Plan Review Details - Permit 15080424
Plan Review Stops For Permit 15080424
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-09-14 Cont ID  
Sent By ppetty Date 2015-09-14 Time 09:35 Rev Time 0.00
Received By ppetty Date 2015-09-14 Time 08:57 Sent To  
Notes
2015-09-14 09:35:18FAILED FIRE
 IN SMALL BIN F
 PHIL PETTY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-03 Cont ID  
Sent By pleduc Date 2015-09-03 Time   Rev Time 0.00
Received By pleduc Date 2015-09-03 Time 12:43 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-08-13 Cont ID  
Sent By wjolin Date 2015-08-13 Time 16:25 Rev Time 0.00
Received By wjolin Date 2015-08-13 Time 16:21 Sent To E
Notes
2015-08-13 16:25:20515 NORTH FLAGLER DRIVE - #400
 PERMIT #15080424
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A FLOOR PLAN SHOWING THE EXIT ACCESS ROUTES TO
 THE EXIT STAIRS.
  
 PER SECTION 7.2.1.6.2, ACCESS-CONTROLLED EGRESS DOORS
 ARE PERMITTED PROVIDED THAT ALL SEVEN OF THE FOLLOWING
 CRITERIA ARE MET:
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER
 TO THE SENSOR.
 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
 4. THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 PUSH TO EXIT.
 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER
 SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
  
 OR
  
 PER SECTION 7.2.1.6.3, EACH ELEVATOR LANDING AND LOBBY
 SHALL HAVE ACCESS TO AT LEAST ON EXIT. EXIT ACCESS
 SHALL NOT REQUIRE THE USE OF A KEY, TOOL, SPECIAL
 KNOWLEDGE, OR SPECIAL EFFORT. DOORS SEPARATING THE
 ELEVATOR LOBBY FROM THE EXIT ACCESS SHALL BE PERMITTED
 TO BE ELECTRONICALLY LOCKED IN ACCORDANCE WITH SECTION
 7.2.1.6.3 ELEVATOR LOBBY EXIT ACCESS DOOR ASSEMBLIES
 LOCKING: DOOR ASSEMBLIES SEPARATING THE ELEVATOR LOBBY
 FROM THE EXIT ACCESS SHALL BE PERMITTED TO BE
 ELECTRONICALLY LOCKED, PROVIDED THAT ALL THE FOLLOWING
 CRITERIA ARE MET:
 (1) THE ELECTRONIC SWITCH FOR RELEASING THE LOCK IS
 LISTED IN ACCORDANCE WITH UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS
 (2) THE BUILDING IS PROTECTED THROUGHOUT BY A FIRE
 ALARM SYSTEM
 (3) THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 (4) WATERFLOW IN THE SPRINKLER SYSTEM REQUIRED BY
 7.2.1.6.3(3) IS ARRANGED TO INITIATE THE BUILDING FIRE
 ALARM SYSTEM.
 (5) THE ELEVATOR LOBBY IS PROTECTED BY AN APPROVED,
 SUPERVISED SMOKE DETECTION SYSTEM
 (6) DETECTION OF SMOKE BY THE DETECTION SYSTEM REQUIRED
 BY 7.2.1.6.3(5) IS ARRANGED TO INITIATE THE BUILDING
 FIRE ALARM SYSTEM.
 (7) INITIATION OF THE BUILDING FIRE ALARM SYSTEM BY
 OTHER THAN MANUAL FIRE ALARM BOXES UNLOCKS THE ELEVATOR
 LOBBY DOOR ASSEMBLY.
 (8) LOSS OF POWER TO THE ELEVATOR LOBBY ELECTRONIC LOCK
 SYSTEM UNLOCKS THE ELEVATOR LOBBY DOOR ASSEMBLIES.
 (9) THE ELEVATOR LOBBY ELECTRONIC LOCK SYSTEM IS NOT
 SUPPLIED WITH EMERGENCY OR STANDBY ELECTRICAL POWER.
 (10) ONCE UNLOCKED, THE ELEVATOR LOBBY DOOR ASSEMBLIES
 REMAIN UNLOCKED UNTIL THE BUILDING FIRE ALARM SYSTEM
 HAS BEEN MANUALLY RESET.
 (11) WHERE THE ELEVATOR LOBBY DOOR ASSEMBLIES REMAIN
 LATCHED AFTER BEING UNLOCKED, LATCH-RELEASING HARDWARE
 IS AFFIXED TO THE DOOR LEAVES.
 (12) A TWO-WAY COMMUNICATION SYSTEM IS PROVIDED FOR
 COMMUNICATION BETWEEN THE ELEVATOR LOBBY AND A CENTRAL
 CONTROL POINT THAT IS CONSTANTLY STAFFED.
 (13) THE CENTRAL CONTROL POINT STAFF REQUIRED BY
 7.2.1.6.3(12) IS CAPABLE, TRAINED, AND AUTHORIZED TO
 PROVIDE EMERGENCY ASSISTANCE.
 (14) THE PROVISIONS OF DELAYED-EGRESS LOCKING SYSTEMS
 ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR ASSEMBLIES.
 (15) THE PROVISIONS OF ACCESS-CONTROLLED EGRESS DOOR
 ASSEMBLIES ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR
 ASSEMBLIES.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-14 Cont ID  
Sent By skennedy Date 2015-09-14 Time 10:39 Rev Time 0.00
Received By skennedy Date 2015-08-12 Time 12:07 Sent To  
Notes
2015-08-12 12:07:44FIRE
  