| 2015-08-17 16:44:30 | BUILDING PLAN REVIEW |
| | REVISION: 15080255 |
| | PERMIT:14071105 |
| | ADD: 1517 CAMERON SAMUEL LN. |
| | CONT: KAST |
| | TEL: (561)346-4994 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: MON. AUG.17/2015 |
| | ACTION: DENIED |
| | |
| | ROOF SUBMITTALS; |
| | |
| | 1) FLAT ROOF: |
| | 1A) THE ENGINEERING FROM FORENSIC ENGINEERING IS A COPY |
| | NOT THE SIGNED SEALED ORIGINALS. 61G15-30.003 |
| | ENGINEERING DOCUMENT CLASSIFICATION. ENGINEERS SHALL |
| | LEGIBLY INDICATE THEIR NAME AND BUSINESS ADDRESS, ON |
| | ENGINEERING DOCUMENTS. ENGINEERING DOCUMENTS WHICH ARE |
| | ISSUED FOR PRELIMINARY OR CONCEPTUAL USE, SHALL CLEARLY |
| | NOTE THE INTENDED PURPOSE OF SUCH DOCUMENTS. |
| | |
| | 1B) THE FORENSIC ENGINEERING SHEET WIND DESIGN CRITERIA |
| | IS 170 MPH AND EXPOSURE D. PLEASE REVIEW THE STRUCTURAL |
| | SHEET S6 THE WIND DESIGN |
| | IS 180 MPH, EXPOSURE C RISK CATEGORY III. PLEASE |
| | RE-CALCULATE THE PRESSURES AND ANCHORING TO THE CORRECT |
| | CRITERIA. 2010 FBC-B 2010 FBC-B 1609.1.1 DETERMINATION |
| | OF WIND DESIGN- CHAPTER 6 OF ASCE 7-10. |
| | |
| | 2) SLOPED ROOFS METAL |
| | 2A) THE ENGINEERING SHEET FROM GFA CARLOS MERCADO P.E. |
| | IS A COPY NOT THE SIGNED SEALED ORIGINALS. 61G15-30.003 |
| | ENGINEERING DOCUMENT CLASSIFICATION. ENGINEERS SHALL |
| | LEGIBLY INDICATE THEIR NAME AND BUSINESS ADDRESS, ON |
| | ENGINEERING DOCUMENTS. ENGINEERING DOCUMENTS WHICH ARE |
| | ISSUED FOR PRELIMINARY OR CONCEPTUAL USE, SHALL CLEARLY |
| | NOTE THE INTENDED PURPOSE OF SUCH DOCUMENTS. |
| | |
| | 2B) PLEASE NOT THE GFA ENGINEEREING INCLUDES METAL ROOF |
| | SYSTEMS FOR 2 BUILDINGS; |
| | 1) CLUBHOUSE |
| | 2) TOWER ROOF |
| | |
| | PLEASE NOTE THERE WILL BE (2) DESIGN CRITERIA REQUIRED. |
| | THE CLUBHOUSE IS DESIGNED TO 180 MPH EXPOSURE C |
| | BUILDING CATEGORY III, WHERE AS THE TOWER ROOF IS ONLY |
| | A BUILDING CATEGORY II THE WIND DESIGN AT 170 MPH. |
| | PLEASE ALSO NOTE THERE WILL BE 2 DIFFERENT MEAN ROOF |
| | HEIGHTS INVOLVED. |
| | 2010 FBC-B 2010 FBC-B 1609.1.1 DETERMINATION OF WIND |
| | DESIGN- CHAPTER 6 OF ASCE 7-10. PLEASE RECALCULATE TO |
| | THE APPROPRIATE WIND DESIGN FOR EACH OF THE BUILDINGS. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |