Plan Review Details - Permit 15080485
Plan Review Stops For Permit 15080485
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-08-27 Cont ID  
Sent By jwitmer Date 2015-08-27 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2015-08-27 Time 11:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-09-09 Cont ID  
Sent By albarran Date 2015-09-09 Time 19:48 Rev Time 0.00
Received By albarran Date 2015-09-09 Time 18:38 Sent To I
Notes
2015-09-09 19:48:51IMPORTANT NOTICE FOR PERMIT 15080485
 PER NEC 110.16 ARC-FLASH PROTECTION LABELS ARE REQUIRED
 ON ALL PANELS.
 CAUTION: WITH THIS TYPE OF ELECTRICAL SERVICE IT IS
 VERY EASY TO MISTAKE PHASE B FOR A 120 VAC SLOT AND
 FEED 208 VAC TO THE CONNECTED LOAD.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-09-08 Cont ID  
Sent By albarran Date 2015-09-08 Time 16:20 Rev Time 0.00
Received By albarran Date 2015-09-08 Time 16:10 Sent To I
Notes
2015-09-08 16:22:44PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. YOU SHALL CLEARLY INDICATE THE SCOPE OF WORK ON
 BOTH, THE PERMIT APPLICATION AS WELL AS ON THE PLANS.
 2. INDICATE IF THIS IS TO BE A REVISION TO THE MASTER
 PERMIT 14100194 OR OTHERWISE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-09 Cont ID  
Sent By albarran Date 2015-09-09 Time 19:49 Rev Time 0.00
Received By albarran Date   Time   Sent To  
Notes
2015-09-09 19:50:319/9/15 = PASSED ELECTRICAL REVIEW . CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO SMALL READY BIN "M". MA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-08 Cont ID  
Sent By albarran Date 2015-09-08 Time 16:23 Rev Time 0.00
Received By albarran Date 2015-08-13 Time 10:55 Sent To  
Notes
2015-09-08 16:31:259/8/15 FAILED ELECTRICAL REVIEW AS NOTED. CONTACTED
 CONTRACTOR FOR EMAIL TO INFORM OF STATUS. SENT TO SMALL
 DENIED BIN "M". MA
2015-08-14 10:55:52B13

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-09-09 Cont ID  
Sent By ccole Date 2015-09-09 Time 15:06 Rev Time 0.00
Received By ccole Date 2015-09-09 Time 15:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-21 Cont ID  
Sent By ccole Date 2015-08-21 Time 14:02 Rev Time 0.00
Received By ccole Date 2015-08-21 Time 13:38 Sent To  
Notes
2015-08-21 14:16:131ST REVIEW: FBC 2010 MECHANICAL
 REVISION #15080485
 MASTER #14100194
  
 1) PLEASE PROVIDE A BRIEF NARRATIVE TO CLARIFY THE
 SCOPE OF THE MECHANICAL REVISION. THE PLAN INDICATES
 TENANT SPACE 105 IS NOW CONVERTED TO A VANILLA BOX WITH
 NO AC. PLEASE REVISE THE ENERGY CALCULATIONS (FORM
 506-2010) THAT WERE SUBMITTED UNDER THE MASTER PERMIT
 #14100194 TO CORRELATE WITH THE REVISION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  