Plan Review Details - Permit 15080440
Plan Review Stops For Permit 15080440
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-22 Cont ID  
Sent By jwitmer Date 2015-09-22 Time 13:44 Rev Time 0.00
Received By jwitmer Date 2015-09-22 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-27 Cont ID  
Sent By jwitmer Date 2015-08-27 Time 07:29 Rev Time  
Received By jwitmer Date 2015-08-27 Time 07:01 Sent To  
Notes
2015-08-27 07:15:37BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080440
 ADD: 4225 45TH ST. WALMART
 CONT: TBD
 TEL: (479)273-7780X281
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. AUGUST 27/ 2015
 ACTION: DENIED
  
 1) STURTURAL FIXTURE ANCHORAGE CALCULATIONS BY P.E.
 BART J. HALVERSON ONLY THE COVER PAGE IS SEALED.
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE
 COVERED UNDER THE COVER SHEET OR INDEX SHEET.
  
 2) PLEASE NOTE 1ST REVIEW ONLY (1) SET OF STURTURAL
 FIXTURE ANCHORAGE CALCULATIONS WERE TURNED IN FOR PLAN
 REVIEW & INSPECTION PURPOSES.
 107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, GEOTECHNICAL REPORT AND OTHER
 DATA SHALL BE SUBMITTED IN TWO OR MORE SETS WITH EACH
 PERMIT APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES& 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES& 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-09-10 Cont ID  
Sent By skennedy Date 2015-09-10 Time 16:19 Rev Time 0.00
Received By skennedy Date 2015-09-10 Time 16:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-24 Cont ID  
Sent By pleduc Date 2015-08-24 Time   Rev Time 0.00
Received By pleduc Date 2015-08-24 Time 11:33 Sent To  
Notes
2015-08-24 11:46:16THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) ANY FIRE ALARM OR FIRE SPRINKLER WORK SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-22 Cont ID  
Sent By   Date 2015-09-22 Time   Rev Time 0.00
Received By lmarchan Date 2015-09-16 Time 11:09 Sent To  
Notes
2015-09-17 11:10:06RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-10 Cont ID  
Sent By skennedy Date 2015-09-10 Time 16:19 Rev Time 0.00
Received By skennedy Date 2015-08-12 Time 11:26 Sent To  
Notes
2015-08-21 15:02:24TO SAK DESK
  
2015-08-13 11:27:07BLDG MISC 2

Review Stop Z ZONING
Rev No 1 Status N Date 2015-08-26 Cont ID  
Sent By dkittrid Date 2015-08-26 Time 09:38 Rev Time 0.00
Received By dkittred Date 2015-08-26 Time 09:35 Sent To  
Notes
2015-08-26 09:46:108/26/15 - REPLACING PHOTO LAB WITH SHELVING - ZONING
 REVIEW, NOT REQUIRED. DK
2015-08-24 10:48:338/24/15