Plan Review Details - Permit 15080178
| Plan Review Stops For Permit 15080178 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2016-05-18 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2016-05-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-05-18 |
Time |
07:00 |
Sent To |
|
|
| Notes |
| 2016-05-18 08:08:59 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT:15080178 / NEW 7/11 BUILDING | | | ADD: 2100 45TH ST. | | | CONT: CREIGHTON CONSTRUCTION & MANAGEMENT LLC | | | TEL: (239)210-0455 | | | E-MAIL: ???????????????? | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION, | | | | | | 5TH REVIEW | | | DATE: WED.MAY 18/ 2016 | | | ACTION: BUILDING PROVISO | | | | | | 1) PROVISO: PLEASE CALL THE CITY OF WEST PALM BEACHS | | | AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700) | | | FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE | | | INSPECTIONS. | | | | | | 2) PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. FOR THE | | | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE | | | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT | | | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE | | | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A | | | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL | | | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE | | | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE | | | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION | | | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE | | | BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE | | | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND | | | FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF THE | | | BUILDING. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE | | | INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN APPROVED BY THE BUILDING OFFICIAL. | | | | | | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING.FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | | WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS. | | | (B) WINDOWS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | | (E) SHUTTERS | | | (F) SKYLIGHTS | | | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C | | | STANDS | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2015-12-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-12-29 |
Time |
07:00 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-12-28 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2015-12-29 07:00:45 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT:15080178 / NEW 7/11 BUILDING | | | ADD: 2100 45TH ST. | | | CONT: TBD/ TO BE DETERMINED | | | TEL: (479)372-7837 | | | E-MAIL: ???????????????? | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION, | | | | | | 4TH REVIEW | | | DATE: TUES. DEC. 29/ 2015 | | | ACTION: DENIED | | | | | | ) NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA | | | STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A | | | FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE | | | REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO | | | CORRECT A CODE VIOLATION. | | | | | | 1) COMPLIED. (3) SOILS REPORTS. | | | | | | 2) 4TH REQUEST. RESIDENT INSPECTOR PROGRAM. SHEET S0.0 | | | ALSO INDICATES REQUIRED SPECIAL INSPECTIONS. PLEASE | | | NOTE A RESIDENT INSPECTOR SHALL BE REQUIRED FOR THIS | | | JOB. 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER | | | INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, | | | OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED | | | BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS | | | OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER | | | INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR | | | QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED | | | FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT | | | BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING | | | AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. | | | THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY | | | AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: | | | | | | FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR | | | METHODS OF CONSTRUCTION | | | STRUCTURAL MASONRY | | | STRUCTURAL CONCRETE | | | FIELD WELDING | | | STRUCTURAL STEEL/ BOLTED CONNECTIONS | | | | | | 2A) 4TH REQUEST. RESPONSE INDICATES FORMS HAVE BEEN | | | RECEIVED. WE NEED A E-MAIL ADDRESS TO BE ABLE TO SEND | | | THE RESIDENT INSPECTOR FORMS TO BE FILED OUT. RESIDENT | | | INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES NOTARIZED | | | AND RETURNED TO THE BUILDING DEPARTMENT. | | | RESIDENT INSPECTOR FORMS E-MAILED TO: | | | [email protected] 10/16/2015 09:59 AM | | | | | | 2B) 4TH REQUEST. FOR THE RESIDENT INSPECTOR PLEASE | | | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS | | | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL | | | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL | | | OR HIS DESIGNEE WILL REVIEW THE RESUME'. | | | | | | 2C)4TH REQUEST. THE CONTRACTOR WILL PRODUCE A JOB | | | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. | | | | | | 2D) COMPLIED. NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS | | | ARE REQUIRED. | | | 2E) PROVISO: PLEASE CALL THE CITY OF WEST PALM BEACH?S | | | AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700) | | | FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE | | | INSPECTIONS. | | | | | | 3) 3RD REQUEST. SHEET S0.0 THE PRESSURES FOR ZONES 1-5 | | | ARE INDICATED IN VASD, ALLOWABLE DESIGN PRESSURES. THE | | | ROOF PRESSURES ARE RIGHT ON, THE WALL PRESSURES SHOWN | | | ARE A LITTLE LOW FOR THE TRIBUTARY AREAS SHOWN. | | | 1609.4.4.1. COMPONENTS & CLADDING. | | | | | | 4) SHEET S4.0 THE WALL PRESSURES FOR ZONES 4 AND 5 | | | APPEAR TO BE LOW FOR A MEAN ROOF HEIGHT OF 15 FT, | | | EXPOSURE C FOR WALL ZONES 4 & 5. NEGATIVE PRESSURES ARE | | | TAKEN AT THE ROOF HEIGHT OF 15 FT. | | | 2014 FBC-B TABLE 1609.6.2 | | | 2014 FBC-B TABLE 1609.7.2 | | | | | | 5) COMPLIED. UNDER SEPARATE PERMIT AND REVIEW. SHEET | | | S4.0 ALSO INDICATES THE USE OF A HORIZONTAL AWNING | | | CANOPY, THERE IS NO DESIGN CRITERIA FOR THE CANOPY. | | | 2014 FBC-B 3105.5 RIGID AWNINGS AND CANOPY SHUTTERS. | | | | | | 6) COMPLIED. UNDER A SEPARATE PERMIT AND REVIEW. SHEET | | | S5.1 THE MONUMENT SIGN DETAILS. NOTE SIGNS REQUIRE A | | | SEPARATE PERMIT AND WILL BE REVIEWED UNDER THE SIGN | | | PERMIT. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 7-8) PROVISO: DEFERRED SUBMITTALS. | | | | | | 9) COMPLIED. | | | | | | 10) COMPLIED. ROOFS OR ELEVATED STRUCTURES. SHEET A4.1 | | | INDICATES THE USE OF ROOF TOP LADDERS, PLEASE PROVIDE | | | COMPLIANCE WITH SECTION 1509.6.4 2014 FBC-B | | | | | | 11) IMPACT FEES BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | PLEASE NOTE THAT A BUILDING WILL BE DEMOLISHED AT THIS | | | SITE, PLEASE MAKE SURE THEY GIVE YOU THE SQUARE FOOT | | | CREDIT. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2015-11-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-11-10 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-11-10 |
Time |
08:35 |
Sent To |
|
|
| Notes |
| 2015-11-10 15:05:18 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT:15080178 / NEW 7/11 BUILDING | | | ADD: 2100 45TH ST. | | | CONT: TBD/ TO BE DETERMINED | | | TEL: (???)???-???? | | | E-MAIL:???????????????? | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION, | | | | | | 3RD REVIEW | | | DATE: FRI. OCT. 16/ 2015 | | | ACTION: DENIED | | | | | | ) NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA | | | STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A | | | FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE | | | REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO | | | CORRECT A CODE VIOLATION. | | | | | | 1) COMPLIED. (3) SOILS REPORTS. | | | | | | 2) 3RD REQUEST. RESIDENT INSPECTOR PROGRAM. SHEET S0.0 | | | ALSO INDICATES REQUIRED SPECIAL INSPECTIONS. PLEASE | | | NOTE A RESIDENT INSPECTOR SHALL BE REQUIRED FOR THIS | | | JOB. 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER | | | INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, | | | OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED | | | BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS | | | OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER | | | INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR | | | QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED | | | FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT | | | BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING | | | AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. | | | THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY | | | AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: | | | | | | FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR | | | METHODS OF CONSTRUCTION | | | STRUCTURAL MASONRY | | | STRUCTURAL CONCRETE | | | FIELD WELDING | | | STRUCTURAL STEEL/ BOLTED CONNECTIONS | | | | | | 2A) 3RD REQUEST. RESPONSE INDICATES FORMS HAVE BEEN | | | RECEIVED. WE NEED A E-MAIL ADDRESS TO BE ABLE TO SEND | | | THE RESIDENT INSPECTOR FORMS TO BE FILED OUT. RESIDENT | | | INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES NOTARIZED | | | AND RETURNED TO THE BUILDING DEPARTMENT. | | | RESIDENT INSPECTOR FORMS E-MAILED TO: | | | [email protected] 10/16/2015 09:59 AM | | | | | | 2B) 3RD REQUEST. FOR THE RESIDENT INSPECTOR PLEASE | | | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS | | | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL | | | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL | | | OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE | | | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. | | | UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED | | | FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. | | | CONTACT: KEN CONRAD | | | TEL: 561-805-6666 | | | E-MAIL: [email protected] | | | | | | 2C) 3RD REQUEST. THE CONTRACTOR WILL PRODUCE A JOB | | | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS | | | MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: | | | [email protected] | | | | | | 2D) 3RD REQUEST. NOTE FOR PAPER PLANS 3 SETS OF | | | DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT | | | ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE | | | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR | | | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN | | | COLOR, (1) FOR THE RESIDENT INSPECTOR, THE OTHER FOR | | | THE MEP INSPECTORS. | | | | | | 2E) 3RD REQUEST. NOTICE ONLY! PLEASE CALL THE CITY OF | | | WEST PALM BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE | | | (561) 805-6700) FOR IN-PROGRESS INSPECTIONS FOR | | | AUDITING OF JOBSITE INSPECTIONS. | | | | | | 3) 3RD REQUEST. SHEET S0.0 THE PRESSURES FOR ZONES 1-5 | | | ARE INDICATED IN VASD, ALLOWABLE DESIGN PRESSURES. THE | | | ROOF PRESSURES ARE RIGHT ON, THE WALL PRESSURES SHOWN | | | ARE A LITTLE LOW FOR THE TRIBUTARY AREAS SHOWN. | | | 1609.4.4.1. COMPONENTS & CLADDING. | | | | | | 4) SHEET S4.0 THE WALL PRESSURES FOR ZONES 4 AND 5 | | | APPEAR TO BE LOW FOR A MEAN ROOF HEIGHT OF 15 FT, | | | EXPOSURE C FOR WALL ZONES 4 & 5. NEGATIVE PRESSURES ARE | | | TAKEN AT THE ROOF HEIGHT OF 15 FT. | | | 2014 FBC-B TABLE 1609.6.2 | | | 2014 FBC-B TABLE 1609.7.2 | | | | | | 5) COMPLIED. UNDER SEPARATE PERMIT AND REVIEW. SHEET | | | S4.0 ALSO INDICATES THE USE OF A HORIZONTAL AWNING | | | CANOPY, THERE IS NO DESIGN CRITERIA FOR THE CANOPY. | | | 2014 FBC-B 3105.5 RIGID AWNINGS AND CANOPY SHUTTERS. | | | | | | 6) COMPLIED. UNDER A SEPARATE PERMIT AND REVIEW. SHEET | | | S5.1 THE MONUMENT SIGN DETAILS. NOTE SIGNS REQUIRE A | | | SEPARATE PERMIT AND WILL BE REVIEWED UNDER THE SIGN | | | PERMIT. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 7) 3RD REQUEST. PLEASE NOTE THE PRODUCT APPROVALS HAVE | | | NOT BEEN REVIEWED BY THE DESIGNER OF RECORD, NO SHOP | | | DRAWING STAMP OF APPROVAL HAS BEEN AFFIXED. THE PERMIT | | | EXPEDITER HAS JUST LIMPED THESE APPROVALS TOGETHER, | | | THEY ARE NOT STAPLED, THEY ARE NOT MARKED WHICH ARE OLD | | | AND WHICH ARE NEW. | | | THERE WILL BE ISSUES WITH THE APPROVALS THAT WILL TAKE | | | TO LONG OF A TIME PERIOD TRYING TO GUESS WHAT IS | | | WHAT!!!!! | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS | | | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. | | | | | | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | | WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS. | | | (B) WINDOWS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS | | | E) STORM SHUTTERS | | | (F) SKYLIGHTS | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | | | | 3RD REVIEW PRODUCTS NOT REVIEWED NOT STAPLED, COLLATED: | | | EXTERIOR DOORS, THERE WERE 2 REPORTS SUBMITTED NOA | | | 14-0602 ALUMINUM STOREFRONT DOOR LARGE MISSILE IMPACT | | | AND NOA 14-0811.22 | | | NON-IMPACT OS DOOR AND STORE FRONT PLEASE SHOW WHERE | | | THE LARGE MISSILE IMPACT DOOR WILL BE INSTALLED. STORM | | | SHUTTERS WILL BE REQUIRED FOR THE NON-IMPACT GLAZING IN | | | THE STOREFRONT WALL AND DOOR SYSTEM!!!!! | | | | | | A PRODUCT APPROVAL FOR STORM SHUTTERS WILL ALSO BE | | | REQUIRED. PROVIDE STORM PANEL INFORMATION WITH | | | INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC | | | ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT | | | GLAZING. FBC 1609.1.2. | | | | | | FL BLD CODE 2010 SECTION 107.2.5., 1609.1.2, 1715.8 A | | | COMPLETE INSTALLATION SCHEDULE SUMMARIZING & | | | IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK | | | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR REINFORCING | | | REQUIREMENTS, WALL PRESSURE ZONES, SLAT TYPES, ETC., | | | SHALL BE SUBMITTED AT TIME OF PERMIT APPLICATION TO | | | FACILITATE PLAN REVIEW AND PERMIT ISSUANCE. | | | | | | FOR ALL GLAZING UNITS IDENTIFY THE TYPE OF GLAZING, | | | MULLION TYPES, WIDTH, HEIGHT OF UNITS TYPES OF | | | FASTENERS, PRESSURES FOR UNITS. | | | | | | ROOFING PRODUCT APPROVAL SUBMITTED NOA 13-0419.05 PAGE | | | 08 MAXIMUM DESIGN PRESSURE OF -45 AND LIMITATION NUMBER | | | 9 NO ENHANCED FASTENING IS ALLOWED!!!!!!! | | | | | | SKYLIGHT REPORT PTC IS A OLD 2007 REPORT UNDER RULE 9B. | | | PLEASE NOTE RULE 9B ENDED OCT 31/ 2010. RULE 9N-3 | | | REPLACED THIS RULE NOV.01/2010. THERE HAS BEEN 2 CODE | | | CYCLES THE 2010 AND 2014 FBC, PLEASE UPDATE EVALUATION | | | REPORT. NOTE THE NOA 08-0305.02 POLYCARBONATE IS A | | | EXPIRED REPORT ALSO. | | | | | | NOTICE!!!!!. CARRIER ROOF TOP CURBS NOA 15-0218.11 | | | PLEASE BE AWARE THERE IS A ISSUE WITH THE RESTRAINT | | | BRACKET SHOWN ON SHEET 2 OF 5, ALSO SEE DETAIL OF | | | RESTRAINT BRACKET ON SHEET 5 OF 5. SHEET 2 OF 5 | | | INDICATES (7) # 10 TEK SCREWS THAT ARE TO HOLD THE | | | RESTRAINT BRACKET TO THE ROOF CURB. PAGE 5 SHOWS THE | | | BRACKET DOES NOT TURN DOWN THE INTERIOR OF THE CURB. | | | HOW WILL THE RESTRAINT BRACKET BE HELD TO THE CURB. | | | NOA 14-0513.10 IS FOR THE ROOFTOP FANS, NO PRODUCT | | | APPROVALS WAS SUBMITTED FOR THE CURB. HIGHLIGHT CIRCLE | | | TYPE OF UNIT AND PRESSURES. 107.2.1.3 ADDITIONAL | | | INFORMATION IS REQUIRED. | | | | | | THE CITY HAS RECEIVED THE LETTER FROM THYBAR ABOUT THE | | | CHANGE IN CONFIGURATION THE BRACKET FROM THE CURB TO | | | THE RTU ROOF TOP UNIT. CONTACTING MIAMI-DADE?S OFFICE | | | THEY INDICATED ON SHEET 5 OF 5 NOTE: RESTRAINT BRACKET | | | IS TO BE DETERMINED BY PROJECT SPECIFIC CALCULATIONS BY | | | A FLORIDA LICENSED PE OF FLORIDA REGISTERED ARCHITECT. | | | | | | 8) 3RD REVIEW. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. | | | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE | | | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE | | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. | | | | | | 9) COMPLIED. SHEETS A4.0 & A4.1 BOTH SHOW THE USE OF | | | VENEER STONE (V1) ON THE EXTERIOR OF THE BUILDING. | | | SHEET A6.0 DETAIL # 3 SHOWS HOW THE PLACEMENT OF VENEER | | | STONE, MONOLITHIC FOUNDATION SLAB AND THE CONCRETE | | | SIDEWALK AND THE EXPANSION JOINT HIDDEN BENEATH THE | | | BUILT OUT WALL WHERE THE VENEER STONE IS INSTALLED. | | | 2014 FBC-B 1403.8 & 2114.2. | | | | | | 10) COMPLIED. SHEET A4.1 INDICATES THE USE OF ROOF TOP | | | LADDERS, PLEASE PROVIDE COMPLIANCE WITH SECTION | | | 1509.6.4 2014 FBC-B | | | | | | ROOFS OR ELEVATED STRUCTURES. WHERE EQUIPMENT AND | | | APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR | | | ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET (4877 | | | MM), SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT | | | APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE | | | FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND | | | APPLIANCES? LEVEL SERVICE SPACE. | | | | | | 11) IMPACT FEES BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | PLEASE NOTE THAT A BUILDING WILL BE DEMOLISHED AT THIS | | | SITE, PLEASE MAKE SURE THEY GIVE YOU THE SQUARE FOOT | | | CREDIT. | | | | | | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-10-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-10-16 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-10-15 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2015-10-16 11:43:57 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT:15080178 / NEW 7/11 BUILDING | | | ADD: 2100 45TH ST. | | | CONT: TBD/ TO BE DETERMINED | | | TEL: (???)???-???? | | | E-MAIL:???????????????? | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION, | | | | | | 2ND REVIEW | | | DATE: FRI. OCT. 16/ 2015 | | | ACTION: DENIED | | | | | | ) NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA | | | STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A | | | FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE | | | REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO | | | CORRECT A CODE VIOLATION. | | | | | | 1) SHEET S0.0: | | | | | | 1) SEMI-COMPLIED ONLY 2 REPORTS WERE SUBMITTED, | | | REQUIRES A RESIDENT INSPECTOR REQUIRES (3) OF ALL | | | ARCHITECTURAL & STRUCTURAL PLANS AND DOCUMENTS. | | | | | | ONLY (1) SOILS REPORT SUBMITED, (2 ) WILL BE REQUIRED | | | FOR THE UNDERGROUND TANKS AND (2) FOR THE CANOPY. THE | | | SOILS REPORT INDICATES THERE TO BE UNDER LAYING ORGANIC | | | SOILS. THE SOILS REPORT IS SUGESTIONSAND ALTERNATIVES | | | IN DEALING WITH THIS MATTER. THE DESIGNER OF RECORD HAS | | | NOT RESPONDED AS TO HOW THE ORGANIC SOILS ARE TO BE | | | DELT WITH. | | | | | | THE (2) ISSUE IS THAT GROUND WATER WILL BE PRESENT | | | AROUND 7 FEET BELOW GRADE, PLEASE PROVIDE HOW THE | | | GROUND WATER WILL BE LOWERED TO BE ABLE TO WORK AT THE | | | REQUIRED DEEPER ELEVATION FROM GRADE. | | | | | | SHEET S0.0 UNDER THE HEADING OF FOUNDATION INDICATES A | | | GEOTECHNICAL SOILS REPORT COMPLETED BY ARDAMAN & | | | ASSOCIATES, DATED MARCH 09/ 2015, REPORT NUMBER | | | 15-1628. PLEASE PROVIDE (2) SIGNED AND SEALED ORIGINALS | | | OF REPORT. 2014 FBC-B 1803.2. SOILS INVESTIGATION | | | REQUIRED. | | | | | | 2) RESIDENT INSPECTOR PROGRAM. SHEET S0.0 ALSO | | | INDICATES REQUIRED SPECIAL INSPECTIONS. PLEASE NOTE A | | | RESIDENT INSPECTOR SHALL BE REQUIRED FOR THIS JOB. | | | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER | | | INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, | | | OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED | | | BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS | | | OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER | | | INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR | | | QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED | | | FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT | | | BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING | | | AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. | | | THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY | | | AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: | | | | | | FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR | | | METHODS OF CONSTRUCTION | | | STRUCTURAL MASONRY | | | STRUCTURAL CONCRETE | | | FIELD WELDING | | | STRUCTURAL STEEL/ BOLTED CONNECTIONS | | | | | | 2)A) WE NEED A E-MAIL ADDRESS TO BE ABLE TO SEND THE | | | RESIDENT INSPECTOR FORMS TO BE FILED OUT. RESIDENT | | | INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES NOTARIZED | | | AND RETURNED TO THE BUILDING DEPARTMENT. | | | RESIDENT INSPECTOR FORMS E-MAILED TO: | | | [email protected] 10/16/2015 09:59 AM | | | | | | 1B)B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A | | | RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. | | | THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS | | | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE | | | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, | | | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES | | | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST | | | MEETING THE ABOVE CRITERIA. | | | CONTACT: KEN CONRAD | | | TEL: 561-805-6666 | | | E-MAIL: [email protected] | | | | | | 2()C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR | | | HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE | | | SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: | | | [email protected] | | | | | | 2(D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE | | | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE | | | PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND | | | BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO | | | SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR | | | THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP | | | INSPECTORS. | | | | | | 2(E) NOTICE ONLY! PLEASE CALL THE CITY OF WEST PALM | | | BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561) | | | 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF | | | JOBSITE INSPECTIONS. | | | | | | 3) SHEET S0.0 THE PRESSURES FOR ZONES 1-5 ARE INDICATED | | | IN VASD, ALLOWABLE DESIGN PRESSURES. THE ROOF PRESSURES | | | ARE RIGHT ON, THE WALL PRESSURES SHOWN ARE A LITTLE LOW | | | FOR THE TRIBUTARY AREAS SHOWN. 1609.4.4.1. COMPONENTS & | | | CLADDING. | | | | | | 4) SHEET S4.0 THE WALL PRESSUES FOR ZONES 4 AND 5 | | | APPEAR TO BE LOWFOR A MEAN ROOF HEIGHT OF 15 FT, | | | EXPOSUE C. | | | | | | 5) COMPLIED. SHEET S4.0 ALSO INDICATES THE USE OF A | | | HORIZONTAL AWNING CANOPY, THERE IS NO DESIGN CRITERIA | | | FOR THE CANOPY. 2014 FBC-B 3105.5 RIGID AWNINGS AND | | | CANOPY SHUTTERS. | | | | | | 6) COMPLIED. SHEET S5.1 THE MONUMENT SIGN DETAILS. NOTE | | | SIGNS REQUIRE A SEPARATE PERMIT AND WILL BE REVIEWED | | | UNDER THE SIGN PERMIT. 107.2.1.3 ADDITIONAL INFORMATION | | | IS REQUIRED. | | | | | | 7) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | | WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS. | | | (B) WINDOWS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS | | | E) STORM SHUTTERS | | | (F) SKYLIGHTS | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | | | | 2ND REVIEW: | | | EXTERIOR DOORS, THERE WERE 2 REPORTS SUBMITTED NOA | | | 14-0602 ALUMINUM STOREFRONT DOOR LARGE MISSILE IMPACT | | | AND NOA 14-0811.22 | | | NON-IMPACT OS DOOR AND STORE FRONT PLEASE SHOW WHERE | | | THE LARGE MISSLE IMPACT DOOR WILL BE INSTALLED. STORM | | | SHUTTERS WILL BE REQUIRED FOR THE NON-IMPACT GLAZING IN | | | THE STOREFRONT WALL AND DOOR SYSTEM!!!!! | | | | | | A PRODUCT AAPPROVAL FOR STORM SHUTTERS WILL ALSO BE | | | REQUIRED. PROVIDE STORM PANEL INFORMATION WITH | | | INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC | | | ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT | | | GLAZING. FBC 1609.1.2. | | | | | | FL BLD CODE 2010 SECTION 107.2.5., 1609.1.2, 1715.8 A | | | COMPLETE INSTALLATION SCHEDULE SUMMARIZING & | | | IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK | | | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR REINFORCING | | | REQUIREMENTS, WALL PRESSURE ZONES, SLAT TYPES, ETC., | | | SHALL BE SUBMITTED AT TIME OF PERMIT APPLICATION TO | | | FACILITATE PLAN REVIEW AND PERMIT ISSUANCE. | | | | | | FOR ALL GLAZING UNITS IDENTIFY THE TYPE OF GLAZING, | | | MULLION TYPES, WIDTH, HEIGHT OF UNITS TYPES OF | | | FASTENERS, PRESSURES FOR UNITS. | | | | | | ROOFING PRODUCT APPROVAL SUBMITTED NOA 13-0419.05 PAGE | | | 08 MAXIMUM DESIGN PRESSURE OF -45 AND LIMITATION NUMBER | | | 9 NO ENHANCED FASTENING IS ALLOWED!!!!!!! | | | | | | SKYLIGHT REPORT PTC IS A OLD 2007 REPORT UNDER RULE 9B. | | | PLEASE NOTE RULE 9B ENDED OCT 31/ 2010. RULE 9N-3 | | | REPLACED THIS RULE NOV.01/2010. THERE HAS BEEN 2 CODE | | | CYCLES THE 2010 AND 2014 FBC, PLEASE UPDATE EVALUATION | | | REPORT. NOTE THE NOA 08-0305.02 POLYCARBONATE IS A | | | EXPIRED REPORT ALSO. | | | | | | CARRIER ROOF TOP CURBS NOA 15-0218.11 PLEASE BE AWARE | | | THERE IS A ISSUE WITH THE RESTRAINT BRACKET SHOWN ON | | | SHEET 2 OF 5, ALSO SEE DETAIL OF RESTRAINT BRACKET ON | | | SHEET 5 OF 5. SHEET 2 OF 5 INDICATES (7) # 10 TEK | | | SCREWS THAT ARE TO HOLD THE RESTRAINT BRACKET TO THE | | | ROOF CURB. PAGE 5 SHOWS THE BRACKET DOES NOT TURN DOWN | | | THE INTERIOR OF THE CURB. HOW WILL THE RESTRAINT | | | BRACKET BE HELD TO THE CURB. | | | DISCREPANCY IN PLANS. 107.2.1.3. ADDITIONAL INFORMATION | | | IS REQUIRED. | | | | | | NOA 14-0513.10 IS FOR THE ROOFTOP FANS, NO PRODUCT | | | APPROVALS WAS SUBMITTED FOR THE CURB. HIGHLIGHT CIRCLE | | | TYPE OF UNIT AND PRESSURES. 107.2.1.3 ADDITIONAL | | | INFORMATION IS REQUIRED. | | | | | | 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 9) COMPLIED. SHEETS A4.0 & A4.1 BOTH SHOW THE USE OF | | | VENEER STONE (V1) ON THE EXTERIOR OF THE BUILDING. | | | SHEET A6.0 DETAIL # 3 SHOWS HOW THE PLACEMENT OF VENEER | | | STONE, MONOLITHIC FOUNDATION SLAB AND THE CONCRETE | | | SIDEWALK AND THE EXSPANSION JOINT HIDDEN BENEATH THE | | | BUILT OUT WALL WHERE THE VENEER STONE IS INSTALLED. | | | 2014 FBC-B 1403.8 & 2114.2. | | | | | | 10) COMPLIED. SHEET A4.1 INDICATES THE USE OF ROOF TOP | | | LADDERS, PLEASE PROVIDE COMPLIANCE WITH SECTION | | | 1509.6.4 2014 FBC-B | | | ROOFS OR ELEVATED STRUCTURES. WHERE EQUIPMENT AND | | | APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR | | | ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET (4877 | | | MM), SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT | | | APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE | | | FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND | | | APPLIANCES? LEVEL SERVICE SPACE. | | | | | | 11) IMPACT FEES BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | PLEASE NOTE THAT A BUILDING WILL BE DEMOLISHED AT THIS | | | SITE, PLEASE MAKE SURE THEY GIVE YOU THE SQUARE FOOT | | | CREDIT. | | | | | | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-08-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-08-24 |
Time |
14:56 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2015-08-24 |
Time |
10:00 |
Sent To |
|
|
| Notes |
| 2015-08-24 14:56:12 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT:15080178 / NEW 7/11 BUILDING | | | ADD: 2100 45TH ST. | | | CONT: TBD/ TO BE DETERMINED | | | TEL: (???)???-???? | | | E-MAIL:???????????????? | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION, | | | | | | 1ST REVIEW | | | DATE: MON. AUGUST 24/ 2015 | | | ACTION: DENIED | | | | | | 1) SHEET S0.0: | | | | | | 1A) SHEET S0.0 UNDER THE HEADING OF FOUNDATION | | | INDICATES A GEOTECHNICAL SOILS REPORT COMPLETED BY | | | ARDAMAN & ASSOCIATES, DATED MARCH 09/ 2015, REPORT | | | NUMBER 15-1628. PLEASE PROVIDE (2) SIGNED AND SEALED | | | ORIGINALS OF REPORT. 2014 FBC-B 1803.2. SOILS | | | INVESTIGATION REQUIRED. | | | | | | 1B) SHEET S0.0 ALSO INDICATES REQUIRED SPECIAL | | | INSPECTIONS. PLEASE NOTE A RESIDENT INSPECTOR SHALL BE | | | REQUIREDFOR THIS JOB. | | | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER | | | INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, | | | OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED | | | BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS | | | OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER | | | INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR | | | QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED | | | FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT | | | BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING | | | AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. | | | THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY | | | AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: | | | | | | 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR | | | METHODS OF CONSTRUCTION | | | STRUCTURAL MASONRY | | | STRUCTURAL CONCRETE | | | FIELD WELDING | | | STRUCTURAL STEEL/ BOLTED CONNECTIONS | | | | | | 7A) WE NEED A E-MAIL ADDRESS TO BE ABLE TO SEND THE | | | RESIDENT INSPECTOR FORMS TO BE FILED OUT. RESIDENT | | | INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES NOTARIZED | | | AND RETURNED TO THE BUILDING DEPARTMENT. | | | | | | 7B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' | | | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE | | | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS | | | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE | | | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, | | | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES | | | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST | | | MEETING THE ABOVE CRITERIA. | | | CONTACT: KEN CONRAD | | | TEL: 561-805-6666 | | | E-MAIL: [email protected] | | | | | | 7C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR | | | HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE | | | SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: | | | [email protected] | | | | | | 7D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE | | | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE | | | PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND | | | BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO | | | SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR | | | THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP | | | INSPECTORS. | | | | | | 7E) NOTICE ONLY! PLEASE CALL THE CITY OF WEST PALM | | | BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561) | | | 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF | | | JOBSITE INSPECTIONS. | | | | | | 8) SHEET S4.0 THE PRESSURES FOR ZONES 1-5 DO NOT | | | INDICATE IF THEY ARE IN VULT OR VASD. PLEASE PROVIDE | | | PRESSURES IN VASD TO COINCIDE WITH THE PRESSURES FOUND | | | IN THE PRODUCT APPROVALS. 1609.4.4.1. COMPONENTS & | | | CLADDING. | | | | | | 9) SHEET S4.0 THE WALL PRESSUES FOR ZONES 4 AND 5 | | | APPEAR TO BE LOWFOR A MEAN ROOF HEIGHT OF 15 FT, | | | EXPOSUE C. | | | | | | 10) SHEET S4.0 ALSO INDICATES THE USE OF A HORIZONTAL | | | AWNING CANOPY, THERE IS NO DESIGN CRITERIA FOR THE | | | CANOPY. 2014 FBC-B 3105.5 RIGID AWNINGS AND CANOPY | | | SHUTTERS. | | | | | | 11) SHEET S5.1 THE MONUMENT SIGN DETAILS. NOTE SIGNS | | | REQUIRE A SEPARATE PERMIT AND WILL BE REVIEWED UNDER | | | THE SIGN PERMIT. 107.2.1.3 ADDITIONAL INFORMATION IS | | | REQUIRED. | | | | | | 12) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | | WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS. | | | (B) WINDOWS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS | | | (F) SKYLIGHTS | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | NOTE ROOFING ASSEMBLY MUST MEET THE ENERGY REQUIREMENTS | | | FOR INSULATION, PROVIDE ANCHORING OF ROOF TOP | | | INSULATION AND 1/2 INCH RECOVERY BOARD. | | | | | | 13) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE | | | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 | | | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE | | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. | | | | | | 14) SHEETS A4.0 & A4.1 BOTH SHOW THE USE OF VENEER | | | STONE (V1) ON THE EXTERIOR OF THE BUILDING. SHEET A6.0 | | | DETAIL # 3 SHOWS HOW THE PLACEMENT OF VENEER STONE, | | | MONOLITHIC FOUNDATION SLAB AND THE CONCRETE SIDEWALK | | | AND THE EXSPANSION JOINT HIDDEN BENEATH THE BUILT OUT | | | WALL WHERE THE VENEER STONE IS INSTALLED. 2014 FBC-B | | | 1403.8 & 2114.2. | | | | | | 15) SHEET A4.1 INDICATES THE USE OF ROOF TOP LADDERS, | | | PLEASE PROVIDE COMPLIANCE WITH SECTION 1509.6.4 2014 | | | FBC-B | | | ROOFS OR ELEVATED STRUCTURES. WHERE EQUIPMENT AND | | | APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR | | | ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET (4877 | | | MM), SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT | | | APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE | | | FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND | | | APPLIANCES? LEVEL SERVICE SPACE. | | | | | | 16) IMPACT FEES BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | PLEASE NOTE THAT A BUILDING WILL BE DEMOLISHED AT THIS | | | SITE, PLEASE MAKE SURE THEY GIVE YOU THE SQUARE FOOT | | | CREDIT. | | | | | | 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2015-10-20 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-10-20 |
Time |
17:33 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-10-19 |
Time |
13:17 |
Sent To |
|
|
| Notes |
| 2015-10-20 17:33:56 | THE PLANS ARE STAMPED BACK ON 9/23/15 AS | | | PASSED.RETUERNWD TO C28 FOR ZONING REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2015-09-23 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-09-23 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-09-23 |
Time |
08:42 |
Sent To |
I |
|
| Notes |
| 2015-09-23 10:28:27 | THE ELECTRICAL SCOPE OF THIS PERMIT IS LIMITED TO THE | | | 7/11 STORE AND EXCLUDES ANY OF THE WORK FOR THE FUEL | | | DISPENSING EQUIPMENT. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2015-09-04 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
2015-09-04 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
2015-09-04 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2015-09-04 10:15:05 | AS MENTIONED DURING PPRC REVIEW, AN ENGINEERING | | | DEVELOPMENT APPROVAL IS REQUIRED. | | | | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED AT | | | HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/ | | | SUPPORTING DOCUMENTATION SHOULD INCLUDE CONSTRUCTION | | | LEVEL DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN. | | | | | | A SEPARATE BUILDING PERMIT APPLICATION SHOULD BE MADE | | | FOR THE DUMPSTER ENCLOSURE. | | | | | | KELLY CRANFORD, P.E. | | | LAND DEVELOPMENT ENGINEER | | | PUBLIC WORKS DEPARTMENT | | | CITY OF WEST PALM BEACH | | | [email protected] | | | 561-494-1098 (OFFICE) |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2015-12-16 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-12-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-12-16 |
Time |
14:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2015-10-16 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-10-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-10-06 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2015-10-07 08:35:12 | PLEASE CONSIDER AS A PROVISO: | | | ENSURE THAT FIRE HYDRANT HAS PROPER SEPARATION FROM | | | PROPOSED LIGHT POLE AND FIXTURES. GJT |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2015-08-20 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-08-20 |
Time |
17:11 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-08-19 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2015-08-19 17:23:57 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | 1) SHEET A 0.1, THERE IS NO REFERENCE TO THE FIRE CODE | | | INDICATED. | | | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING | | | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER | | | APPLICABLE CODES OR STANDARDS. | | | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 241, 2009 EDITION. | | | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 10, 2010 EDITION. | | | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. | | | | | | 2) A LIGHTWEIGHT ROOF TRUSS SIGN IS REQUIRED. | | | | | | PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR | | | STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. | | | ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT | | | RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES | | | HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE | | | CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A | | | MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND | | | 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR. | | | THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO | | | THE LEFT OF THE MAIN ENTRY DOOR. | | | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE | | | MARKED WITH THE LETTER "R". | | | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS | | | SHALL BE MARKED WITH THE LETTER "F". | | | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF | | | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". | | | | | | 3) THE HARDWARE ON THE EXIT DOORS SHALL COMPLY WITH | | | NFPA 101, CHAPTER 7. | | | | | | DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE | | | EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS, | | | IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL, | | | OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE | | | EGRESS SIDE. | | | | | | INDICATE IF THE DOORS WILL BE EQUIPPED WITH ANY | | | LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A | | | LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE | | | RELEASED FROM THE EGRESS SIDE OF THE DOOR. | | | | | | PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING | | | MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT | | | MORE THAN ONE RELEASING OPERATION. THE RELEASING | | | MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION | | | THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS. | | | THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING | | | OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT | | | GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO | | | OPERATE. | | | | | | A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY | | | DOOR(S). IN LIEU OF PANIC HARDWARE, THE MAIN ENTRY IS | | | PERMITTED TO BE EQUIPPED WITH A KEYED LOCK WITH | | | LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE | | | DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO | | | OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED. | | | | | | THUMB-TURN LOCK TO BE EQUIPPED WITH AN ?OPEN/LOCKED? | | | INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 OR SIMILAR). | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2015-12-18 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2015-12-18 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2015-12-18 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2015-12-18 13:43:55 | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | GAS PLAN REVIEW | | | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE | | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | | PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT | | | SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE | | | SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | | FBC-R, SEC. G2404.3. | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | | GAS SEC. 301.3. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2016-05-23 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-05-23 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-05-19 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2016-05-20 13:50:42 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2016-05-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-05-18 |
Time |
08:10 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-05-03 |
Time |
08:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2016-01-20 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2016-01-20 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2015-12-15 |
Time |
13:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-11-20 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2015-11-18 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2015-11-02 |
Time |
10:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-10-21 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2015-10-21 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2015-09-29 |
Time |
09:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-09-23 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-09-23 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-08-06 |
Time |
13:03 |
Sent To |
|
|
| Notes |
| 2015-09-23 10:37:04 | 9/23/15 - PASSED ELECTRICAL REVIEW BUT HAS FAILED OTHER | | | TRADES. RUNNER NOTIFIED VIA EMAIL. SENT TO LARGE DENIED | | | BIN "TBD". MA | | 2015-08-06 13:03:48 | C28 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
5 |
Status |
P |
Date |
2016-06-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-06-20 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-06-15 |
Time |
12:37 |
Sent To |
|
|
| Notes |
| 2016-06-20 07:11:45 | 6/20/2016 | | | PALM BEACH COUNTY IMPACT FEES | | | CREDITS TAKEN/ DEMOLITION | | | MU-2016-0614-145 | | | $436.55 | | 2016-06-17 12:37:15 | JWITMER'S DESK |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
4 |
Status |
F |
Date |
2016-05-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-05-18 |
Time |
08:09 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-05-18 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2016-05-18 08:10:00 | IMPACT FEES | | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
F |
Date |
2015-12-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-12-29 |
Time |
06:56 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-12-29 |
Time |
06:56 |
Sent To |
|
|
| Notes |
| 2015-12-29 06:56:22 | IMPACT FEES BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | PLEASE NOTE THAT A BUILDING WILL BE DEMOLISHED AT THIS | | | SITE, PLEASE MAKE SURE THEY GIVE YOU THE SQUARE FOOT | | | CREDIT. | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2015-10-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-10-16 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-10-16 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2015-10-16 11:47:25 | IMPACT FEES | | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2015-08-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-08-24 |
Time |
12:09 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2015-08-24 |
Time |
10:00 |
Sent To |
|
|
| Notes |
| 2015-08-24 12:10:17 | IMPACT FEES | | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2016-05-23 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-05-23 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-05-23 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2016-05-23 13:46:03 | MECHANICAL PROVISO | | | 5/23/16 | | | | | | 1) THE CONTRACTOR HAS REQUESTED THAT THE NOA'S FOR THE | | | RTU CURBS AND CU ROOF STANDS TO BE DEFERRED SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2016-05-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-05-10 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-05-10 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2016-05-10 11:28:06 | MECHANICAL PROVISOS: | | | | | | 1) THE CONTRACTOR HAS REQUESTED THAT THE NOA'S FOR THE | | | RTU CURBS AND CU ROOF STANDS TO BE DEFERRED SUBMITTALS. | | | 2) THE ENGINEER OF RECORD SHALL PROVIDE HIS/HER | | | SIGNATURE AND SEAL ON THE AC LOAD SUMMARY CALCULATIONS. | | | 3) PROVIDE A DUPLICATE SET OF ENERGY CALCULATIONS- ONLY | | | ONE SET WAS SUBMITTED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2015-12-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-12-21 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-12-21 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2015-12-21 14:51:59 | 4TH REVIEW 2014 MECHANICAL | | | PERMIT #15080178 | | | 12/21/15 | | | | | | THE PREVIOUS (3RD) REVIEW COMMENTS STILL EXIST. I HAVE | | | PRINTED THEM BELOW FOR REVIEW. | | | 1) THE RE-SUBMITTED ENERGY CALCULATION FORM 506-2014 | | | MUST BE SIGNED BY THE " BUILDING'S OWNER, THE | | | ARCHITECT, OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED | | | BY THE BUILDING'S OWNER".- SEE PAGE 3 OF THE DOCUMENT | | | AND SECTION C103.1.1.2 FBC-14 ENERGY CONSERVATION. | | | 2) FORM 506-2014: SEE PAGE 1 "CHECKLIST" ITEM #4 ON THE | | | LIST AND COMPLETE THE "MANDATORY REQUIREMENTS" | | | CHECKLIST BEGINNING ON PAGE 8. | | | 3) REFER TO 3RD REVIEW BUILDING COMMENT #7 REGARDING | | | DESIGN PROFESSIONAL APPROVAL FOR PRODUCT APPROVALS AND | | | NOA'S ( INCLUDING THE RTU CURB AND THE ROOF STAND). | | | 4) PLEASE PLACE A NOTE INDICATING ALL REFRIGERATION | | | SYSTEMS INCLUDING THE WALK IN COOLER AND FREEZER, AND | | | THE FLEX PACKWILL BE DONE UNDER SEPARATE PERMIT. PLEASE | | | CLARIFY IF THE MOUNTING DETAILS FOR THE RTU'S SHOWN ON | | | SHEET M1.1, AND THE THYBAR CURB ARE ALSO ALSO | | | APPLICABLE TO THE FLEX PACK INSTALLATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2015-11-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-11-16 |
Time |
12:48 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-11-12 |
Time |
07:21 |
Sent To |
|
|
| Notes |
| 2015-11-12 08:39:55 | 3RD REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15080178 | | | 11/12/15 | | | | | | 1) THE RE-SUBMITTED ENERGY CALCULATION FORM 506-2014 | | | MUST BE SIGNED BY THE " BUILDING'S OWNER, THE | | | ARCHITECT, OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED | | | BY THE BUILDING'S OWNER".- SEE PAGE 3 OF THE DOCUMENT | | | AND SECTION C103.1.1.2 FBC-14 ENERGY CONSERVATION. | | | 2) FORM 506-2014: SEE PAGE 1 "CHECKLIST" ITEM #4 ON THE | | | LIST AND COMPLETE THE "MANDATORY REQUIREMENTS" | | | CHECKLIST BEGINNING ON PAGE 8. | | | 3) REFER TO 3RD REVIEW BUILDING COMMENT #7 REGARDING | | | DESIGN PROFESSIONAL APPROVAL FOR PRODUCT APPROVALS AND | | | NOA'S ( INCLUDING THE RTU CURB AND THE ROOF STAND). | | | 4) PLEASE PLACE A NOTE INDICATING ALL REFRIGERATION | | | SYSTEMS INCLUDING THE WALK IN COOLER AND FREEZER, AND | | | THE FLEX PACKWILL BE DONE UNDER SEPARATE PERMIT. PLEASE | | | CLARIFY IF THE MOUNTING DETAILS FOR THE RTU'S SHOWN ON | | | SHEET M1.1, AND THE THYBAR CURB ARE ALSO ALSO | | | APPLICABLE TO THE ROOF VENTILATOR AND THE FLEX PACK | | | INSTALLATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2015-10-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-10-08 |
Time |
07:19 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-10-08 |
Time |
07:19 |
Sent To |
|
|
| Notes |
| 2015-10-08 07:35:31 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15080178 | | | 10/8/15 | | | | | | 1) THE PREVIOUSLY SUBMITTED ENERGY CALCULATIONS WERE | | | NOT RE-SUBMITTED WITH THE CORRECTED PLANS- REFER TO | | | SECTIONS C101.3 & C101.5 FBC-14 ENERGY CONSERVATION AND | | | PROVIDE THE CALCULATIONS. | | | 2) SHEET M1.1, DETAIL #5: SPECIFY THE THE TYPE, SIZE, | | | AND SPACING OF THE CURB ANCHOR BOLTS. | | | 3) THE SUBMITTED NOA'S FOR THE ROOF TOP EQUIPMENT ARE | | | INCOMPLETE. A) AC STAND NOA #13-1017.09: PAGES | | | 3,4,6,7,8, & 9 OF INSTALLATION DETAILS ARE MISSING. THE | | | REMAINING INSTALLATION PAGES WERE REDUCED IN SIZE AND | | | HAVE PRINT THAT IS TOO SMALL TO READ AND TO SCAN INTO | | | THE BUILDING DEPARTMENT COMPUTER FILES. B) GREENHECK | | | FAN #14-0513.10: INSTALLATION PAGES 1-7 HAVE PRINT TOO | | | SMALL TO READ OR TO SCAN. C) THYBAR CORP. CURB | | | #15-0218.11: INSTALL. SHEETS 1-5 HAVE PRINT TOO SMALL | | | TO READ OR SCAN. PLEASE REFER TO SECTION 107.2.1 WPB | | | AMENDMENTS TO THE FLORIDA BUILDING CODE AND PROVIDE | | | LEGIBLE DOCUMENTS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-08-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-08-13 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-08-13 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2015-08-13 16:46:08 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15080178 | | | 8/13/15 | | | | | | 1) REFERENCE SECTION C403.2.1 FBC-14 ENERGY | | | CONSERVATION AND PROVIDE COMPLIANCE SUBMITTALS- | | | CALCULATION OF HEATING AND COOLING LOADS: | | | DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE | | | PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR | | | ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE | | | COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT | | | WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE | | | MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE | | | SIZING CALCULATION SHALL BE SUBMITTED WITH THE | | | APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND | | | COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD | | | REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY | | | SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE | | | WITH THE ASHRAE HVAC SYSTEMS AND EQUIPMENT HANDBOOK. | | | ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN | | | APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE | | | DESIGN PARAMETERS SPECIFIED IN CHAPTER 3. | | | 2) PLEASE NOTE THAT THE CITY OF WEST PALM BEACH | | | CONSTRUCTION SERVICES DIVISION REQUIRES SEPARATE | | | PERMITS FOR REFRIGERATION SYSTEMS, AND KTICHEN HOOD AND | | | EXHAUST SYSTEMS. | | | 3) PROVIDE DUCT SEALING AND ATTACHMENT DETAILS IN | | | COMPLIANCE WITH TABLE C403.2.7.2 FBC-14 ENERGY | | | CONSERVATION, AND DUCT SUPPORT DETAILS IN COMPLIANCE | | | WITH SMACNA HVAC DUCT CONSTRUCTION STANDARDS- 2005. | | | 4) SHEET M1.1: REFERENCE SECTION 301.15 FBC-14 | | | MECHANICAL AND PROVIDE THE DESIGN WIND PRESSURES FOR | | | THE ROOF TOP EQUIPMENT INSTALLATIONS. THE DETAILS SHOWN | | | ON THE PLAN ARE FOR THE RTU AND FLEXPACK INSTALLATIONS- | | | PLEASE ALSO PROVIDE DETAILS FOR THE FLEXPACK GRAVITY | | | VENTILATOR. | | | 5) M1.1: SUBMIT TWO COPIES OF A CURRENT FLORIDA PRODUCT | | | APPROVAL OR MIAMI-DADE NOA FOR THE CONDENSER ROOF STAND | | | REVIEWED AND APPROVED BY THE ENGINEER OF RECORD. THE | | | ENGINEER SHALL CIRCLE, HIGHLIGHT, OR OTHERWISE MARK ALL | | | DETAILS, NOTES, ANCHOR AND FASTENER SCHEDULES | | | APPLICABLE TO THE PROPOSED INSTALLATION. | | | 6) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE RTU'S AND | | | FLEXPACK UNIT: SHOW THE TYPE AND SIZE OF CONDENSATE | | | PIPES, PIPE RUNS, PIPE SUPPORTS, PIPE PROTECTION, AND | | | CONDENSATE DISCHARGE LOCATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2015-12-18 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2015-12-18 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2015-12-18 |
Time |
13:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2015-11-10 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2015-11-10 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2015-11-10 |
Time |
08:35 |
Sent To |
|
|
| Notes |
| 2015-11-10 08:34:58 | | | | FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | PROVISO | | | 1. PROVIDE ON THE JOBSITE FOR INSPECTION TWO COPIES OF | | | SIGNED AND SEALED MANUFACTURE SPECS FOR INSTALLATION | | | /ANCHORING OF CO2 TANK. | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2015-10-04 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-10-04 |
Time |
04:30 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-10-04 |
Time |
08:36 |
Sent To |
|
|
| Notes |
| 2015-10-04 08:53:39 | 1) THE SUBMITTED ENGINEERING FOR THE CO2 TANK ARE | | | COPIES AND CANNOT BE ACCEPTED.FL. ADMIN. CODE RULE | | | 62G15-23.002 REQUIRES A SEAL AND WET SIGNATURE. | | | 2) THE CIRCLED WIND LOAD IS FOR 140 MPH AND THE WIND | | | ZONE FOR THIS AREA IS 170 MPH. | | | 3)THE CALCULATIONS FOR THE SCHIER GREASE TRAP SHALL BE | | | REVIEWED BY SCHIER TO ENSURE CORRECT SIZING.2014 | | | FBC-PLUMBING SEC.1003.2. PLEASE CONTACT LEE | | | SCHNEEWEISS, SCHIER REPRESENTATIVE AT | | | 1-800-538-4792.2ND REQUEST. | | | 4) SUBMIT ELEVATION DETAILS FOR THE DRINKING | | | FOUNTAIN.COMPLY WITH 2014 FBC-ACCESSIBILITY SECS.306 & | | | 602. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2015-08-28 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-08-28 |
Time |
12:36 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-08-27 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2015-08-28 11:00:13 | 1) A MINIMUM OF 2 DRINKING FOUNTAINS ARE REQUIRED IN | | | ACCORDANCE WITH TABLE 403.1 AND FOOTNOTE (E) OF THE | | | 2014 FBC-PLUMBING AND ALSO FBC-ACCESSIBILITY SEC. | | | 211.2. | | | 2) SHT. A2.0 - SUBMIT ENGINEERING ON THE ANCHORING OF | | | THE CO2 TANK. THE ANCHORING SHALL BE DESIGNED FOR 170 | | | MPH V ULT EXPOSURE B. | | | 3) THE BEVERAGE AND COFFEE MACHINES AND NONCARBONATED | | | BEVERAGE DISPENSERS SHALL BE EQUIPPED WITH BACKFLOW | | | PREVENTERS COMPLYING WITH ASSE 1022 PER THE 2014 | | | FBC-PLUMBING SECS.608.16.1 & 608.16.10. | | | 3) THE CALCULATIONS FOR THE SCHIER GREASE TRAP SHALL BE | | | REVIEWED BY SCHIER TO ENSURE CORRECT SIZING.2014 | | | FBC-PLUMBING SEC.1003.2. PLEASE CONTACT LEE | | | SCHNEEWEISS, SCHIER REPRESENTATIVE AT 1-800-538-4792. | | | 4) SHT. A2.2 - SUBMIT ROOF DRAINAGE CALCULATIONS. THE | | | CALCULATIONS SHALL INCLUDE 1/2 THE AREA OF ANY VERTICAL | | | WALL (PARAPET) THAT DIVERTS RAINWATTER TO THE ROOF. THE | | | SCUPPERS SHALL BE SIZED IN ACCORDANCE WITH 2014 | | | FBC-PLUMBING TABLE 1106.7. INDICATE THE HEAD IN INCHES | | | IN THE CALCULATIONS. | | | 5) SHT.A2.2 - SHOW THE DIMENSIONS OF THE OVERFLOW | | | SCUPPERS ON THE PLANS. | | | 6) SUBMIT DETAILS ON THE CANOPY DOWNSPOUTS. WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | 7) SHT. A5.1 - DETAIL #3 - SHOW THE REQUIRED KNEE AND | | | TOE CLEARANCES FOR THE LAVATORY PER 2014 | | | FBC-ACCESSIBILITY SEC. 306. | | | 8) SHT. A5.1 - DETAIL #4 - THE WATER CLOST SHALL BE | | | 16"- 18" TO THE CENTER FROM THE SIDE WALL PER 2014 | | | FBC-ACCESSIBILITY, SEC.604.2. | | | 9) SHT. A8.0 - EQUIPMENT #'S 113,195, 196, & 306 APPEAR | | | HAVE THE OPERABLE PARTS OF THE EQUIPMENT OUTSIDE THE | | | MAXIMUM REACH RANGES REQUIRED IN 2014 FBC SECS.227, 308 | | | & 309. INDICATE THE MAXIMUM WIDTH OF THE OBSTRUCTION | | | FOR ALL EQUIPMENT ON THE COUNTERS.( SHOW THE DISTANCE | | | THAT THE EQUIPMENT IS SET BACK FROM THE EDGE OF THE | | | COUNTER. THIS WILL DETERMINE THE WIDTH OF THE | | | "OBSTRUCTION." ) REFER TO 2014 FBC-ACCESSIBILITY, | | | FIGURE 308.3.2. | | | 10.) SHT. P1.0 & P1.1- THE PLANS REFER TO CIVIL | | | DRAWINGS FOR THE CONTINUATION OF THE 4' SEWER FROM THE | | | ADJACENT TENANT SPACE AND ALSO FOR THE CONTINUATION OF | | | THE WATER AND SEWER FORM THE 7-11. THERE ARE NO CIVIL | | | DRAWINGS WITH THESE PLANS. CLARIFY. | | | 11) SHOW THE TERMINATION POINT OF THE RELIEF VALVE AND | | | THE PAN DRAIN FROM THE WATER HEATER. COMPLY WITH 2014 | | | FBC-PLUMBING SECS.504.6, 504.7-504.7.2. | | | 12) SHT. P1.3 - SIZE ALL SECTIONS OF THE VENTING | | | SYSTEM, SIZE ALL STACKS (WET & DRY SECTIONS.) WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 13) SHT. P1.3 - THE STACK FOR THE 3" HUB DRAIN FOR | | | CONDENSATE STARTS AS 3", A SECTION OF THE VENT IS 1 | | | 1/2", AND THEN 3" THROUGH THE ROOF. CLARIFY. | | | 14) IF THE DEVELOPED LENGTH OF THE HOT WATER PIPING | | | FROM THE SOURCE OF HOT WATER EXCEEDS 50 FEET THEN A HOT | | | WATER RECIRCULATION LINE SHALL BE INSTALLED PER 2014 | | | FBC-PLUMBING SEC.607.2. | | | 15) THE MAXIMUM TEMPERATURE OF HOT WATER TO LAVATORIES | | | IN PUBLIC RESTROOMS SHALL NOT EXCEED 110 DEGREES. 2014 | | | FBC-ENERGY SEC. C404.3 & C404.8.2. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2015-12-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-12-29 |
Time |
06:56 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-12-29 |
Time |
06:56 |
Sent To |
|
|
| Notes |
| 2015-12-29 06:58:46 | ROOFING: DEFERRED SUBMITTALS. ROOFING PRODUCT APPROVALS | | | TO BE SUBMITTED AFTER PERMIT ISSUANCE AS A SUBMITTAL TO | | | BE REVIEWED BY THE DESIGNER OF RECORD BEFORE | | | SUBMITTING TO THE BUILDING DEPARTMENT. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2015-10-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-10-16 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-10-16 |
Time |
|
Sent To |
|
|
| Notes |
| 2015-10-16 11:46:39 | ROOFING PLAN REVIEW | | | W. P. B. PERMIT:15080178 / NEW 7/11 BUILDING | | | ADD: 2100 45TH ST. | | | CONT: TBD/ TO BE DETERMINED | | | TEL: (???)???-???? | | | E-MAIL:???????????????? | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION, | | | | | | 2ND REVIEW | | | DATE: FRI. OCT. 16/ 2015 | | | ACTION: DENIED | | | | | | 1) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | | WILL REQUIRE PRODUCT APPROVALS: | | | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | ROOFING PRODUCT APPROVAL SUBMITTED NOA 13-0419.05 PAGE | | | 08 MAXIMUM DESIGN PRESSURE OF -45 AND LIMITATION NUMBER | | | 9 NO ENHANCED FASTENING IS ALLOWED!!!!!!! | | | | | | SKYLIGHT REPORT PTC IS A OLD 2007 REPORT UNDER RULE 9B. | | | PLEASE NOTE RULE 9B ENDED OCT 31/ 2010. RULE 9N-3 | | | REPLACED THIS RULE NOV.01/2010. THERE HAS BEEN 2 CODE | | | CYCLES THE 2010 AND 2014 FBC, PLEASE UPDATE EVALUATION | | | REPORT. NOTE THE NOA 08-0305.02 POLYCARBONATE IS A | | | EXPIRED REPORT ALSO. | | | | | | CARRIER ROOF TOP CURBS NOA 15-0218.11 PLEASE BE AWARE | | | THERE IS A ISSUE WITH THE RESTRAINT BRACKET SHOWN ON | | | SHEET 2 OF 5, ALSO SEE DETAIL OF RESTRAINT BRACKET ON | | | SHEET 5 OF 5. SHEET 2 OF 5 INDICATES (7) # 10 TEK | | | SCREWS THAT ARE TO HOLD THE RESTRAINT BRACKET TO THE | | | ROOF CURB. PAGE 5 SHOWS THE BRACKET DOES NOT TURN DOWN | | | THE INTERIOR OF THE CURB. HOW WILL THE RESTRAINT | | | BRACKET BE HELD TO THE CURB. | | | DISCREPANCY IN PLANS. 107.2.1.3. ADDITIONAL INFORMATION | | | IS REQUIRED. | | | | | | NOA 14-0513.10 IS FOR THE ROOFTOP FANS, NO PRODUCT | | | APPROVALS WAS SUBMITTED FOR THE CURB. HIGHLIGHT CIRCLE | | | TYPE OF UNIT AND PRESSURES. 107.2.1.3 ADDITIONAL | | | INFORMATION IS REQUIRED. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2015-08-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-08-24 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-08-24 |
Time |
10:00 |
Sent To |
|
|
| Notes |
| 2015-08-24 12:12:18 | THIS SUBMISSION NO ROOFING PRODUCT APPROVALS WERE | | | SUBMITTED. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE | | | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR | | | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31) (D) ROOFING PRODUCTS AND ASSEMBLIES | | | | | | 2014 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
P |
Date |
2016-06-24 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2016-06-24 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2016-06-24 |
Time |
11:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
F |
Date |
2016-05-17 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2016-05-17 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2016-05-13 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2016-05-17 15:03:19 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 05.17.2016 | | | PERMIT NO.: 15080178 | | | ADDRESS: 2100 45TH STREET | | | CONTRACTOR/CONTACT: | | | TELEPHONE NO.: | | | SCOPE OF REVIEW: NEW MULTI-TENANT BUILDING, INCLUDING | | | 7-ELEVEN CONVENIENCE STORE. | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. PURSUANT TO RESOLUTION NO. 189-15, PRIOR TO THE | | | ISSUANCE OF A BUILDING PERMIT, THE CITY OF WEST PALM | | | BEACH POLICE DEPARTMENT - CRIME PREVENTION UNIT SHALL | | | REVIEW AND APPROVE ALL CONSTRUCTION DRAWINGS TO ENSURE | | | THE ADHERENCE TO GENERALLY-ACCEPTED CRIME PREVENTION | | | THROUGH ENVIRONMENTAL DESIGN PRINCIPLES, AS WELL AS | | | COMPLIANCE WITH ALL LOCAL AND STATE REGULATIONS | | | PERTAINING TO THE PROPOSED USE. SUCH SUBMITTAL SHALL | | | INCLUDE A CONSTRUCTION SITE SECURITY AND MANAGEMENT | | | PLAN. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | WWW.WPB.ORG | | | | | | 8/17/15 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2016-01-20 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2016-01-20 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2016-01-20 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2016-01-20 10:41:09 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 01.20.2015 | | | PERMIT NO.: 15080178 | | | ADDRESS: 2100 45TH STREET | | | CONTRACTOR/CONTACT: | | | TELEPHONE NO.: | | | SCOPE OF REVIEW: NEW MULTI-TENANT BUILDING, INCLUDING | | | 7-ELEVEN CONVENIENCE STORE. | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. TWO (2) COPIES OF A SITE PLAN SHALL BE PROVIDED. THE | | | SITE PLAN SHALL PROVIDE THE FOLLOWING: | | | | | | A. DATE, NORTH ARROW, AND A GRAPHIC SCALE. | | | | | | B. VICINITY MAP SHOWING THE PROPERTY IN RELATION TO | | | THE SURROUNDING AREA. | | | | | | C. LOCATION OF THE PROPERTY LINE, RIGHT-OF-WAY, | | | PROPOSED/EXISTING EASEMENTS, WATER COURSES AND OTHER | | | ESSENTIAL FEATURES. | | | | | | D. STREETS, DRIVEWAYS, INTERSECTIONS, CURBS CUTS AND | | | TURNING LANES ADJACENT TO OR ACROSS FROM THE SUBJECT | | | PROPERTY. | | | | | | E. THE OUTLINES OF ALL BUILDINGS SHOWING THEIR | | | PROPOSED USES, SETBACKS, DIMENSIONS, FLOOR AREA, NUMBER | | | OF STORIES, HEIGHT AND POINTS OF ACCESS. | | | | | | F. LOCATION AND DIMENSIONS OF ALL PERIMETER TREATMENT | | | (SIDEWALKS, FENCES, WALLS, OR BERMS). | | | | | | G. LOCATION, HEIGHT AND SIZE OF ALL FREESTANDING SIGNS | | | AND OTHER ACCESSORY STRUCTURES. | | | | | | H. MEANS OF VEHICULAR AND PEDESTRIAN ACCESS TO AND | | | FROM THE SITE. | | | | | | I. LAYOUT AND LOCATION OF ALL OFF-STREET PARKING, | | | LOADING AND OTHER VEHICULAR USE AREAS, INCLUDING WHERE | | | APPLICABLE, THE DISTANCE FROM THE PRINCIPLE USES. | | | | | | J. LOCATION OF ALL DISABLED SPACES, RAMPS AND SIGNS. | | | | | | K. LOCATION OF EXISTING AND PROPOSED FIRE HYDRANTS (OR | | | OPERATIONAL EQUIVALENTS) WITHIN 250 FEET OF THE | | | PROPOSED STRUCTURE OR STRUCTURES. | | | | | | L. LOCATION AND SCREENING OF ALL GARBAGE RECEPTACLES. | | | | | | M. STANDARD CITY DETAILS OF PARKING (SMALL CAR, | | | HANDICAP SPACE, STANDARD SPACE), HANDICAP RAMPS, | | | DRIVEWAYS, DUMPSTERS AND SIGNS. | | | | | | N. LOCATION, DIMENSIONS AND SCREENING ALL OF PROPOSED | | | SATELLITE DISHES. | | | | | | O. SUPPLY A DATA TABLE IN THE FOLLOWING FORMAT: | | | | | | I. EXISTING/PROPOSED LAND USE AND ZONING. | | | | | | II. TOTAL ACRES OF THE PROJECT. | | | | | | III. TOTAL GROSS BUILDING SQUARE FOOTAGE. | | | | | | IV. PERCENT OF OPEN SPACE, LANDSCAPING, BUILDING | | | COVERAGE & IMPERMEABLE SURFACE. | | | | | | V. ACRES AND PERCENT OF WATER BODIES. | | | | | | VI. DENSITY AND NUMBER OF DWELLING UNITS | | | (RESIDENTIAL). | | | | | | VII. PARKING COMPUTATIONS (PARKING REQUIRED, | | | PROVIDED, ETC.) | | | | | | VIII. FLOOR AREA RATIO (FAR). | | | | | | 2. PURSUANT TO RESOLUTION NO. 189-15, PRIOR TO THE | | | ISSUANCE OF A BUILDING PERMIT: | | | | | | A. ONE (1) OF THE FOLLOWING SHALL OCCUR: | | | | | | I. THE EXISTING 12 FOOT UTILITY EASEMENT, AS | | | DEDICATED AND SHOWN ON THE PLAT OF VILLAGE PROMENADE, | | | RECORDED IN PLAT BOOK 51, PAGE 120 OF THE PUBLIC | | | RECORDS OF PALM BEACH COUNTY, FLORIDA, SHALL BE | | | ABANDONED; OR | | | | | | II. THE DEVELOPER SHALL OBTAIN CONSENT FROM ALL | | | UTILITY COMPANIES FOR ALL IMPROVEMENTS PROPOSED WITHIN | | | THE ABOVE-REFERENCED UTILITY EASEMENT; OR | | | | | | III. THE PLANS SHALL BE REVISED TO REMOVE OR RELOCATE | | | ALL IMPROVEMENTS PROPOSED WITHIN THE ABOVE-REFERENCED | | | UTILITY EASEMENT. | | | | | | B. THE DEVELOPER SHALL OBTAIN WRITTEN APPROVAL FROM | | | PERINI LAND AND DEVELOPMENT COMPANY, OR ITS SUCCESSORS | | | OR ASSIGNS, IN ACCORDANCE WITH THAT COVENANT AND | | | CONDITION DISCLOSED BY WARRANTY DEED RECORDED IN | | | OFFICIAL RECORDS BOOK 4469, PAGE 541 OF THE PUBLIC | | | RECORDS OF PALM BEACH COUNTY, FLORIDA. | | | | | | C. THE CITY OF WEST PALM BEACH POLICE DEPARTMENT - | | | CRIME PREVENTION UNIT SHALL REVIEW AND APPROVE ALL | | | CONSTRUCTION DRAWINGS TO ENSURE THE ADHERENCE TO | | | GENERALLY-ACCEPTED CRIME PREVENTION THROUGH | | | ENVIRONMENTAL DESIGN PRINCIPLES, AS WELL AS COMPLIANCE | | | WITH ALL LOCAL AND STATE REGULATIONS PERTAINING TO THE | | | PROPOSED USE. SUCH SUBMITTAL SHALL INCLUDE A | | | CONSTRUCTION SITE SECURITY AND MANAGEMENT PLAN. | | | | | | 3. A LANDSCAPE PERMIT APPLICATION SHALL BE SUBMITTED | | | ALONG WITH TWO (2) SETS OF SIGNED/SEALED LANDSCAPE | | | PLANS AND A CERTIFIED COST ESTIMATE (MATERIALS + | | | LABOR). | | | | | | 4. A SEPARATE PERMIT APPLICATION SHALL BE SUBMITTED FOR | | | SITE LIGHTING ALONG WITH TWO (2) SETS OF PHOTOMETRIC | | | PLANS, DETAILS/SPECS/ETC. OF THE PROPOSED FIXTURES AND | | | POLES, ETC. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | WWW.WPB.ORG | | | | | | 8/17/15 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2015-11-18 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2015-11-18 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2015-11-18 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2015-11-18 10:07:27 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 11.18.2015 | | | PERMIT NO.: 15080178 | | | ADDRESS: 2100 45TH STREET | | | CONTRACTOR/CONTACT: | | | TELEPHONE NO.: | | | SCOPE OF REVIEW: NEW MULTI-TENANT BUILDING, INCLUDING | | | 7-ELEVEN CONVENIENCE STORE. | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. TWO (2) COPIES OF A CURRENT AND ACCURATE SURVEY | | | SHALL BE PROVIDED. | | | | | | 2. TWO (2) COPIES OF A SITE PLAN SHALL BE PROVIDED. THE | | | SITE PLAN SHALL PROVIDE THE FOLLOWING: | | | | | | A. DATE, NORTH ARROW, AND A GRAPHIC SCALE. | | | | | | B. VICINITY MAP SHOWING THE PROPERTY IN RELATION TO | | | THE SURROUNDING AREA. | | | | | | C. LOCATION OF THE PROPERTY LINE, RIGHT-OF-WAY, | | | PROPOSED/EXISTING EASEMENTS, WATER COURSES AND OTHER | | | ESSENTIAL FEATURES. | | | | | | D. STREETS, DRIVEWAYS, INTERSECTIONS, CURBS CUTS AND | | | TURNING LANES ADJACENT TO OR ACROSS FROM THE SUBJECT | | | PROPERTY. | | | | | | E. THE OUTLINES OF ALL BUILDINGS SHOWING THEIR | | | PROPOSED USES, SETBACKS, DIMENSIONS, FLOOR AREA, NUMBER | | | OF STORIES, HEIGHT AND POINTS OF ACCESS. | | | | | | F. LOCATION AND DIMENSIONS OF ALL PERIMETER TREATMENT | | | (SIDEWALKS, FENCES, WALLS, OR BERMS). | | | | | | G. LOCATION, HEIGHT AND SIZE OF ALL FREESTANDING SIGNS | | | AND OTHER ACCESSORY STRUCTURES. | | | | | | H. MEANS OF VEHICULAR AND PEDESTRIAN ACCESS TO AND | | | FROM THE SITE. | | | | | | I. LAYOUT AND LOCATION OF ALL OFF-STREET PARKING, | | | LOADING AND OTHER VEHICULAR USE AREAS, INCLUDING WHERE | | | APPLICABLE, THE DISTANCE FROM THE PRINCIPLE USES. | | | | | | J. LOCATION OF ALL DISABLED SPACES, RAMPS AND SIGNS. | | | | | | K. LOCATION OF EXISTING AND PROPOSED FIRE HYDRANTS (OR | | | OPERATIONAL EQUIVALENTS) WITHIN 250 FEET OF THE | | | PROPOSED STRUCTURE OR STRUCTURES. | | | | | | L. LOCATION AND SCREENING OF ALL GARBAGE RECEPTACLES. | | | | | | M. STANDARD CITY DETAILS OF PARKING (SMALL CAR, | | | HANDICAP SPACE, STANDARD SPACE), HANDICAP RAMPS, | | | DRIVEWAYS, DUMPSTERS AND SIGNS. | | | | | | N. LOCATION, DIMENSIONS AND SCREENING ALL OF PROPOSED | | | SATELLITE DISHES. | | | | | | O. SUPPLY A DATA TABLE IN THE FOLLOWING FORMAT: | | | | | | I. EXISTING/PROPOSED LAND USE AND ZONING. | | | | | | II. TOTAL ACRES OF THE PROJECT. | | | | | | III. TOTAL GROSS BUILDING SQUARE FOOTAGE. | | | | | | IV. PERCENT OF OPEN SPACE, LANDSCAPING, BUILDING | | | COVERAGE & IMPERMEABLE SURFACE. | | | | | | V. ACRES AND PERCENT OF WATER BODIES. | | | | | | VI. DENSITY AND NUMBER OF DWELLING UNITS | | | (RESIDENTIAL). | | | | | | VII. PARKING COMPUTATIONS (PARKING REQUIRED, | | | PROVIDED, ETC.) | | | | | | VIII. FLOOR AREA RATIO (FAR). | | | | | | 3. PURSUANT TO RESOLUTION NO. 189-15, PRIOR TO THE | | | ISSUANCE OF A BUILDING PERMIT: | | | | | | A. ONE (1) OF THE FOLLOWING SHALL OCCUR: | | | | | | I. THE EXISTING 12 FOOT UTILITY EASEMENT, AS | | | DEDICATED AND SHOWN ON THE PLAT OF VILLAGE PROMENADE, | | | RECORDED IN PLAT BOOK 51, PAGE 120 OF THE PUBLIC | | | RECORDS OF PALM BEACH COUNTY, FLORIDA, SHALL BE | | | ABANDONED; OR | | | | | | II. THE DEVELOPER SHALL OBTAIN CONSENT FROM ALL | | | UTILITY COMPANIES FOR ALL IMPROVEMENTS PROPOSED WITHIN | | | THE ABOVE-REFERENCED UTILITY EASEMENT; OR | | | | | | III. THE PLANS SHALL BE REVISED TO REMOVE OR RELOCATE | | | ALL IMPROVEMENTS PROPOSED WITHIN THE ABOVE-REFERENCED | | | UTILITY EASEMENT. | | | | | | B. THE DEVELOPER SHALL OBTAIN WRITTEN APPROVAL FROM | | | PERINI LAND AND DEVELOPMENT COMPANY, OR ITS SUCCESSORS | | | OR ASSIGNS, IN ACCORDANCE WITH THAT COVENANT AND | | | CONDITION DISCLOSED BY WARRANTY DEED RECORDED IN | | | OFFICIAL RECORDS BOOK 4469, PAGE 541 OF THE PUBLIC | | | RECORDS OF PALM BEACH COUNTY, FLORIDA. | | | | | | C. THE CITY OF WEST PALM BEACH POLICE DEPARTMENT - | | | CRIME PREVENTION UNIT SHALL REVIEW AND APPROVE ALL | | | CONSTRUCTION DRAWINGS TO ENSURE THE ADHERENCE TO | | | GENERALLY-ACCEPTED CRIME PREVENTION THROUGH | | | ENVIRONMENTAL DESIGN PRINCIPLES, AS WELL AS COMPLIANCE | | | WITH ALL LOCAL AND STATE REGULATIONS PERTAINING TO THE | | | PROPOSED USE. SUCH SUBMITTAL SHALL INCLUDE A | | | CONSTRUCTION SITE SECURITY AND MANAGEMENT PLAN. | | | | | | 4. A LANDSCAPE PERMIT APPLICATION SHALL BE SUBMITTED | | | ALONG WITH TWO (2) SETS OF SIGNED/SEALED LANDSCAPE | | | PLANS AND A CERTIFIED COST ESTIMATE (MATERIALS + | | | LABOR). | | | | | | 5. A SEPARATE PERMIT APPLICATION SHALL BE SUBMITTED FOR | | | SITE LIGHTING ALONG WITH TWO (2) SETS OF PHOTOMETRIC | | | PLANS, DETAILS/SPECS/ETC. OF THE PROPOSED FIXTURES AND | | | POLES, ETC. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | WWW.WPB.ORG | | | | | | 8/17/15 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2015-10-21 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2015-10-21 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2015-10-21 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2015-10-21 10:27:18 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 10.21.2015 | | | PERMIT NO.: 15080178 | | | ADDRESS: 2100 45TH STREET | | | CONTRACTOR/CONTACT: | | | TELEPHONE NO.: | | | SCOPE OF REVIEW: NEW MULTI-TENANT BUILDING, INCLUDING | | | 7-ELEVEN CONVENIENCE STORE. | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. TWO (2) COPIES OF A CURRENT AND ACCURATE SURVEY | | | SHALL BE PROVIDED. | | | | | | 2. TWO (2) COPIES OF A SITE PLAN SHALL BE PROVIDED. THE | | | SITE PLAN SHALL PROVIDE THE FOLLOWING: | | | | | | A. DATE, NORTH ARROW, AND A GRAPHIC SCALE. | | | | | | B. VICINITY MAP SHOWING THE PROPERTY IN RELATION TO | | | THE SURROUNDING AREA. | | | | | | C. LOCATION OF THE PROPERTY LINE, RIGHT-OF-WAY, | | | PROPOSED/EXISTING EASEMENTS, WATER COURSES AND OTHER | | | ESSENTIAL FEATURES. | | | | | | D. STREETS, DRIVEWAYS, INTERSECTIONS, CURBS CUTS AND | | | TURNING LANES ADJACENT TO OR ACROSS FROM THE SUBJECT | | | PROPERTY. | | | | | | E. THE OUTLINES OF ALL BUILDINGS SHOWING THEIR | | | PROPOSED USES, SETBACKS, DIMENSIONS, FLOOR AREA, NUMBER | | | OF STORIES, HEIGHT AND POINTS OF ACCESS. | | | | | | F. LOCATION AND DIMENSIONS OF ALL PERIMETER TREATMENT | | | (SIDEWALKS, FENCES, WALLS, OR BERMS). | | | | | | G. LOCATION, HEIGHT AND SIZE OF ALL FREESTANDING SIGNS | | | AND OTHER ACCESSORY STRUCTURES. | | | | | | H. MEANS OF VEHICULAR AND PEDESTRIAN ACCESS TO AND | | | FROM THE SITE. | | | | | | I. LAYOUT AND LOCATION OF ALL OFF-STREET PARKING, | | | LOADING AND OTHER VEHICULAR USE AREAS, INCLUDING WHERE | | | APPLICABLE, THE DISTANCE FROM THE PRINCIPLE USES. | | | | | | J. LOCATION OF ALL DISABLED SPACES, RAMPS AND SIGNS. | | | | | | K. LOCATION OF EXISTING AND PROPOSED FIRE HYDRANTS (OR | | | OPERATIONAL EQUIVALENTS) WITHIN 250 FEET OF THE | | | PROPOSED STRUCTURE OR STRUCTURES. | | | | | | L. LOCATION AND SCREENING OF ALL GARBAGE RECEPTACLES. | | | | | | M. STANDARD CITY DETAILS OF PARKING (SMALL CAR, | | | HANDICAP SPACE, STANDARD SPACE), HANDICAP RAMPS, | | | DRIVEWAYS, DUMPSTERS AND SIGNS. | | | | | | N. LOCATION, DIMENSIONS AND SCREENING ALL OF PROPOSED | | | SATELLITE DISHES. | | | | | | O. SUPPLY A DATA TABLE IN THE FOLLOWING FORMAT: | | | | | | I. EXISTING/PROPOSED LAND USE AND ZONING. | | | | | | II. TOTAL ACRES OF THE PROJECT. | | | | | | III. TOTAL GROSS BUILDING SQUARE FOOTAGE. | | | | | | IV. PERCENT OF OPEN SPACE, LANDSCAPING, BUILDING | | | COVERAGE & IMPERMEABLE SURFACE. | | | | | | V. ACRES AND PERCENT OF WATER BODIES. | | | | | | VI. DENSITY AND NUMBER OF DWELLING UNITS | | | (RESIDENTIAL). | | | | | | VII. PARKING COMPUTATIONS (PARKING REQUIRED, | | | PROVIDED, ETC.) | | | | | | VIII. FLOOR AREA RATIO (FAR). | | | | | | 3. PURSUANT TO RESOLUTION NO. 189-15, PRIOR TO THE | | | ISSUANCE OF A BUILDING PERMIT: | | | | | | A. ONE (1) OF THE FOLLOWING SHALL OCCUR: | | | | | | I. THE EXISTING 12 FOOT UTILITY EASEMENT, AS | | | DEDICATED AND SHOWN ON THE PLAT OF VILLAGE PROMENADE, | | | RECORDED IN PLAT BOOK 51, PAGE 120 OF THE PUBLIC | | | RECORDS OF PALM BEACH COUNTY, FLORIDA, SHALL BE | | | ABANDONED; OR | | | | | | II. THE DEVELOPER SHALL OBTAIN CONSENT FROM ALL | | | UTILITY COMPANIES FOR ALL IMPROVEMENTS PROPOSED WITHIN | | | THE ABOVE-REFERENCED UTILITY EASEMENT; OR | | | | | | III. THE PLANS SHALL BE REVISED TO REMOVE OR RELOCATE | | | ALL IMPROVEMENTS PROPOSED WITHIN THE ABOVE-REFERENCED | | | UTILITY EASEMENT. | | | | | | B. THE DEVELOPER SHALL OBTAIN WRITTEN APPROVAL FROM | | | PERINI LAND AND DEVELOPMENT COMPANY, OR ITS SUCCESSORS | | | OR ASSIGNS, IN ACCORDANCE WITH THAT COVENANT AND | | | CONDITION DISCLOSED BY WARRANTY DEED RECORDED IN | | | OFFICIAL RECORDS BOOK 4469, PAGE 541 OF THE PUBLIC | | | RECORDS OF PALM BEACH COUNTY, FLORIDA. | | | | | | C. THE CITY OF WEST PALM BEACH POLICE DEPARTMENT - | | | CRIME PREVENTION UNIT SHALL REVIEW AND APPROVE ALL | | | CONSTRUCTION DRAWINGS TO ENSURE THE ADHERENCE TO | | | GENERALLY-ACCEPTED CRIME PREVENTION THROUGH | | | ENVIRONMENTAL DESIGN PRINCIPLES, AS WELL AS COMPLIANCE | | | WITH ALL LOCAL AND STATE REGULATIONS PERTAINING TO THE | | | PROPOSED USE. SUCH SUBMITTAL SHALL INCLUDE A | | | CONSTRUCTION SITE SECURITY AND MANAGEMENT PLAN. | | | | | | 4. A LANDSCAPE PERMIT APPLICATION SHALL BE SUBMITTED | | | ALONG WITH TWO (2) SETS OF SIGNED/SEALED LANDSCAPE | | | PLANS AND A CERTIFIED COST ESTIMATE (MATERIALS + | | | LABOR). | | | | | | 5. A SEPARATE PERMIT APPLICATION SHALL BE SUBMITTED FOR | | | SITE LIGHTING ALONG WITH TWO (2) SETS OF PHOTOMETRIC | | | PLANS, DETAILS/SPECS/ETC. OF THE PROPOSED FIXTURES AND | | | POLES, ETC. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | WWW.WPB.ORG | | | | | | 8/17/15 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2015-09-10 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2015-09-10 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2015-09-10 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2015-09-10 15:01:09 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 08.21.2015 | | | PERMIT NO.: 15080178 | | | ADDRESS: 2100 45TH STREET | | | CONTRACTOR/CONTACT: | | | TELEPHONE NO.: | | | SCOPE OF REVIEW: NEW MULTI-TENANT BUILDING, INCLUDING | | | 7-ELEVEN CONVENIENCE STORE. | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. TWO (2) COPIES OF A CURRENT AND ACCURATE SURVEY | | | SHALL BE PROVIDED. | | | | | | 2. TWO (2) COPIES OF A SITE PLAN SHALL BE PROVIDED. THE | | | SITE PLAN SHALL PROVIDE THE FOLLOWING: | | | | | | A. DATE, NORTH ARROW, AND A GRAPHIC SCALE. | | | | | | B. VICINITY MAP SHOWING THE PROPERTY IN RELATION TO | | | THE SURROUNDING AREA. | | | | | | C. LOCATION OF THE PROPERTY LINE, RIGHT-OF-WAY, | | | PROPOSED/EXISTING EASEMENTS, WATER COURSES AND OTHER | | | ESSENTIAL FEATURES. | | | | | | D. STREETS, DRIVEWAYS, INTERSECTIONS, CURBS CUTS AND | | | TURNING LANES ADJACENT TO OR ACROSS FROM THE SUBJECT | | | PROPERTY. | | | | | | E. THE OUTLINES OF ALL BUILDINGS SHOWING THEIR | | | PROPOSED USES, SETBACKS, DIMENSIONS, FLOOR AREA, NUMBER | | | OF STORIES, HEIGHT AND POINTS OF ACCESS. | | | | | | F. LOCATION AND DIMENSIONS OF ALL PERIMETER TREATMENT | | | (SIDEWALKS, FENCES, WALLS, OR BERMS). | | | | | | G. LOCATION, HEIGHT AND SIZE OF ALL FREESTANDING SIGNS | | | AND OTHER ACCESSORY STRUCTURES. | | | | | | H. MEANS OF VEHICULAR AND PEDESTRIAN ACCESS TO AND | | | FROM THE SITE. | | | | | | I. LAYOUT AND LOCATION OF ALL OFF-STREET PARKING, | | | LOADING AND OTHER VEHICULAR USE AREAS, INCLUDING WHERE | | | APPLICABLE, THE DISTANCE FROM THE PRINCIPLE USES. | | | | | | J. LOCATION OF ALL DISABLED SPACES, RAMPS AND SIGNS. | | | | | | K. LOCATION OF EXISTING AND PROPOSED FIRE HYDRANTS (OR | | | OPERATIONAL EQUIVALENTS) WITHIN 250 FEET OF THE | | | PROPOSED STRUCTURE OR STRUCTURES. | | | | | | L. LOCATION AND SCREENING OF ALL GARBAGE RECEPTACLES. | | | | | | M. STANDARD CITY DETAILS OF PARKING (SMALL CAR, | | | HANDICAP SPACE, STANDARD SPACE), HANDICAP RAMPS, | | | DRIVEWAYS, DUMPSTERS AND SIGNS. | | | | | | N. LOCATION, DIMENSIONS AND SCREENING ALL OF PROPOSED | | | SATELLITE DISHES. | | | | | | O. SUPPLY A DATA TABLE IN THE FOLLOWING FORMAT: | | | | | | I. EXISTING/PROPOSED LAND USE AND ZONING. | | | | | | II. TOTAL ACRES OF THE PROJECT. | | | | | | III. TOTAL GROSS BUILDING SQUARE FOOTAGE. | | | | | | IV. PERCENT OF OPEN SPACE, LANDSCAPING, BUILDING | | | COVERAGE & IMPERMEABLE SURFACE. | | | | | | V. ACRES AND PERCENT OF WATER BODIES. | | | | | | VI. DENSITY AND NUMBER OF DWELLING UNITS | | | (RESIDENTIAL). | | | | | | VII. PARKING COMPUTATIONS (PARKING REQUIRED, | | | PROVIDED, ETC.) | | | | | | VIII. FLOOR AREA RATIO (FAR). | | | | | | 3. PURSUANT TO RESOLUTION NO. 189-15, PRIOR TO THE | | | ISSUANCE OF A BUILDING PERMIT: | | | | | | A. ONE (1) OF THE FOLLOWING SHALL OCCUR: | | | | | | I. THE EXISTING 12 FOOT UTILITY EASEMENT, AS | | | DEDICATED AND SHOWN ON THE PLAT OF VILLAGE PROMENADE, | | | RECORDED IN PLAT BOOK 51, PAGE 120 OF THE PUBLIC | | | RECORDS OF PALM BEACH COUNTY, FLORIDA, SHALL BE | | | ABANDONED; OR | | | | | | II. THE DEVELOPER SHALL OBTAIN CONSENT FROM ALL | | | UTILITY COMPANIES FOR ALL IMPROVEMENTS PROPOSED WITHIN | | | THE ABOVE-REFERENCED UTILITY EASEMENT; OR | | | | | | III. THE PLANS SHALL BE REVISED TO REMOVE OR RELOCATE | | | ALL IMPROVEMENTS PROPOSED WITHIN THE ABOVE-REFERENCED | | | UTILITY EASEMENT. | | | | | | B. THE DEVELOPER SHALL OBTAIN WRITTEN APPROVAL FROM | | | PERINI LAND AND DEVELOPMENT COMPANY, OR ITS SUCCESSORS | | | OR ASSIGNS, IN ACCORDANCE WITH THAT COVENANT AND | | | CONDITION DISCLOSED BY WARRANTY DEED RECORDED IN | | | OFFICIAL RECORDS BOOK 4469, PAGE 541 OF THE PUBLIC | | | RECORDS OF PALM BEACH COUNTY, FLORIDA. | | | | | | C. THE CITY OF WEST PALM BEACH POLICE DEPARTMENT ? | | | CRIME PREVENTION UNIT SHALL REVIEW AND APPROVE ALL | | | CONSTRUCTION DRAWINGS TO ENSURE THE ADHERENCE TO | | | GENERALLY-ACCEPTED CRIME PREVENTION THROUGH | | | ENVIRONMENTAL DESIGN PRINCIPLES, AS WELL AS COMPLIANCE | | | WITH ALL LOCAL AND STATE REGULATIONS PERTAINING TO THE | | | PROPOSED USE. SUCH SUBMITTAL SHALL INCLUDE A | | | CONSTRUCTION SITE SECURITY AND MANAGEMENT PLAN. | | | | | | 4. A LANDSCAPE PERMIT APPLICATION SHALL BE SUBMITTED | | | ALONG WITH TWO (2) SETS OF SIGNED/SEALED LANDSCAPE | | | PLANS AND A CERTIFIED COST ESTIMATE (MATERIALS + | | | LABOR). | | | | | | 5. A SEPARATE PERMIT APPLICATION SHALL BE SUBMITTED FOR | | | SITE LIGHTING ALONG WITH TWO (2) SETS OF PHOTOMETRIC | | | PLANS, DETAILS/SPECS/ETC. OF THE PROPOSED FIXTURES AND | | | POLES, ETC. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | WWW.WPB.ORG | | | | | 2015-08-17 11:10:27 | 8/17/15 |
|
|
|