Plan Review Details - Permit 15080126
Plan Review Stops For Permit 15080126
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-13 Cont ID  
Sent By jwitmer Date 2015-08-13 Time 08:23 Rev Time  
Received By jwitmer Date 2015-08-13 Time 07:01 Sent To  
Notes
2015-08-13 08:22:59BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080126
 ADD: 333 CLEMATIS ST. SUITE # 100
 CONT: HORMAK CONSTRUCTION
 TEL: (561)790-6863
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. AUG. 13/ 2015
 ACTION: DENIED
  
 CHANGE IN OCCUPANCY FROM A MERCANILE TO BUSINESS. TO BE
 REVIEWED UNDER THE 2014 EXISITNG BUILDING CODE CHAPTER
 10.
  
 1) SHEET A1 UNDER THE HEADING APPLICABLE CODES MAKES
 REFERENCE TO THE 2010 FBC AND FAMILY OF CODES. PLEASE
 NOTE ON JUNE 30/ 2015 STATEWIDE THE 5TH EDITION OF THE
 FLORIDA BUILDING CODE (2014 FBC) WAS ADOPTED, PLEASE
 UPDATE PLANS.
  
 2) PLEASE NOTE THE CONTRACT VALUE OF THIS PROJECT IS
 $20,000.00 DOLLORS. PLEASE PROVIDE A ITEMIZED LIST
 WHERE THESE FUNDS ARE TO BE SPENT. 2014
 FBC-ACCESSIBILITY PLEASE REVIEW WHERE MONIES ARE TO BE
 SPENT IN THIS ORDER SEE 202.4.2 ACCESSIBLE FEATURES IN
 THE EVENT OF DISPROPORTIONALITY.
  
 3) SHEET A1 SHOWS THE REAR EXTERIOR DOOR BEING BLOCKED
 IN. DOOR # 104 A EXISTING NON-CONFORMING DOOR WILL BE A
 REQUIRED MEANS OF EGRESS.
 THIS TENNANT SPACE IS APPROXIMATELY 120 FEET DEEP. THE
 2014 FBC-B TABLE 1013.3 WITH AN OCCUPAN LOAD LESS THAN
 OR EQUALL TO 30 NON-SPRINKLERED BUILDING COMMON PATH OF
 TRAVEL IS LIMITED TO 100 FEET. THIS TENNANT SPACE WILL
 REQUIRE 2 MEANS OF EGRESS.
  
 4) PLEASE REFER TO THE 2014 FBC-ACCESSIBILITY CODE TO
 207.1. MEANS OF EGRESS SHALL COMPLY WITH SECTION
 1003.2.13 OF THE INTERNATIONAL BUILDING CODE (2000
 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF THE
 INTERNATIONAL BUILDING CODE (2003 EDITION)
 (INCORPORATED BY REFERENCE, SEE ?REFERENCED STANDARDS?
 IN CHAPTER 1).
  
 2003 IBC0-B 1007.1 WHERE MORETHAN ONE OF MEANS OF
 EGRESS IS REQUIREDBY SECTION 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE,EACH ACCESSIBLE PORTIONOF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO ACCESSIBLE MEANS
 OF EGRESS.
  
 2014 FBC-B- ACCESS.CODE (FL. SPECIFIC GRAY BOX) 207.1.1
 BARRIERS AT COMMON OR EMERGENCY ENTRANCES AND EXITS OF
 BUSINESS ESTABLISHMENTS CONDUCTING BUSINESS WITH THE
 GENERAL PUBLIC THAT ARE EXISTING, UNDER CONSTRUCTION,
 OR UNDER CONTRACT FOR CONSTRUCTION WHICH WOULD PREVENT
 A PERSON FROM USING SUCH ENTRANCES OR EXITS SHALL BE
 REMOVED.
  
 5) DISCREPANCY IN PLANS SHEET A1 VERSES A2. PLEASE
 REVIEW THE NEW EXTERIOR FRONT DOOR 101. SHEET A-1
 INDICATES A SINGLE EXTERIOR SWING DOOR WHERE AS SHEET
 A2 INDICATES THIS SAME DOOR 101 TO BE A (2) 3 FT.
 DOORS. 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, ADDITIONAL
 INFORMATION IS REQUIRED, DISCREPANCY IN PLANS.
  
 6) SHEET A-1 AND A-4 THE NEW FRONT ENTRY SHOWS A
 EXISTING CONCRETE COLUMN. PLEASE SEE 2014
 FBC-ACCESSIBILITY CODE FIGURE 404.2.4.1(A) THE REQUIRED
 MANEUVERING CLEARANCES, IT APPEARS THE EXISTING
 CONCRETE COLUMN WILL BE IN THE MANEUVERING CLEARANCES.
 PLEASE BE AWARE OF THE REQUIRED 42 INCHES REQUIRED FOR
 MANEUVERING CLEARANCES SEE FIGURE 404.2.4.1( K).
  
 7) THE SUBMITTED ENERGY COMPLIANCE FORMS SUBMITTED ARE
 FORM 506-2010. PLEASE UPDATE FORMS TO THE 2014
 FBC-ENERGY.
  
  
 8) CHANGE IN OCCUPANCY: BEFORE A PERMIT TO CONSTRUCT,
 MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED
 BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025
 FOR MORE INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-08-19 Cont ID  
Sent By pleduc Date 2015-08-19 Time   Rev Time 0.00
Received By pleduc Date 2015-08-19 Time 09:16 Sent To  
Notes
2015-08-19 09:31:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 FIRE PREVENTION HAS NO ADDITIONAL COMMENTS THAN THOSE
 ALREADY PROVIDED BY BUILDING.
  
 ADDRESS THOSE COMMENTS AND RESUBMIT.
  
 ADDITIONAL COMMENTS MAY BE PROVIDED BASED ON THE
 RE-SUBMITTAL.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2015-08-05 Time 13:05 Sent To  
Notes
2015-08-05 13:05:59B21

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-08-13 Cont ID  
Sent By jwitmer Date 2015-08-13 Time 08:23 Rev Time 0.00
Received By jwitmer Date 2015-08-13 Time 08:23 Sent To  
Notes
2015-08-13 08:23:42IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-19 Cont ID  
Sent By ccole Date 2015-08-19 Time 12:30 Rev Time 0.00
Received By ccole Date 2015-08-19 Time 12:30 Sent To  
Notes
2015-08-19 13:01:461ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080126
 8/19/15
  
 1) THE SUBMITTED PLANS DO NOT CONTAIN ANY DETAILS OR
 SPECIFICATIONS FOR THE REQUIRED NAIL SALON EXHAUST
 SYSTEMS. PLEASE REFER TO TABLE 403.3 FBC-14 MECHANICAL-
 AN EXHAUST RATE OF 0.6 IS REQUIRED FOR NAIL SALONS. SEE
 FOOTNOTES B AND H REPRINTED BELOW AS THEY APPLY TO NAIL
 SALONS.
 B. MECHANICAL EXHAUST REQUIRED AND THE RECIRCULATION OF
 AIR FROM SUCH SPACES IS PROHIBITED (SEE SECTION
 403.2.1, ITEM 3).
 H. FOR NAIL SALONS, EACH NAIL STATION SHALL BE PROVIDED
 WITH A SOURCE CAPTURE SYSTEM CAPABLE OF EXHAUSTING NOT
 LESS THAN 50 CFM PER STATION.
  
 SECTION 403.2.1 RECIRCULATION OF AIR.
 THE OUTDOOR AIR REQUIRED BY SECTION 403.3 SHALL NOT BE
 RECIRCULATED. AIR IN EXCESS OF THAT REQUIRED BY SECTION
 403.3 SHALL NOT BE PROHIBITED FROM BEING RECIRCULATED
 AS A COMPONENT OF SUPPLY AIR TO BUILDING SPACES, EXCEPT
 THAT:
 1. VENTILATION AIR SHALL NOT BE RECIRCULATED FROM ONE
 DWELLING TO ANOTHER OR TO DISSIMILAR OCCUPANCIES.
 2. SUPPLY AIR TO A SWIMMING POOL AND ASSOCIATED DECK
 AREAS SHALL NOT BE RECIRCULATED UNLESS SUCH AIR IS
 DEHUMIDIFIED TO MAINTAIN THE RELATIVE HUMIDITY OF THE
 AREA AT 60 PERCENT OR LESS. AIR FROM THIS AREA SHALL
 NOT BE RECIRCULATED TO OTHER SPACES WHERE MORE THAN 10
 PERCENT OF THE RESULTING SUPPLY AIRSTREAM CONSISTS OF
 AIR RECIRCULATED FROM THESE SPACES.
 3. WHERE MECHANICAL EXHAUST IS REQUIRED BY NOTE B IN
 TABLE 403.3, RECIRCULATION OF AIR FROM SUCH SPACES
 SHALL BE PROHIBITED. ALL AIR SUPPLIED TO SUCH SPACES
 SHALL BE EXHAUSTED, INCLUDING ANY AIR IN EXCESS OF THAT
 REQUIRED BY TABLE 403.3.
 4. WHERE MECHANICAL EXHAUST IS REQUIRED BY NOTE G IN
 TABLE 403.3, MECHANICAL EXHAUST IS REQUIRED AND
 RECIRCULATION IS PROHIBITED WHERE MORE THAN 10 PERCENT
 OF THE RESULTING SUPPLY AIRSTREAM CONSISTS OF AIR
 RECIRCULATED FROM THESE SPACE
  
 PLEASE NOTE THAT ITEM 3 PRINTED ABOVE IS APPLICABLE TO
 NAIL SALON SYSTEMS- PROVIDE AN EXHAUST SYSTEM THAT IS
 IN COMPLIANCE.
  
 2) PLEASE REVIEW SECTION C403.2.6 AND TABLE C403.2.6
 FBC-14 ENERGY CONSERVATION AND SHOW COMPLIANCE AS
 APPLICABLE TO THE REQUIRED MAKEUP AIR FOR THE EXHAUST
 SYSTEM(S).
 3) THE SUBMITTED ENERGY COMPLIANCE FORM 506-2010 IS
 OUTDATED FOR THE NEW 2014 FLORIDA BUILDING CODE CYCLE.
 PLEASE UPDATE THE SOFTWARE AND SUBMIT A VALID UP TO
 DATE PRINTOUT.
  
 AS THE SUBMITTED PLANS ARE INCOMPLETE, A THOROUGH
 REVIEW CANNOT BE ACCOMPLISHED AT THIS TIME.
 PLEASE NOTE THAT ADDITIONAL COMMENTS MAY FOLLOW AFTER
 THE REVISED PLANS HAVE BEEN SUBMITTED FOR REVIEW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-08-20 Cont ID  
Sent By tklarge Date 2015-08-20 Time 09:30 Rev Time 0.00
Received By tklarge Date 2015-08-20 Time 05:39 Sent To  
Notes
2015-08-20 09:30:451) SHT.A-1 - A FRACTIONAL NUMBER OF OCCUPANTS SHALL BE
 ROUNDED UP TO THE NEXT WHOLE NUMBER , NOT DOWN.
 THEREFORE, THE OCCUPANT LOAD SHALL BE 18, NOT 17.
 2) THIS IS A CHANGE OF OCCUPANCY CLASSIFICATION. TWO
 TOILET ROOMS ARE REQUIRED (ONE FOR MALES & ONE FOR
 FEMALES) PER THE 2014 FBC-EXISTING BUILDING CODE
 SEC.1010.1 AND 2014 PLUMBING CODE TABLE 403.1.
 3) A SERVICE SINK IS REQUIRED PER 2014 FBC-PLUMBING
 TABLE 403.1.
 4) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER
 TABLE 403.1 AND FOOTNOTE ( E) OF FBC-PLUMBING AND SEC.
 211.2. OF THE 22014 FBC-ACCESSIBILITY. SHOW THE
 LOCATION OF THE DRINKING FOUNTAINS ON THE PLAN AND THE
 CLEAR FLOOR SPACE PER FBC-ACCESSIBILITY SEC. SEC.602.2.
 5) SUBMIT MANUF. SPECIFICATIONS FOR THE PEDICURE
 CHAIRS. WPB AMEND. TO FBC SEC. 107.2.1.
 6) THE VENT FOR THE PEDICURE CHAIRS IS NOT TO CODE. THE
 VENT SHALL CONNECT TO THE HORIZONTAL DRAIN ABOVE THE
 CENTERLINE OF THE HORIZONTAL DRAIN PIPE PER 2014 FBC
 PLUMBING SEC.905.3.FLAT,DRY VENTS ARE NOT PERMITTED.
 7) THE SANITARY DRAINAGE TO THE PEDICURE SINKS DOES NOT
 MEET CODE AS DRAWN. CONSIDER PIPING THIS AS A CIRCUIT
 VENTING SYSTEM IN ACCORDANCE WITH 2014 FBC-PLUMBING.
 8) SHOW THE CONNECCTION POINT OF THE TO THE POINT OF
 SERVICE FOR THE POTABLE WATER LINE ON THE WATER RISER.
 WPB AMEND. TO 2014 FBC SEC. 107.2.1.
 9) CLEANOUTS ARE REQUIRED IN THE STACKS PER FPC SEC.
 708.3.4.
 10) SHOW PROVISIONS FOR THERMAL EXPANSION IN ACCORDANCE
 WITH FPC SEC. 607.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  