| 2015-08-10 09:10:42 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 5TH EDITION 2014 |
| | |
| | PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | SAM 3 90 SPEC SHEETS, STC & IIC TEST REPORTS PROVIDED |
| | |
| | NOTE - THE MANUFACTURER HAS BEEN CONTACTED VIA EMAIL |
| | (CONTRACTOR CC'D) ABOUT POSSIBLE USE OF SUPERSAM 125. |
| | TEST REPORTS HAVE BEEN PROVIDED FOR THIS PRODUCT BUT A |
| | LETTER ON LETTERHEAD IS REQUIRED FOR THE IIC (ASTM E |
| | 492) STATING THAT THE ASSEMBLY TESTED (QUARRY TILE, |
| | MORTAR BED, OVER 6" SLAB) IS EQUIVALENT TO AN 8.25" (OR |
| | THINNER) SLAB, CERAMIC TILE. IF PROVIDED, THIS LETTER |
| | WILL BE PUT ON FILE. |
| | |
| | 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | |
| | THE TEST REPORT PROVIDED INCLUDES A DROPPED INSULATED |
| | GYPSUM BOARD CEILING ASSEMBLY, CASTELE TRAVERTINE TILE |
| | IN A MORTAR BED. THIS IS NOT CONSISTENT WITH THE |
| | PROPOSED INSTALLATION. |
| | |
| | 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. |
| | |
| | THE TEST REPORT PROVIDED INCLUDES A DROPPED INSULATED |
| | GYPSUM BOARD CEILING ASSEMBLY, CASTELE TRAVERTINE TILE |
| | IN A MORTAR BED. THIS IS NOT CONSISTENT WITH THE |
| | PROPOSED INSTALLATION. |
| | |
| | 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM |
| | E 84 OR UL 723. |
| | |
| | 4. TO AVOID MULTIPLE PLAN REVIEWS, A PRELIMINARY REVIEW |
| | WILL BE DONE VIA EMAIL UNDER THE FOLLOWING CONDITIONS: |
| | |
| | QUALIFIER IS TO REVIEW THE COMMENT LIST AND DOCUMENTS |
| | PROPOSED. FOR THE ACOUSTICAL (STC & IIC) TESTS, |
| | QUALIFIER TO HIGHLIGHT THE ASSEMBLY (SPECIFICALLY WHERE |
| | NO DROPPED CEILING WAS USED IN THE TEST) AS WELL AS THE |
| | TEST RESULT. |
| | FOR THE FLAME SPREAD, QUALIFIER IS TO HIGHLIGHT THE |
| | TEST STANDARD (SHOULD BE EITHER ASTM E 84 OR UL 723) |
| | AND TEST RESULT. |
| | |
| | DUE TO CURRENT WORK LOAD AND LACK OF TIME TO MAINTAIN |
| | TARGET TURNAROUND TIMES, IF APPLICANT IS UNABLE TO |
| | COMPLY WITH ITEM 4, THE COURTESY REVIEW VIA EMAIL WILL |
| | NOT BE DONE. PLEASE RESUBMIT AT THE BUILDING DIVISION |
| | COUNTER. |
| | |