Plan Review Details - Permit 15080162
Plan Review Stops For Permit 15080162
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-09-25 Cont ID  
Sent By jwitmer Date 2015-09-25 Time 14:27 Rev Time 0.00
Received By jwitmer Date 2015-09-25 Time 14:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-10 Cont ID  
Sent By JWitmer Date 2015-09-10 Time 06:58 Rev Time 0.00
Received By jwitmer Date 2015-09-10 Time 06:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-25 Cont ID  
Sent By jwitmer Date 2015-08-25 Time 14:02 Rev Time  
Received By jwitmer Date 2015-08-25 Time 10:33 Sent To  
Notes
2015-08-25 14:02:27BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080162
 ADD: 314 CLEMATIS ST.
 CONT: DOMUS CONSTRUCTION
 TEL: (954)931-1159
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 25/ 2015
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS INDICATE THE SUB-DIVIDING THIS
 A2 ASSEMBLY AREA INTO A RESTARAUNT AND THE OTHER A
 NIGHTCLUB. THE ACTUAL CONCERN IS THE EXTERIOR OCCUPANT
 LOAD OF 112 OCCUPANTS, ACTUAL COUNT BY SEATING 68.
 THERE NEEDS TO BE 2 MEANS OF EGRESS FROM THIS DECK
 WITHOUT GOING THROUGH THE BUILDING. NOTE THE PLANS SHOW
 2 EXITS IN THE RAILING SYSTEM BUT IN REALITY THERE IS
 ONLY ONE. DISCREPANCY IN THE PLANS. SINCE THE OCCUPANT
 LOAD FOR THIS ASSEMBLY AREA IS OVER 50 OCCUPANTS THE
 CODE REQUIRES (2) EXITS FROM THIS AREA, SEE 2014 FBC-B
 TABLE 1015.1. ASSEMBLY OCCUPANCY WITH OCCUPANT LOADS
 GREATER THAN 49 REQUIRES (2) MEANS OF EGRESS.
  
 2) PLEASE REVIEW SECTION 1015.2.1 EXCEPTION # 2
 REQUIRES 2014 FBC-B THE 2 EXITS TO BE 1/3RD THE
 DISTANCE APART.
  
 3) THE 2014 FL ACCESSIBLITY CODE SECTION 207.1 REFERS
 YOU TO SECTION 1007 OF THE 2003 IBC-B. SECTION 1007.1
 OF THE 2003 IBC STATES WHERE MORE THAN ONE MEANS OF
 EGRESS IS REQUIRED BY EITHER 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN 2 ACCESSIBLE MEANS OF
 EGRESS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-09-25 Cont ID  
Sent By skennedy Date 2015-09-25 Time 14:46 Rev Time 0.00
Received By skennedy Date 2015-09-21 Time 14:26 Sent To  
Notes
2015-09-25 14:50:22PROVISIONALLY APPROVED. SUBMIT
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
2015-09-22 17:15:019/22/15 - SPOKE W/ P. AGUIRRE. WE DISCUSSED THE
 CORRECTIONS REQUIRED. IN THE INTEREST OF A SPEEDY TURN
 AROUND, I OFFERED TO REVIEW THE CORRECTED PDF AND GET
 THEM BACK TO HIM ELECTRONICALLY STAMPED.
2015-09-22 09:30:159/21/15 PUT A CALL IN TO P. AGUIRRE. SPOKE W/BYRON AND
 LEFT MESSAGE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-09-17 Cont ID  
Sent By MAlbarra Date 2015-09-17 Time 20:11 Rev Time 0.00
Received By albarran Date 2015-09-17 Time 19:56 Sent To I
Notes
2015-09-17 20:12:45THE RESUBMITTAL FAILED TO ADDRESS THE ELECTRICAL
 COMMENTS, PRODUCT OF THE PREVIOUS REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-09-01 Cont ID  
Sent By albarran Date 2015-09-01 Time 10:18 Rev Time 0.00
Received By albarran Date 2015-09-01 Time 09:55 Sent To I
Notes
2015-09-01 10:26:04PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. THE NEC REQUIRES THAT THERE BE A DEDICATED SIGN
 OUTLET ABOVE/ADJACENT TO EVERY PEDESTRIAN ENTRY DOOR.
 2. NEC REQUIRES THAT THERE BE A SHOW WINDOW OUTLET
 ABOVE EVERY SHOW WINDOW FOR EVERY 12' OF OF WINDOW OR
 PORTION THEREOF.
 3. NEC PROHIBIT ELECTRICAL PANELS FROM BEING INSIDE
 BATHROOMS; THERE APPEARS TO BE A PANEL INSIDE THE MEN'S
 ROOM.
 4. THE SUBMITTED PLANS ARE MISSING SHEET "E2", RISER
 DIAGRAM AND PANEL SCHEDULES.
 5. THIS SHEET SHALL ALSO INCLUDE THE ELECTRICAL LOAD
 CALCS, OTHERWISE THEY SHALL BE PROVIDED ELSEWHERE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-03 Cont ID  
Sent By pleduc Date 2015-09-03 Time   Rev Time 0.00
Received By pleduc Date 2015-09-03 Time 12:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-08-17 Cont ID  
Sent By pleduc Date 2015-08-17 Time   Rev Time 0.00
Received By pleduc Date 2015-08-17 Time 15:13 Sent To  
Notes
2015-08-17 15:50:30THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE NEWLY CREATED EXITS SHALL COMPLY WITH NFPA 101,
 CHAPTER 7, 7.4 NUMBER OF EXITS.
  
 2) THE EXITS SHALL COMPLY WITH NFPA 101, CHAPTER 7, 7.5
 ARRANGEMENTS OF EXITS.
  
 3) SHEET A3, THE MINIMUM EXIT SEPARATION IS NOT
 INDICATED OF THE EXITS. THE TWO EXITS AT THE FRONT ARE
 NOT SEPARATED ENOUGH TO BE QUILFIED AT TWO EXITS. A
 THIRD EXIT IS REQUIRED.
  
 4) SHEET A3, THE COMMON PATH OF TRAVEL ALONG THE NEWLY
 CREATED REAR CORRIDOR APPEARS TO EXCEED 75'. PLEASE
 PROVIDE GREATER DETAIL ON ALL COMMON PATHS OF TRAVEL.
  
 5) PROVIDE THE PURPOSE AND FUNCTION OF THE ROLLING
 DOORS. WILL THEY BE TIED INTO THE FIRE ALARM SYSTEM?

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-09-25 Cont ID  
Sent By skennedy Date 2015-09-25 Time 14:46 Rev Time 0.00
Received By skennedy Date 2015-09-18 Time 11:11 Sent To  
Notes
2015-09-21 11:11:25RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-17 Cont ID  
Sent By albarran Date 2015-09-17 Time 20:21 Rev Time 0.00
Received By albarran Date 2015-09-02 Time 12:57 Sent To  
Notes
2015-09-17 20:22:259/17/15 - FAILED ELECTRICAL REVIEW. FAILED TO ADDRESS
 THE COMMENTS. CONTRACTOR NOTIFIED VIA EMAIL. SENT TO
 LARGE DENIED BIN "D". MA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-01 Cont ID  
Sent By albarran Date 2015-09-01 Time 10:28 Rev Time 0.00
Received By albarran Date 2015-08-06 Time 14:00 Sent To  
Notes
2015-09-01 10:28:079/1/15 - FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "D". MA

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-08-31 Cont ID  
Sent By ccole Date 2015-08-31 Time 15:28 Rev Time 0.00
Received By ccole Date 2015-08-31 Time 15:28 Sent To  
Notes
2015-08-31 15:30:461ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080162
 8/31/15
  
 MECHANICAL PROVISO:
 1) A REVISION TO THE PLANS IS REQUIRED FOR ANY
 ALTERATIONS TO THE EXISTING HVAC SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-09-04 Cont ID  
Sent By GJohnson Date 2015-09-04 Time 15:45 Rev Time 0.00
Received By gjohnson Date 2015-09-04 Time 15:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-08-20 Cont ID  
Sent By gjohnson Date 2015-08-20 Time 13:02 Rev Time 0.00
Received By gjohnson Date 2015-08-20 Time 13:02 Sent To  
Notes
2015-08-20 13:17:301ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  
  
 COMMENTS:
  
 1. COVER SHEET INDECATES A SHEET P-2 WITH RISER DIAGRAM
 PLEASE PROVIDE.
 WPB AMEND. TO FBC SEC.107.3.5.1.3(13)
 2. PLEASE CLARIFY AND MARK EXISTING AND NEW WATER AND
 SANITY PIPING ON SHEET P-1.
 WPB AMEND. TO FBC SEC. 107.2.1