| 2015-09-10 19:34:42 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | SCOTT, AS SIMPLE AS THIS SYSTEM MAY SEEM TO BE, NONE |
| | THE LESS, IT IS A FIRE ALARM SYSTEM AND THUS HAS |
| | SPECIFIC SUBMITTAL REQUIREMENTS BY THE FLORIDA BUILDING |
| | CODE 5TH EDITION 2014. SECTION 907. |
| | IN ADDITION TO THAT YOU NEED TO INDICATE HOW WILL THIS |
| | SYSTEM BE INTERCONNECTED WITH THE HOOD SYSTEM. CODE |
| | REQUIRES THAT THE FUEL TO THE COOKING APPARATUS BE SHUT |
| | DOWN IN THE EVENT OF AN ALARM, IS THAT BEING |
| | ACCOMPLISHED DIRECTLY FROM THE HOOD MECHANISM OR WILL |
| | IT BE VIA THE FIRE ALARM. |
| | THE PLANS SHALL HAVE AN INDICATION AS TO THE LOCATION |
| | OF THE OCPD FOR THE FACP. |
| | THE CODE REQUIRES THAT THE DRAWINGS BEAR THE NAME AND |
| | SIGNATURE OF WHOEVER DESIGNED/DREW THE PLANS. |
| | YOU PROVIDED SPEC SHEET FOR AN ANNUNCIATOR AND DIDN'T |
| | SHOW IT ON THE RISER, YET SHOWN IS A CELL TRANSMITTER |
| | AND NO SPEWC SHEET IS PROVIDED FOR IT. |
| | BE MORE SPECIFIC ON THE SCOPE AND INCLUDE IT ON THE |
| | DRAWINGS AS WELL. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |