Plan Review Details - Permit 15080352
| Plan Review Stops For Permit 15080352 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2015-09-22 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-09-22 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-09-22 |
Time |
14:20 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-09-09 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-09-09 |
Time |
18:25 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-09-09 |
Time |
17:51 |
Sent To |
I |
|
| Notes |
| 2015-09-09 18:32:36 | 1. ELECTRICAL NOTE 1 HAS THE CODE REFERENCES MIXED UP. | | | NATIONAL ELECTRICAL CODE (NEC) ARTICLE 760, IT SHALL | | | ALSO ADDRESS NFPA 72. NFPA 70 IS THE SAME AS THE NEC. | | | 2. PER FBC-907 YOU SHALL PROVIDE YOUR SCOPE OF WORK ON | | | THE DRAWINGS, AND CLEARLY DEFINE THE WORK. | | | 3. PER FBC 907 YOU SHALL LABEL AND/OR IDENTIFY EVERY | | | ROOM AS TO ITS INTENDED USE. | | | 4. COPPER TAN IS LACKING NOTIFICATION APPLIANCES. | | | 5. CORRECT THE RISER DIAGRAM TO INCLUDE THE ADDED | | | NOTIFICATION APPLIANCES. | | | 6. UPDATE ALL YOUR CALCS TO INCLUDE THE ADDITIONAL | | | DEVICES. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | | | | PS: IF AT ALL POSSIBLE, PLEASE CONSIDER FILING | | | ELECTRONICALLY IN THE FUTURE. IT IS NOT ONLY BETTER ON | | | THE ENVIRONMENT, BUT USUALLY A QUICKER TURN AROUND. | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2015-09-22 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2015-09-22 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2015-09-22 |
Time |
14:16 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2015-08-20 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2015-08-20 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2015-08-20 |
Time |
11:03 |
Sent To |
E |
|
| Notes |
| 2015-08-20 11:04:31 | PERMIT #15080352 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | APPROVED WITH COMMENTS: | | | | | | 1) ONE (1) ADDITIONAL HORN STROBE IS REQUIRED FOR | | | JERRY'S ART-A-RAMA FOR PROPER COVERAGE. | | | | | | | | | SUE ELLEN CALDERON | | | ASST. FIRE MARSHAL | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-09-22 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-09-22 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-09-18 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2015-09-22 15:53:11 | 9/22/15 - PASSED ELECTRICAL & FIRE REVIEWS. CONTRACTOR | | | NOTIFIED VIA EMAIL. SENT TO SMALL READY BIN "T". MA | | 2015-09-21 10:42:18 | RESUB ROUTED TO FIRE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
F |
Date |
2015-09-09 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-09-09 |
Time |
18:34 |
Rev Time |
|
| Received By |
albarran |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2015-09-09 18:35:16 | 9/9/15 - FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR | | | NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "T". MA |
|
|
|