Plan Review Details - Permit 15080269
Plan Review Stops For Permit 15080269
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-09 Cont ID  
Sent By skennedy Date 2015-09-09 Time 12:05 Rev Time 0.00
Received By skennedy Date 2015-09-09 Time 12:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-27 Cont ID  
Sent By jwitmer Date 2015-08-27 Time 11:00 Rev Time 0.00
Received By jwitmer Date 2015-08-26 Time 15:22 Sent To  
Notes
2015-08-27 11:00:52BUILDING PLAN REVIEW
 W. P. B. PERMIT:15080269
 ADD: 7501 N. JOG RD.
 CONT: AMERICAN ENGINEERS & CONTRATORS
 TEL: (561)889-6621
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. AUGUST 27/2015
 ACTION: DENIED
  
 1) WED. AUGUST 26/ 2015 CALLED DESIGNER OF RECORD PERRY
 DOUGLAS IN ORDER TO FIND OUT THE HEIGHT OF THE MODULAR
 PARTITION SYSTEM. I RECEIVED MR. DOUGLAS'S VOICE MAIL.
 THE ISSUE THE PLANS DO NOT INDICATE HOW TALL THE
 MODULAR PARTITIONS ARE, DO THEY GO ALL THE WAY TO THE
 CEILING, AT 6'-0", THE PLANS DO NOT INDICATE?
 COMPLIANCE WITH 2014 FBC-B TABLE 1604.3 CAN NOT BE
 DETERMINED OR IF FOOTNOTE B IS A DETERMINING FACTOR.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-09-09 Cont ID  
Sent By skennedy Date 2015-09-09 Time 12:05 Rev Time 0.00
Received By skennedy Date 2015-09-09 Time 12:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-28 Cont ID  
Sent By skennedy Date 2015-08-28 Time 16:44 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
2015-08-28 16:52:551ST REVIEW: FBC 2014 5TH ED.
 NEC 2011
  
 THE ELECTRICAL PLAN LACKS MINIMUM DETAIL AS FOLLOWS:
  
 FBC- 107.3.5.3 ? SHOW WIRING METHOD, CONDUCTOR TYPE &
 SIZES, CONDUIT DETAIL, PANEL SCHEDULES AND SHOW
 CIRCUITS OR PROVIDE ADEQUATE NOTES;
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-21 Cont ID  
Sent By pleduc Date 2015-08-21 Time   Rev Time 0.00
Received By pleduc Date 2015-08-20 Time 13:29 Sent To  
Notes
2015-08-21 10:01:38THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 ANY WORK ON THE FIRE ALARM AND FIRE SPRINKLER SYSTEMS
 SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-28 Cont ID  
Sent By skennedy Date 2015-08-28 Time 16:44 Rev Time 0.00
Received By skennedy Date 2015-08-07 Time 16:07 Sent To  
Notes
2015-08-07 16:08:00B01

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-08-28 Cont ID  
Sent By skennedy Date 2015-08-28 Time 16:44 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved