THE MAKES AND MODEL NUMBERS IOF THE SUPPLY
 DIFFUSERS AND RETURN GRILLS.
 8) SHEET 5: REFER TO SECTION C403.2.7 (INCLUDING TABLES
 AND SUB-SECTIONS): PROVIDE DETAILS FOR DUCT
 INSTALLATIONS INCLUDING THE TYPE OF DUCTS, AND SUPPORT,
 CONNECTION, AND SEALING DETAILS AND SPECIFICATION.
 9) SHEET 5: PROVIDE EQUIPMENT SCHEDULES FOR THE TOILET
 ROOM EXHAUST FANS.
 10) SHEET 5: REFER TO SECTION 601.2 AND CORRECT THE
 PLAN THE RETURN AIR SYSTEM ACCORDINGLY- AIR MOVEMENT IN
 EGRESS ELEMENTS:
 CORRIDORS SHALL NOT SERVE AS SUPPLY, RETURN, EXHAUST,
 RELIEF OR VENTILATION AIR DUCTS.
 EXCEPTIONS:
 1. USE OF A CORRIDOR AS A SOURCE OF MAKEUP AIR FOR
 EXHAUST SYSTEMS IN ROOMS THAT OPEN DIRECTLY ONTO SUCH
 CORRIDORS, INCLUDING TOILET ROOMS, BATHROOMS, DRESSING
 ROOMS, SMOKING LOUNGES AND JANITOR CLOSETS, SHALL BE
 PERMITTED, PROVIDED THAT EACH SUCH CORRIDOR IS DIRECTLY
 SUPPLIED WITH OUTDOOR AIR AT A RATE GREATER THAN THE
 RATE OF MAKEUP AIR TAKEN FROM THE CORRIDOR.
 2. WHERE LOCATED WITHIN A DWELLING UNIT, THE USE OF
 CORRIDORS FOR CONVEYING RETURN AIR SHALL NOT BE
 PROHIBITED.
 3. WHERE LOCATED WITHIN TENANT SPACES OF 1,000 SQUARE
 FEET (93 M2) OR LESS IN AREA, USE OF CORRIDORS FOR
 CONVEYING RETURN AIR IS PERMITTED.
 4. INCIDENTAL AIR MOVEMENT FROM PRESSURIZED ROOMS
 WITHIN HEALTH CARE FACILITIES, PROVIDED THAT THE
 CORRIDOR IS NOT THE PRIMARY SOURCE OF SUPPLY OR RETURN
 TO THE ROOM.
 11) PLEASE NOTE THAT ADDITIONAL COMMENTS MAY OCCUR UPON
 REVIEW OF CORRECTED AND RE-SUBMITTED PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-10-06 Cont ID  
Sent By gjohnson Date 2015-10-06 Time 12:20 Rev Time 0.00
Received By gjohnson Date 2015-10-06 Time 12:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-08-21 Cont ID  
Sent By tklarge Date 2015-08-21 Time 06:52 Rev Time 0.00
Received By tklarge Date 2015-08-21 Time 05:41 Sent To  
Notes
2015-08-21 06:52:191) SHOW THE REQUIRED CLEAR FLOOR SPACES FOR THE
 LAVATORY AND THE WATER CLOSETS IN THE TOILET ROOMS IN
 ACCORDANCE WITH THE 2014 FBC-ACCESSIBILITY SEC.604.3.1,
 606.2,606.3 & SEC. 306.2.
 2) THE BREAK ROOM SINK SHALL COMPLY WITH THE
 FBC-ACCESSIBILITY SEC.606.2.
 3) THE WIDTH OF THE SINGLE USER TOLET ROOMS SHALL BE A
 MINIMUM 85 INCHES WIDE IF BUILT PERFECT. 86 INCHES
 ALLOWS FOR TOLERANCES.
 4) SHOW THE FIXTURE CLEARANCES FOR THE WATER CLOSET IN
 THE TOILET ROOMS. COMPLY WITH FBC-ACCESSIBILITY
 SEC.604.2.
 5) IDENTIFY THE TOILET ROOM WITH JUST THE URINAL.
 6) INDICATE THE TYPE OF OCCUPANCY OF THIS SPACE IN
 ACCORDANCE WITH 2014 FBC SEC.302.1.
 7) INDICATE THE SQUARE FOOTAGE OF THE SPACE AND THE
 OCCUPANT LOAD IN ACCORDANCE WITH THE 2014 FBC TABLE
 1004.1.2
 8) SUBMIT DETAILS FOR THE MOUNTING HEIGHTS FOR ALL
 HANDICAP ACCESSORIES LOCATED IN THE TOILET ROOMS.WPB
 AMEND. TO FBC SEC. 107.2.1.
 9) SUBMIT MANUF.SPECIFICATIONS FOR THE TANKLESS WATER
 HEATER. WPB AMEND. TO FBC SEC. 107.2.1.
 10) A DRINKING FOUNTAIN IS REQUIRED IN THIS SPACE PER
 TABLE 403.1 OF 2014 FBC-PLUMBING. A MINIMUM OF TW
 DRINKING FOUNTAINS SHALL BE PROVIDED PER THE 2014
 FBC-ACCESSIBILITY SEC.211.2.
 11) SHT.#4 - DOMESTIC WATER RISER - THERE IS A 1" LINE
 SUPPLYING AN UNIDENTIFIED FIXTURE. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  