Plan Review Details - Permit 15080415
Plan Review Stops For Permit 15080415
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-02-24 Cont ID  
Sent By rmcdouga Date 2016-02-24 Time 17:23 Rev Time 0.00
Received By rmcdouga Date 2016-02-18 Time 19:01 Sent To  
Notes
2016-02-24 17:23:55APPROVED WITH EXCEPTIONS.
 1) A SEPARATE PERMIT APPLICATION, REVIEW AND PLANS ARE
 REQUIRED FOR THE GENERATOR.
 2) ADDITIONAL INFORMATION AND DETAILS ARE REQUIRED TO
 BE SUBMITTED FOR THE EXTERIOR MASONRY FIREPLACE AND
 CHIMNEY.
 3) REVISION REQUIRED FOR SHEET S-7 TO CORRECT WEST
 ELEVATION SO THAT IT CORRESPONDS WITH THE FLOOR PLANS.
2016-02-08 17:13:24SEE GENERATOR SUBMITTAL 16020245 TRAVELING WITH.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-01-22 Cont ID  
Sent By rmcdouga Date 2016-01-22 Time 16:50 Rev Time 0.00
Received By rmcdouga Date 2016-01-22 Time 06:57 Sent To  
Notes
2016-01-22 13:37:59PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) (NEW COMMENT) THE PERMIT APPLICATION IS MISSING FROM
 THE RESUBMITTAL. IF THE ORIGINAL IS NOT LOCATED A
 REPLACEMENT WILL BE REQUIRED.
  
 2) (PREVIOUS COMMENT) THE ENERGY COMPLIANCE FORMS
 SPECIFY R-20 CEILING INSULATION AND PLAN SHEET A-302
 HAS R-19 CEILING INSULATION. FBC 107.2.1
  
 3) (PREVIOUS COMMENT) THE REFERENCES TO THE STANDARDS
 ON SHEET S-1 ARE INCORRECT. THEY SHOULD BE AS FOLLOWS:
 ACI 318-11, ACI 530-11, ACI 530.1-11, ASCE 5-11, ASCE
 6-11, TMS 402-11 AND TMS 602-11. THE 2011 EDITIONS OF
 THESE STANDARDS ARE THE ONES THAT ARE REFERENCED IN
 CHAPTER 46 THE FBC FIFTH EDITION (2014).
  
 4) (NEW COMMENT) THE COMPONENT AND CLADDING PRESSURES
 FOR THE WALL AREAS ON SHEET S-1 ARE LOW FOR A TWO STORY
 STRUCTURE (25' MEAN ROOF HEIGHT) LOCATED IN EXPOSURE C.
 FBC-R301.2.1
  
 5) (PREVIOUS COMMENT) THE WEST ELEVATION DOES NOT MATCH
 THE FLOOR PLANS. THE EXTERIOR DOOR (ED 109) TO THE
 MASTER BATH IS SHOWN AS A WINDOW AND A WINDOW IS
 MISSING. THE SECOND FLOOR PLAN HAS TWO WINDOWS AND THE
 ELEVATION HAS THREE. FBC 107.2.1 SEE SHEETS A-100,
 A-101, A-201 AND S-7
  
 6) (PREVIOUS COMMENT) ADDITIONAL INFORMATION IS
 REQUIRED FOR THE MASONRY FIREPLACE AND CHIMNEY TO SHOW
 THAT IT WILL COMPLY WITH FBC R1001. PROVIDE DIMENSIONS
 AND DETAILS OF ALL PARTS AND COMPONENTS. FBC 107.2.1
 PROVIDE FIREBOX, DAMPER, SMOKE CHAMBER DIMENSIONS AND
 FLUE DIMENSIONS.
  
 7) (PREVIOUS COMMENT) FBC 107.3.4 - PROVIDE TWO SETS OF
 PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. NO
 PRODUCT APPROVALS WERE SUBMITTED FOR THE EXTERIOR DOORS
 OR WINDOWS. THE NOA NUMBERS ON THE LETTER FROM THE
 ARCHITECT DO NOT MATCH THE ONES THAT WERE SUBMITTED.
 ALSO, LIST ALL OF THE PRODUCT APPROVALS ON ONE LETTER.
  
 8) (PREVIOUS COMMENT) SUBMIT TWO SETS OF THE PRODUCT
 EVALUATION REPORT AND INSTALLATION INSTRUCTIONS FOR THE
 SPRAY FOAM INSULATION. FBC - R 316 SUBMIT THE PRODUCT
 EVALUATION REPORT FOR THE ICYNENE SPRAY FOAM.
  
 9) (PREVIOUS COMMENT) SUBMIT PRODUCT APPROVALS,
 MANUFACTURES' SPECIFICATIONS WITH INSULATION
 INSTRUCTIONS FOR THE COLONIAL AND BAHAMA SHUTTERS SHOWN
 ON THE ELEVATION DRAWINGS. FBC 107.2.1 & R301.2.1 THE
 PRODUCT APPROVAL FOR THE BAHAMA SHUTTERS IS EXPIRED AND
 NOTHING WAS SUBMITTED FOR THE COLONIAL SHUTTERS.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-01 Cont ID  
Sent By rmcdouga Date 2015-10-01 Time 18:23 Rev Time 0.00
Received By rmcdouga Date 2015-09-28 Time 17:59 Sent To  
Notes
2015-09-29 11:33:36PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 COMPLIANCE FORMS. FBC ENERGY CONSERVATION R103.1.1.2
  
 2) THE ENERGY COMPLIANCE FORMS SPECIFY R-20 CEILING
 INSULATION AND PLAN SHEET A-302 HAS R-19 CEILING
 INSULATION. FBC 107.2.1
  
 3) SUBMIT A SITE DRAINAGE PLAN THAT SHOWS COMPLIANCE
 WITH FBC - R401.3 SURFACE DRAINAGE SHALL BE DIVERTED TO
 A STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF
 COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE
 GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES (152
 MM) WITHIN THE FIRST 10 FEET (3048 MM).
  
 4) FBC - R302.5.1 REQUIRES A SELF-CLOSING DEVICE ON THE
 DOOR FROM THE GARAGE TO THE HABITABLE SPACE.
  
 5) GENERAL NOTE 1 ON SHEET A-100 INCORRECTLY REFERENCES
 THE 2010 FBC. THE FBC FIFTH EDITION (2014) WENT INTO
 EFFECT ON JUNE 30, 2015. ALL NEW PERMITS APPLIED FOR ON
 OR AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE FBC FIFTH EDITION.
  
 6) THE STRUCTURAL DESIGN CRITERIA NOTES ON SHEET S-1
 REFERENCE THE 2010 FBC. THE FBC FIFTH EDITION (2014)
 WENT INTO EFFECT ON JUNE 30, 2015. ALL NEW PERMITS
 APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED TO
 COMPLY WITH AND REFERENCE THE FBC FIFTH EDITION.
  
 7) THE REFERENCES TO THE FOLLOWING STANDARDS ON SHEET
 S-1 ARE INCORRECT, THEY SHOULD BE AS FOLLOWS: ACI
 318-11, ACI 530-11, ACI 530.1-11, ASCE 5-11, ASCE 6-11,
 TMS 402-11 AND TMS 602-11. THE 2011 EDITIONS OF THESE
 STANDARDS ARE THE ONES THAT ARE REFERENCED IN CHAPTER
 46 THE FBC FIFTH EDITION (2014).
  
 8) ON THE LOW ROOF AND HIGH ROOF FRAMING PLANS ON SHEET
 S-3, THE SECTION ID TAGS ARE INCORRECT. THEY DO NOT
 CORRESPOND WITH THE CORRECT SECTION DETAILS ON S-5. FBC
 107.2.1
  
 9) SECTION DETAIL 4 0N S-5 IS BLANK , HOWEVER, THERE IS
 A TAG FOR IT ON S-3. PLEASE CLARIFY. FBC 107.2.1
  
 10) THE WEST ELEVATION DOES NOT MATCH THE FLOOR PLANS.
 THE EXTERIOR DOOR (ED 109) TO THE MASTER BATH IS NOT
 SHOWN. THE SECOND FLOOR PLAN HAS TWO WINDOWS AND THE
 ELEVATION HAS THREE. FBC 107.2.1
  
 11) ADDITIONAL INFORMATION IS REQUIRED FOR THE MASONRY
 FIREPLACE AND CHIMNEY TO SHOW THAT IT WILL COMPLY WITH
 FBC R1001. PROVIDE DIMENSIONS AND DETAILS OF ALL PARTS
 AND COMPONENTS. FBC 107.2.1
  
 12) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.
  
 13) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE BORAL CEMENT ROOF TILE AND RESIST THE
 REQUIRED OVERTURN MOMENT. IF AN ADHESIVE WILL BE USED
 SUBMIT TWO SETS OF ITS PRODUCT APPROVAL. FBC - R
 301.2.1
  
 14) SUBMIT TWO SETS OF THE PRODUCT EVALUATION REPORT
 AND INSTALLATION INSTRUCTIONS FOR THE SPRAY FOAM
 INSULATION. FBC - R 316
  
 15) SUBMIT PRODUCT APPROVALS, MANUFACTURES'
 SPECIFICATIONS WITH INSULATION INSTRUCTIONS FOR THE
 COLONIAL AND BAHAMA SHUTTERS SHOWN ON THE ELEVATION
 DRAWINGS. FBC 107.2.1 & R301.2.1
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-02-19 Cont ID  
Sent By rmcdouga Date 2016-02-19 Time 18:15 Rev Time 0.00
Received By rmcdouga Date 2016-02-18 Time 19:01 Sent To  
Notes
2016-02-19 18:15:59APPROVED WITH EXCEPTIONS. REDLINE PLANS.
 A SEPARATE PERMIT IS REQUIRED FOR THE GENERATOR.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-01-22 Cont ID  
Sent By rmcdouga Date 2016-01-22 Time 18:56 Rev Time 0.00
Received By rmcdouga Date 2016-01-22 Time 07:10 Sent To  
Notes
2016-01-22 18:25:402ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRIC
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. THE LOAD
 CALCULATIONS, RISER DIAGRAM AND PANEL SCHEDULE ARE
 MISSING THIS. THE RISER DIAGRAM AND PANEL SCHEDULE ARE
 MISSING FROM THE RE-SUBMITTAL.
  
 2) SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED
 FOR THE GENERATOR.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-01 Cont ID  
Sent By rmcdouga Date 2015-10-01 Time 18:53 Rev Time 0.00
Received By rmcdouga Date 2015-10-01 Time 18:53 Sent To  
Notes
2015-10-01 18:34:511ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRIC
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. THE LOAD
 CALCULALTIONS, RISER DIAGRAM AND PANEL SCHEDULE ARE
 MISSING THIS.
  
 2) NEC 210.52(A) - (H) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL SPACE EXCEED 6' FROM AN OUTLET IN
 THE FAMILY ROOM AND MASTER BEDROOM.
  
 3) NEC 210.52 (C) (1) - A RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH COUNTERTOP SPACE 12 INCHES OR WIDER
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 2
 FEET MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN
 THAT SPACE.ALSO THE KITCHEN COUNTER TOP APPEARS TO BE
 MISSING A RECEPTACLE OUTLET.
  
 4) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE
 REQUIRED.
  
 5) NEC 210.12 (B) - OUTLETS ARE REQUIRED TO BE AFCI
 PROTECTED.
  
 6) NEC 210.52 (E)(1) - AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE WHILE STANDING AT GRADE LEVEL AND LOCATED
 NOT MORE THAN 6.5 FT. ABOVE GRADE SHALL BE INSTALLED AT
 THE FRONT AND BACK OF THE DWELLING. RECEPTACLE IS
 REQUIRED AT FRONT.
  
 7) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL
 BE PROVIDED.
  
 8) NEC 250.104(B) THE GAS PIPING IS REQUIRED TO BE
 BONDED.
  
 9) SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED
 FOR THE GENERATOR.
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2016-02-16 Cont ID  
Sent By tklarge Date 2016-02-16 Time 06:48 Rev Time 0.00
Received By tklarge Date 2016-02-16 Time 06:17 Sent To  
Notes
2016-02-16 06:50:34SEPARATE PERMIT REQD. FOR GAS.
 MANUFACTURER'S INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES/EQUIPMENT SHALL BE ONSITE FOR INSPECTION.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-01-13 Cont ID  
Sent By tklarge Date 2016-01-13 Time 12:14 Rev Time 0.00
Received By tklarge Date 2016-01-13 Time 09:12 Sent To  
Notes
2016-01-13 10:26:071) FYI - THE GAS PERMIT SHALL BE DONE UNDER A SEPARATE
 PERMIT WITH A SEPARATE PERMIT APPLICATION.SINCE THE GAS
 INFORMATION AND DRAWINGS HAVE BEEN SUBMITTED A REVIEW
 WILL BE PERFORMED ON THE DOCUMENTS.
 2) THE ARCHITECTURAL PLAN A-100 SHOWS THE FIREPLACE AS
 GAS BUT IT IS NOT SHOWN ON THE GAS RISER OR ON THE GAS
 PLAN VIEW DRAWING. CLARIFY.
 3) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS APPLIANCES. THE SPECIFICATION SHEETS SHALL CLEALY
 SHOW THAT THE APPLIANCES ARE LISTED AND LABELED IN
 ACCORDANCE WITH THE 2014 FBCR SEC.G2404.3. 2ND REQUEST.
 4) SHOW THE CORRESPONDING EHD FOR EACH SIZE OF CSST.THE
 DIFFERENT EHD NUMBERS CARRY DIFFERENT BTU LOADS.2ND
 REQUEST.
 5) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE DRYERS
 LOCATED IN THE LAUNDRY ROOMS. REFER TO 2014
 FBC-RESIDENTIAL SEC. G2407.1. NOTE: THERE IS AN E-MAIL
 IN THE DOCUMENTS FROM A DANIEL DOLBEE THAT STATES THE
 RANGE IS 154,00 BTU'S BUT THE GAS DRAWING SHOWS THE
 RANGE AS 108,000 BTU'S .CLARIFY.
 6) THE 2 PSI LINE TO THE GENERATOR, POOL HEATER AND
 TANKLESS WATER HEATER IS SHOWN AS PE PIPE ON THE PLAN
 DRAWING AND AS CSST ON THE RISER DIAGRAM. WHICH IS IT?
 IF CSST, IT IS UNDERSIZED. CLARIFY.
 7) SIZE THE GAS BRANCCH LINES TO THE GENERATOR,POOL
 HEATER AND TANKLESS WATER HEATER. WPB AMEND. TO FBC
 SEC. 107.3.5.3.
 8) SIZE ALL SECTIONS OF THE UNDERGROUND GAS PIPING
 SYSTEM ON THE RISER DIAGRAM.
 9) IDENTIFY THE COOKTOP ON THE GAS RISER AND SHOW THE
 BTU LOAD OF THE APPLIANCE.WPB AMEND. TO FBC SEC.
 107.3.5.3.
 10) SHOW THE LENGTH OF THE SECTION OF PIPE RISING UP
 INTO THE CEILING. WPB AMEND. TO FBC SEC. 107.3.5.3.
 11) SHOW THE LENGTH OF ALL DROPS TO THE APPLIANCES AND
 THE LENGTH OF THE SECTION OF PIPE TO THE 2ND FLOOR. IT
 APPEARS LIKE THE TOTAL DEVELOPED LENGTH WILL EXCEED 100
 FEET.
 12) THE 1/2 PSI GALVANIZED PIPING UP TO THE CEILING IS
 UNDERSIZED.
 13) SHOW THE LENGTH OF EACH CUT SECTION OF PIPE ON THE
 RISER DIAGRAM. 2014 FBCR SEC. G2413.4.
 14) THE GREEN MARKER USED ON THE SIZING TABLE HAS MADE
 THE NUMBERS ON THE TABLES ILLEGIBLE. SUBMIT CLEAN
 SIZING TABLES.
 15) SHT. A-100 SHOWS THE TANKLESS WATER HEATER IN A
 WEATHERPROOF ENCLOSURE. SUBMIT DETAILS ON THE WATER
 HEATER AS TO HOW COMBUSTION AIR AND EXHAUST WILL
 ADDRESSED. WILL BE PROVIDED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-08-21 Cont ID  
Sent By tklarge Date 2015-08-21 Time 02:54 Rev Time 0.00
Received By tklarge Date 2015-08-21 Time 02:27 Sent To  
Notes
2015-08-21 02:54:061) IDENTIFY THE MODEL OF THE GENERATOR ON THE GENERAC
 SPEC. SHEETS. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE LOCATION OF THE POOL HEATER AND GENERATOR
 ON THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
 3) THE GENERATOR IS NOT SHOWN ON THE GAS DRAWING OR
 INCLUDED IN THE DESIGN LOAD OF THE GAS SYSTEM.
 4) THE GAS DRAWING SHOWS THE DRYER AS GAS BUT IT IS
 SHOWN ON THE PLANS AND ON THE ELECTRICIAN'S LOAD CALCS
 AS ELECTRIC. CLARIFY. WPB AMEND. TO FBC SEC. 107.2.1.
 5) SHOW THE LOCATION OF THE GAS WATER HEATERS ON THE
 PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
 6) SUBMIT MANUF. SPECS FOR ALL GAS APPLIANCES /
 EQUIPMENT.APPLIANCES /EQUIPMENT SHALL BE LISTED AND
 LABELED PER 2014 FBC-R SEC. G2404.3.
 7) SUBMIT A GAS PLAN SHOWING THE LOCATION OF THE PE
 PIPE IN RELATION TO THE STRUCTURE. PE PIPE CAN ONLY BE
 USED OUTSIDE UNDERGROUND. 2014 FBC-R SEC.G2415.17.1.
 8) SHOW THE LOCATION OF ALL THE MP
 REGULATORS.REGULATORS SHALL COMPLY WITH 2014 FBC-R SEC.
 G2421.2 (4) [ACCESSIBLE & VENTED TO EXTERIOR], G 2421.2
 (5) (6) [SUPPLIED WITH TEE FITTING FOR MEASURING
 INSTRUMENT & SEDIMENT TRAP.]
 9) SUBMIT MANUF. SPECS FOR THE MP REGULATORS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 10) THE SIZING TABLE SUBMITTED FOR THE PE PIPE IS FROM
 AN OUTDATED CODE STANDARD. THERE HAVE BEEN 2 CODE CYLE
 CHANGES SINCE 2007. SUBMIT COPIES OR REFERNCE THE
 CORRECT AND UPDATED SIZING TABLES USED FOR THE GAS
 DESIGN. WPB AMEND. TO FBC SEC. 107.2.1.
 11) SHOW THE CORRESPONDING EHD FOR THE CSST PIPE. THE
 DIFFERENT EHD NUMBER CARRIES DIFFERNT BTU LOADS.
 12) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE
 APPLIANCES. 2014 FBC-R SEC. G2407.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-24 Cont ID  
Sent By rmcdouga Date 2016-02-24 Time 17:53 Rev Time 0.00
Received By rmcdouga Date 2016-02-08 Time 13:01 Sent To  
Notes
2016-02-08 13:02:01R32

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-22 Cont ID  
Sent By rmcdouga Date 2016-01-22 Time 18:56 Rev Time 0.00
Received By rmcdouga Date 2016-01-08 Time 16:42 Sent To  
Notes
2016-01-08 16:42:56TLARGE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-01 Cont ID  
Sent By rmcdouga Date 2015-10-01 Time 18:53 Rev Time 0.00
Received By rmcdouga Date 2015-08-12 Time 13:42 Sent To  
Notes
2015-08-12 13:42:20R31

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-01-22 Cont ID  
Sent By rmcdouga Date 2016-01-22 Time 07:53 Rev Time 0.00
Received By rmcdouga Date 2016-01-22 Time 07:53 Sent To  
Notes
2016-01-22 07:54:30MU 2015-17460 PAID $318.50
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-09-28 Cont ID  
Sent By rmcdouga Date 2015-09-28 Time 17:57 Rev Time 0.00
Received By rmcdouga Date 2015-09-28 Time 17:57 Sent To  
Notes
2015-09-28 17:59:05SUBMIT A COPY OF THE PAID IMPACT FEE RECEIPT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-01-22 Cont ID  
Sent By rmcdouga Date 2016-01-22 Time 17:38 Rev Time 0.00
Received By rmcdouga Date 2016-01-22 Time 07:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-09-29 Cont ID  
Sent By rmcdouga Date 2015-09-29 Time 11:31 Rev Time 0.00
Received By rmcdouga Date 2015-09-29 Time 07:29 Sent To  
Notes
2015-09-29 08:09:47PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. THE MECHANICAL
 PLANS ARE REQUIRED TO HAVE THE NAME, SIGNATURE AND
 LICENSE NUMBER OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 2) THE MODEL NUMBERS AND SPECIFICATIONS FOR THE HEATING
 AND COOLING EQUIPMENT FOR THE EQUIPMENT SCHEDULE ON THE
 MECHANICAL PLAN DO NOT CORRESPOND WITH THE EQUIPMENT
 SIZING CALCULATIONS FOR ZONES #1 AND #3. FBC 107.2.1
  
 3) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 COMPLIANCE FORMS. FBC ENERGY CONSERVATION R103.1.1.2
  
 4) THE ENERGY COMPLIANCE FORMS SPECIFY R-20 CEILING
 INSULATION AND PLAN SHEET A-302 HAS R-19 CEILING
 INSULATION. FBC 107.2.1
  
 5) SPECIFY THE LOCATIONS OF THE THREE CONDENSING UNITS
 ON THE PLANS. FBC 107.2.1
  
 6) THE LOCATIONS OF THE THREE AIR HANDLERS SHOWN ON
 ARCHITECTURAL PLAN SHEET A-101 DO NOT MATCH THE
 LOCATIONS SHOWN ON THE MECHANICAL PLANS. FBC 107.2.1
  
 7) FBC-R - M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 20 FEET (1829 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE.
  
 8) FBC-R - M1305.1.3.2 AIR-HANDLING UNITS.
 2014 FBC ENERGY CONSERVATION R403.2.4
 AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE
 FOLLOWING CONDITIONS ARE MET:
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC.
  
 9) FBC-R - M1305.1.3.1 ELECTRICAL REQUIREMENTS.
 A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34.
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-02-16 Cont ID  
Sent By tklarge Date 2016-02-16 Time 06:16 Rev Time 0.00
Received By tklarge Date 2016-02-16 Time 03:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-01-13 Cont ID  
Sent By tklarge Date 2016-01-13 Time 09:12 Rev Time 0.00
Received By tklarge Date 2016-01-13 Time 09:10 Sent To  
Notes
2016-01-13 09:12:121)SUBMIT A SANITARY RISER DIAGRAM FOR THE PLUMBING
 SYSTEM FOR THE NEW STRUCTURE. WPB AMEND. TO FBC SEC.
 107.3.5.3.
 2) THE PLANS SHOW 4 AREA DRAINS. WHERE DO THEY
 DISCARGE? IS THERE AN EXFILTRATION TRENCH? IF SO,
 SUBMIT A DETAIL FOR THE EXFILTRATION TRENCH.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-08-21 Cont ID  
Sent By tklarge Date 2015-08-21 Time 02:27 Rev Time 0.00
Received By tklarge Date 2015-08-21 Time 01:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-08-25 Cont ID  
Sent By sgraham Date 2015-08-25 Time 08:55 Rev Time  
Received By sgraham Date   Time   Sent To  
Notes
2015-08-25 08:56:538/25/15
  
 SEPARATE PERMITS AND PLANS REQUIRED FOR LANDSCAPING AND
 DRIVEWAY.
2015-08-17 11:29:018/17/15