Plan Review Details - Permit 15080179
Plan Review Stops For Permit 15080179
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-28 Cont ID  
Sent By rmcdouga Date 2015-09-28 Time 08:17 Rev Time 0.00
Received By rmcdouga Date 2015-09-28 Time 07:15 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-01 Cont ID  
Sent By rmcdouga Date 2015-09-01 Time 15:55 Rev Time 0.00
Received By rmcdouga Date 2015-09-01 Time 15:55 Sent To  
Notes
2015-09-01 16:01:21PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON
 6/30/2015. THE BUILDING PROVISIONS FOR PRIVATE SWIMMING
 POOLS IN THE FBC RESIDENTIAL HAVE BEEN MOVED TO CHAPTER
 45. UPDATE ALL REFERENCED BUILDING CODE SECTIONS TO THE
 CURRENT CODE.
  
 2) THE POOL PERMIT WILL NOT BE ISSUED UNTIL THE
 APPLICATION FOR THE POOL ELECTRICAL SUB-PERMIT IS
 SUBMITTED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-09-28 Cont ID  
Sent By rmcdouga Date 2015-09-28 Time 08:05 Rev Time 0.00
Received By rmcdouga Date 2015-09-28 Time 07:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-09-01 Cont ID  
Sent By rmcdouga Date 2015-09-01 Time 15:55 Rev Time 0.00
Received By rmcdouga Date 2015-09-01 Time 15:14 Sent To  
Notes
2015-09-01 15:50:35PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON
 6/30/2015. THE ELECTRICAL PROVISIONS FOR PRIVATE
 SWIMMING POOLS ARE NOW INCORPORATED INTO THE 2014 FBC
 RESIDENTIAL CHAPTER 42. UPDATE ALL REFERENCED CODE
 SECTIONS TO THE CURRENT CODE.
  
 2) SHOW COMPLIANCE WITH FBCR - E4204.3 FOR BONDING OF
 THE POOL WATER.
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2015-09-01 Cont ID  
Sent By tklarge Date 2015-08-27 Time 15:20 Rev Time 0.00
Received By tklarge Date 2015-08-27 Time 15:18 Sent To  
Notes
2015-09-01 15:22:04GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECTS THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE FBC,
 FUEL GAS, SEC.301.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-29 Cont ID  
Sent By spalmer Date 2015-09-29 Time 13:24 Rev Time 0.00
Received By spalmer Date 2015-09-24 Time 10:04 Sent To  
Notes
2015-09-24 10:04:28RESUB ROUTED TO SGRAHAM

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-09-29 Cont ID  
Sent By tklarge Date 2015-09-29 Time 05:47 Rev Time 0.00
Received By tklarge Date 2015-09-29 Time 05:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-08-27 Cont ID  
Sent By tklarge Date 2015-08-27 Time 08:22 Rev Time 0.00
Received By tklarge Date 2015-08-27 Time 05:37 Sent To  
Notes
2015-08-27 07:11:531) THE PLANS REFER TO THE 2010 FBC. THE CODE IN EFFECT
 FOR THIS PERMIT IS THE 2014 FBC-RESIDENTIAL. REVISE THE
 PLANS TO REFLECT COMPLIANCE WITH THE 2014 CODE. NOTE -
 THE CHAPTER NUMBER HAS CHANGED IN THE CODE . PLEASE
 REFERENCE THE CORRECT CHAPTER AND CODE SECTION ON THE
 PLANS.
 2) SUBMIT A PUMP CURVE FOR THE PENTAIR PUMP TO VERIFY
 COMPLIANCE WITH ANSI/APSP-7 AND 2014 FBC SEC.R4501.6.3.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL
 MAIN DRAIN AND OUTLET COVER. MAIN DRAIN SUCTION OUTLET
 AND COVER/GRATE SHALL BE TESTED AND LISTED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY AND COMPLY
 WITH ASME/ANSI A112.19.8.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL
 HEATER.2014 FBC-ENERGY - SEC. R403.9.1.1 - ALL GAS AND
 SPA HEATERS SHALL HAVE A MINIMUM THERMAL EFFICIENCY OF
 82 % FOR HEATERS MANUFACTURED ON OR AFTER APRIL 16,
 2013 WHEN TESTED IN ACCORDANCE WITH ANSI Z 21.56. POOL
 HEATERS FIRED BY NATURAL OR LP GAS SHALL NOT HAVE
 CONTINUOUSLY BURNING PILOT LIGHTS.
 5) 2014 FBC- ENERGY- SEC. R 403.9.3. - HEATED SWIMMING
 POOLS AND IN GROUND PERMANENTLY INSTALLED SPAS SHALL BE
 EQUIPPED WITH A VAPOR-RETARDANT COVER ON OR AT THE
 WATER SURFACE OR A LIQUID COVER OR OTHER MEANS PROVEN
 TO REDUCE HEAT LOSS.
 6) SHT. 2 - THE PIPING SCHEMATIC AND THE PLAN VIEW SHOW
 A 2 1/2" RETURN LINE BUT ON THE "ASSUMPTIONS" REFERENCE
 IS MADE TO A 2" RETURN LINE. CLARIFY.
 SHT. 2 - SIZE THE RETURN LINE IN ITS ENTIRETY ON THE
 PLAN VIEW.WPB AMEND. TO FBC SEC. 107.2.1.
 7) SUBMIT A PIPING SCHEMATIC FOR THE BADU-JET
 SYSTEM..WPB AMEND. TO FBC SEC. 107.2.1.
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE BADU -
 JET MAIN DRAIN & PUMP & SUBMIT PUMP CURVE.
 9) THE PIPING SCHEMATIC ON SHT. 2 SHOWS 2 SUCTION
 OUTLETS YET THIS IS OMITTED ON THE MAIN DRAIN DETAIL.
 CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status N Date 2015-09-29 Cont ID  
Sent By tklarge Date 2015-09-25 Time   Rev Time 0.00
Received By tklarge Date 2015-09-25 Time   Sent To  
Notes
2015-09-28 07:50:41PASSED BY S. GRAHAM

Review Stop Z ZONING
Rev No 1 Status P Date 2015-08-21 Cont ID  
Sent By sgraham Date 2015-08-21 Time 14:43 Rev Time 0.00
Received By sgraham Date 2015-08-21 Time 14:42 Sent To B
Notes
***NONE***