Plan Review Details - Permit 15080423
Plan Review Stops For Permit 15080423
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-10-07 Cont ID  
Sent By albarran Date 2015-10-07 Time 20:05 Rev Time 0.00
Received By albarran Date 2015-10-07 Time 19:48 Sent To I
Notes
2015-10-07 20:06:49APPROVED WITH THE UNDERSTANDING THAT THE CONTRACTOR
 WILL IDENTIFY THE ELECTRICAL FIRE ALARM CIRCUIT IN THE
 PANEL AS REQUIRED BY CODE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-09-10 Cont ID  
Sent By albarran Date 2015-09-10 Time 19:23 Rev Time 0.00
Received By albarran Date 2015-09-10 Time 19:02 Sent To I
Notes
2015-09-10 19:34:42PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 SCOTT, AS SIMPLE AS THIS SYSTEM MAY SEEM TO BE, NONE
 THE LESS, IT IS A FIRE ALARM SYSTEM AND THUS HAS
 SPECIFIC SUBMITTAL REQUIREMENTS BY THE FLORIDA BUILDING
 CODE 5TH EDITION 2014. SECTION 907.
 IN ADDITION TO THAT YOU NEED TO INDICATE HOW WILL THIS
 SYSTEM BE INTERCONNECTED WITH THE HOOD SYSTEM. CODE
 REQUIRES THAT THE FUEL TO THE COOKING APPARATUS BE SHUT
 DOWN IN THE EVENT OF AN ALARM, IS THAT BEING
 ACCOMPLISHED DIRECTLY FROM THE HOOD MECHANISM OR WILL
 IT BE VIA THE FIRE ALARM.
 THE PLANS SHALL HAVE AN INDICATION AS TO THE LOCATION
 OF THE OCPD FOR THE FACP.
 THE CODE REQUIRES THAT THE DRAWINGS BEAR THE NAME AND
 SIGNATURE OF WHOEVER DESIGNED/DREW THE PLANS.
 YOU PROVIDED SPEC SHEET FOR AN ANNUNCIATOR AND DIDN'T
 SHOW IT ON THE RISER, YET SHOWN IS A CELL TRANSMITTER
 AND NO SPEWC SHEET IS PROVIDED FOR IT.
 BE MORE SPECIFIC ON THE SCOPE AND INCLUDE IT ON THE
 DRAWINGS AS WELL.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-24 Cont ID  
Sent By pleduc Date 2015-09-24 Time   Rev Time 0.00
Received By pleduc Date 2015-09-24 Time 14:28 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-08-13 Cont ID  
Sent By pleduc Date 2015-08-13 Time   Rev Time 0.00
Received By pleduc Date 2015-08-13 Time 09:59 Sent To E
Notes
2015-08-13 10:11:45THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THERE IS INSUFFICIENT INFORMATION PROVIDED TO REVIEW OR
 APPROVE THIS PROJECT.
  
 1) A SITE FLOOR PLAN IS REQUIRED SHOWING THE LOCATION
 OF ALL DEVICES, INCLUDING HEIGHTS.
  
 2) A VOLTAGE DROP CALCUALTION SHEET IS REQUIRED,
 INCLUDING WIRE SIZES.
  
 3) EMERGECNY POWER OR BATTERY BACK-UP CALCULATIONS ARE
 REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-07 Cont ID  
Sent By albarran Date 2015-10-07 Time 20:09 Rev Time 0.00
Received By albarran Date 2015-09-24 Time 11:31 Sent To  
Notes
2015-10-07 20:10:1410/7/15 PASSED ELECTRICAL REVIEW W/PROVISO. CONTRACTOR
 NOTIFIED VIA PHONE CALL . SENT TO SMALL READY BIN "T".
 MA
2015-09-24 11:31:18ROUTED TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-10 Cont ID  
Sent By albarran Date 2015-09-10 Time 19:39 Rev Time 0.00
Received By albarran Date 2015-08-12 Time 12:48 Sent To  
Notes
2015-09-10 19:40:299/10/15 - FAILED FIRE AND ELECTRICAL REVIEW. CONTRACTOR
 NOTIFIED VIA PHONE AS EMAIL WAS NOT AVAILABLE. SENT TO
 SMALL DENIED BIN "T". MA
2015-08-12 12:49:00ROUTED TO FIRE