Plan Review Details - Permit 15080324
Plan Review Stops For Permit 15080324
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-10-30 Cont ID  
Sent By jwitmer Date 2015-10-30 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2015-10-30 Time 06:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-02 Cont ID  
Sent By jwitmer Date 2015-10-02 Time 15:32 Rev Time 0.00
Received By jwitmer Date 2015-10-02 Time 14:04 Sent To  
Notes
2015-10-02 15:31:59BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080324
 ADD: 7800 OKEECHOBEE BLVD SUITE # A18
 CONT: THE EVERGLADES GROUP
 TEL: (561)912-0400
 E-MAIL:[email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2014 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRIDAY OCT. 02/2015
 ACTION: DENIED
  
 1A) 2014 EXISITNG BUILDING CODE 806.1 A BUILDING,
 FACILITY, OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE,
 ACCESSIBILITY. THE DOOR TO RESTROOM 106 IS NOT
 ACCESSIBLE WITH THE WIDTH OF THE CORRIDOR AT 51 INCHES
 WIDE. 202.4.1 DISPROPORTIONATE COST UP TO 20 % OF THE
 CONTRACT VALUE OR $51,412.00 DOLLORS IN ACCESSIBLE
 UPGRADES. THERE IS AN ACCESSIBLE ENTRANCE WITH BOTH
 FRONT DOORS BEING ON AN ACCESSIBLE ROUTE. THE NEXT AREA
 IS AN ACCESSIBLE ROUTE TO ALTERED AREAS, AND THEN
 RESTROOMS THE DOOR # 106 YOU CAN NOT GET BY IT. SHEET
 A-905 DETAIL (E) SHOWS A MINIMUM OF 54 INCHES TO WHEEL
 BY THAT DOOR. PLEASE SHOW HOW COMPLIANCE WITH 2014
 ACCESS. CODE FIGURE 404.2.4.1(E) WILL BE ACHIEVED.
  
 NOTE A SIMPLE FIX FOR THIS DOOR AS WELL AS THE MENS
 RESTROOM DOOR IS THE USE OF A INSWING DOOR. 2014
 ACCESS. CODE 603.2.3 DOOR SWING EXCEPTION # 2. WHERE
 THE TOILET ROOM OR BATHING ROOM IS FOR INDIVIDUAL USE
 AND A CLEAR FLOOR SPACE COMPLYING WITH 305.3 IS
 PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE DOOR
 SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE CLEAR
 FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY FIXTURE
  
 1A) 1ST REVIEW COMMENT. SHEET A-120 & A-250 THE LIFE
 SAFETY PLAN INDICATES THE CORRIDOR INFRONT OF THE
 RESTROOMS TO BE 4'-3" OR 51 INCHES WIDE. PLEASE COMPLY
 WITH SECTION 1005.7.1 DOOR SWING. DOORS, WHEN FULLY
 OPENED, SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN 7 INCHES (178 MM). DOORS IN ANY POSITION SHALL NOT
 REDUCE THE REQUIRED WIDTH BY MORE THAN ONE-HALF.
 36INCHES + 22 INCHES(1/2 0F 44 INCHES)= 58 INCHES
 MINIMUM.
  
 1B) COMPLIED.
  
 1C) COMPLIED, NOT A ACCESSIBLE EXIT
  
 2) COMPLIED.
  
 3) RESPONSE INDICATES RESTROOMS ARE EXISITNG AND THE
 EXISITNG DRAWING INDICATE MOISTURE RESISTANT BOARD IN
 THESE AREAS. PLEASE SEE THERE APPEARS TO BE A
 DISCREPANCY IN THE PLANS. THE COVERSHEET UNDER THE
 SCOPE OF WORK; COMPLETE RENOVATION OF DINING ROOM,
 KITCHEN AND RESTROOM VERSES SHEET A 250 AREA NOT IN
 SCOPE OF WORK GRAY SHADED AREA. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-28 Cont ID  
Sent By jwitmer Date 2015-08-28 Time 07:27 Rev Time  
Received By jwitmer Date 2015-08-28 Time 05:59 Sent To  
Notes
2015-08-28 07:27:35BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080324
 ADD: 7800 OKEECHOBEE BLVD SUITE # A18
 CONT: THE EVERGLADES GROUP
 TEL: (561)912-0400
 E-MAIL:[email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2014 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRIDAY OCT. 02/2015
 ACTION: DENIED
  
 1A) 2014 EXISITNG BUILDING CODE 806.1 A BUILDING,
 FACILITY, OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE,
 ACCESSIBILITY. THE DOOR TO RESTROOM 106 IS NOT
 ACCESSIBLE WITH THE WIDTH OF THE CORRIDOR AT 51 INCHES
 WIDE. 202.4.1 DISPROPORTIONATE COST UP TO 20 % OF THE
 CONTRACT VALUE OR $51,412.00 DOLLORS IN ACCESSIBLE
 UPGRADES. THERE IS AN ACCESSIBLE ENTRANCE WITH BOTH
 FRONT DOORS BEING ON AN ACCESSIBLE ROUTE. THE NEXT AREA
 IS AN ACCESSIBLE ROUTE TO ALTERED AREAS, AND THEN
 RESTROOMS THE DOOR # 106 YOU CAN NOT GET BY IT. SHEET
 A-905 DETAIL (E) SHOWS A MINIMUM OF 54 INCHES TO WHEEL
 BY THAT DOOR. PLEASE SHOW HOW COMPLIANCE WITH 2014
 ACCESS. CODE FIGURE 404.2.4.1(E) WILL BE ACHIEVED.
  
 NOTE A SIMPLE FIX FOR THIS DOOR AS WELL AS THE MENS
 RESTROOM DOOR IS THE USE OF A INSWING DOOR. 2014
 ACCESS. CODE 603.2.3 DOOR SWING EXCEPTION # 2. WHERE
 THE TOILET ROOM OR BATHING ROOM IS FOR INDIVIDUAL USE
 AND A CLEAR FLOOR SPACE COMPLYING WITH 305.3 IS
 PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE DOOR
 SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE CLEAR
 FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY FIXTURE
  
 1A) 1ST REVIEW COMMENT. SHEET A-120 & A-250 THE LIFE
 SAFETY PLAN INDICATES THE CORRIDOR INFRONT OF THE
 RESTROOMS TO BE 4'-3" OR 51 INCHES WIDE. PLEASE COMPLY
 WITH SECTION 1005.7.1 DOOR SWING. DOORS, WHEN FULLY
 OPENED, SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN 7 INCHES (178 MM). DOORS IN ANY POSITION SHALL NOT
 REDUCE THE REQUIRED WIDTH BY MORE THAN ONE-HALF.
 36INCHES + 22 INCHES(1/2 0F 44 INCHES)= 58 INCHES
 MINIMUM.
  
 1B) COMPLIED.
  
 1C) COMPLIED, NOT A ACCESSIBLE EXIT
  
 2) COMPLIED.
  
 3) RESPONSE INDICATES RESTROOMS ARE EXISITNG AND THE
 EXISITNG DRAWING INDICATE MOISTURE RESISTANT BOARD IN
 THESE AREAS. PLEASE SEE THERE APPEARS TO BE A
 DISCREPANCY IN THE PLANS. THE COVERSHEET UNDER THE
 SCOPE OF WORK; COMPLETE RENOVATION OF DINING ROOM,
 KITCHEN AND RESTROOM VERSES SHEET A 250 AREA NOT IN
 SCOPE OF WORK GRAY SHADED AREA. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-09-15 Cont ID  
Sent By ppetty Date 2015-09-15 Time 09:05 Rev Time 0.00
Received By ppetty Date 2015-09-15 Time 09:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-10-19 Cont ID  
Sent By scaldero Date 2015-10-19 Time 13:46 Rev Time 0.00
Received By scaldero Date 2015-10-19 Time 13:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-10-13 Cont ID  
Sent By scaldero Date 2015-10-13 Time 14:18 Rev Time 0.00
Received By scaldero Date 2015-10-13 Time 14:18 Sent To  
Notes
2015-10-13 14:19:41DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL PLAN REVIEWERS' COMMENTS HAVE
 BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-08-31 Cont ID  
Sent By scaldero Date 2015-08-31 Time 14:54 Rev Time 0.00
Received By scaldero Date 2015-08-31 Time 14:37 Sent To  
Notes
2015-08-31 14:51:27PERMIT # 15080324
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) SEE COMMENTS UNDER BUILDING REVIEW AND MECHANICAL
 REVIEW.
  
 2) PLANS MUST LIST AND COMPLY WITH THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-30 Cont ID  
Sent By jwitmer Date 2015-10-30 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2015-10-14 Time 10:50 Sent To  
Notes
2015-10-15 16:38:05B13

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-15 Cont ID  
Sent By cpuell Date 2015-10-13 Time 10:49 Rev Time 0.00
Received By cpuell Date 2015-09-28 Time 10:43 Sent To  
Notes
2015-09-28 10:43:38B29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-15 Cont ID  
Sent By ppetty Date 2015-09-15 Time 09:06 Rev Time 0.00
Received By ppetty Date 2015-09-15 Time 08:19 Sent To  
Notes
2015-08-11 09:21:49B28

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-10-20 Cont ID  
Sent By ccole Date 2015-10-20 Time 10:24 Rev Time 0.00
Received By ccole Date 2015-10-20 Time 10:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-10-07 Cont ID  
Sent By ccole Date 2015-10-07 Time 09:51 Rev Time 0.00
Received By ccole Date 2015-10-07 Time 09:50 Sent To  
Notes
2015-10-07 10:07:442ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080324
 10/7/15
  
 1) THE TRANE 6-TON SYSTEM HAS AN AIRFLOW CAPACITY THAT
 WILL EXCEED 2000 CFM'S- PLEASE REFER TO SECTION 606.2.1
 AND PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN AIR
 SYSTEM. INDICATE CONTROL OPERATION AND SUPERVISORY
 DETAILS FOR THE DEVICE- SEE SECTIONS 606.4 AND 606.4.1.
 2) SHEET M1.1: PLEASE RELOCATE THE RETURN AIR GRILLS
 FOR AHU-1 SHOWN ON THE PLAN IN CLOSE PROXIMITY OF THE
 EXHAUST HOOD- SEE TABLE 403.3 (OCCUPANCY
 CLASSIFICATION-KITCHENS) FOOTNOTE B.
 3) M1.2: REMOVE THE WINDLOAD DETAILS FOR THE 3-TON CU,
 AND REPLACE WITH DETAILS FOR THE 6-TON UNIT. SEE
 COMMENT #3 FROM THE 1ST REVIEW: MIAMI TECH AC STAND
 NOA- AS PREVIOUSLY REQUESTED PLEASE CIRCLE, HIGHLIGHT,
 OR OTHERWISE MARK ALL APPLICABLE DETAILS, NOTES, DESIGN
 PRESSURES, TABLES, ETC. SHOWN ON THE DOC PERTAINING TO
 THE PROPOSED INSTALLATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-17 Cont ID  
Sent By ccole Date 2015-08-17 Time 11:34 Rev Time 0.00
Received By ccole Date 2015-08-17 Time 11:29 Sent To  
Notes
2015-08-17 11:38:051ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080324
 8/17/15
  
 1) SHEET M1.1: PLEASE PROVIDE A NOTE INDICATING THAT
 THE WALK-IN COOLER AND FREEZER WILL BE UNDER A SEPARATE
 PERMIT.
 2) PLEASE PROVIDE THE KITCHEN PLANS SHOWN IN THE INDEX
 AS K0.1- K5.2
 3) REFER TO SECTION 301.15 FBC-14 MECHANICAL: WIND
 RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
 PLEASE PROVIDE THE DESIGN PRESSURES ON THE PLANS AND
 SUBMIT TWO COPIES OF THE NOA #13-1017.09 FOR THE
 MIAMI-TECH ROOF STAND WITH ALL APPLICABLE INSTALLATION
 DETAILS, NOTES, SCHEDULES, AND TABLES CIRCLED,
 HIGHLIGHTED, OR OTHERWISE MARKED TO CORRELATE WITH THE
 INSTALLATION DESIGN SHOWN ON THE PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-10-05 Cont ID  
Sent By tklarge Date 2015-10-05 Time 05:10 Rev Time 0.00
Received By tklarge Date 2015-10-05 Time 04:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-08-27 Cont ID  
Sent By tklarge Date 2015-08-27 Time 15:24 Rev Time 0.00
Received By tklarge Date 2015-08-26 Time 11:50 Sent To  
Notes
2015-08-26 15:24:541) WALLS WITHIN TWO FEET OF WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD NONABSORBANT SURFACE TO A HEIGHT OF 4
 FEET.THE PLANS NOTE "WASHABLE FLAT PAINT". MY CONCERN
 IS OF THE DURABILITY OF THE PAINT TO WITHSTAND THE
 ENVIRONMENT TO WHICH IT WILL BE SUBJECTED.
 2) SHT.P0.1 HAS GREASE TRAP CALCULATIONS FOR A 750
 GALLON GREASE TRAP YET SHT. P0.2 REFERS TO A 1250
 GALLON GREASE TRAP. CLARIFY.
 3) SHT.P0.2 - THE REFERENCED TABLE FOR THE 2 PSI GAS
 SYSTEM IS INCORRECT. THE TABLE NUMBER IN THE 2014
 FBC-FUEL GAS IS 402.4 (5). PLEASE REVISE.
 4) THE SANITARY LINE FOR THE FLOOR SINKS SHALL BE
 VENTED.FBC-PLUMBING SEC.901.2.
 5) SUBMIT A SLAB REPAIR DETAIL FOR THE REPAIR OF ANY
 POTION OF THE EXISTING SLAB THAT WILL HAVE TO BE CUT TO
 ACCOMMODATE THE REROUTING OF ANY PLUMBING. WPB AMEND.
 TO FBC SEC. 107.2.1.
 6) PROVIDE THE KITCHEN DRAWINGS NOTED ON THE COVER
 SHEET FOR REVIEW.WPB AMEND. TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  