Plan Review Details - Permit 15080079
Plan Review Stops For Permit 15080079
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-23 Cont ID  
Sent By jwitmer Date 2015-09-23 Time 08:24 Rev Time 0.00
Received By jwitmer Date 2015-09-23 Time 07:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-14 Cont ID  
Sent By jwitmer Date 2015-08-14 Time 07:29 Rev Time  
Received By jwitmer Date 2015-08-14 Time 06:31 Sent To  
Notes
2015-08-14 07:26:25BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080079
 ADD: 5402 EAST AVENUE
 CONT: STUART & SHELBY
 TEL: (561)637-7902
 E-MAIL:[email protected]
  
 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. AUGUST 14/ 2015
 ACTION: DENIED
  
 1) ARCHITECTURAL PLANS BY RICHARD WENSING ARCHITECT ARE
 COPIES AND REDUCED IN SIZE. PLANS ARE COPYERIGHTED.
  
 1A)PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G16.003 ARCHITECTS.
  
 1B) 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO
 ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE
 SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY,
 OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
 ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE
 REQUIREMENTS OF FLORIDA STATUTES.
  
 2)107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS:
 OCCUPANCY TYPE
 MINIMUM BUILDING TYPE
 FIRE SPREINKLERED OR NOT
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 AND OR CEILINGS MORE THAN 1STORY?
  
 3) NOTE # 3 SCOPE OF WORK NOTE # 3 INDICATES THE
 REMOVAL OF ACOUSTICAL CEILINGS AND THEN FRAMING IN NEW
 AND HANGING DRYWALL CEILINGS AS REQUIRED BY CODE. NO
 PLANS WERE SUPPLIED TO BE ABLE TO COMPLETE A REVIEW
 WITH. NO MATERIALS, SPANS, NO INFORMATION. 107.3.5.1.1
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. 2014 FBC-B
 TABLE 2508.1 ASTM C754; ASTM C1007, GA 216 & ASTM C840.
 PLANS WILL NEED TO IDENTIFY THE DEFLECTION LIMITATION,
 ALLOWABLE CEILING SPAN FOR TYPE OF FRAMING MEMBER,
 IDENTIFY FRAMING MEMBERS, WILL THEY NEED STIFF BACKS,
 GAUGE OF FRAMING MEMBERS, CENTERS OF FRAMING MEMBERS,
 THE THICKNESS OF DRYWALL, ATTACHMENT, TYPE OF FASTENER,
 SPACING, GAUGE OF FASTENER AND LENGTH OF FASTENER.
  
 NOTE DEPENDING ON THE A/C DUCTWORK LAYOUT, MAY REQUIRE
 FIRE DAMPERS AND ACCESSIBLE PANELS.
  
 4) NOTE # 4 ADD ADDITIONAL STUDS TO SHOWER AREAS AS
 REQUIRED BY CODE. PLEASE PROVIDE THE SPACING OF STUDS,
 TYPE OF MATERIALS USED, FOR TYPE OF BUILDING,
 AND COMPLIANCE WITH 2014 FBC-B 2509.2 BASE FOR TILE.
 NOTE: 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, SUCH
 INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 5) NOTE # 5. HHANG DEN-SHIED OR EQUAL. 2014 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION, SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 6) NOTE # 9 INDICATES INSULATE FRAMED CEILING SPACES OF
 GUEST ROOMS WITH R-30 BATT MATERIALS. PLEASE SHOW
 COMPLIANCE WITH 2014 FBC-ENERGY C402.4.9.2 UNVENTED
 DROPPED CEILING CAVITIES.
 WHERE UNVENTED DROPPED CEILING CAVITIES OCCUR OVER
 CONDITIONED SPACES THAT DO NOT HAVE AN AIR BARRIER
 BETWEEN THE CONDITIONED AND UNCONDITIONED SPACE (SUCH
 AS T-BAR CEILINGS), THEY SHALL BE COMPLETELY SEALED
 FROM THE EXTERIOR ENVIRONMENT (AT THE ROOF PLANE) AND
 ADJACENT SPACES BY A CONTINUOUS AIR BARRIER THAT IS
 ALSO SEALED TO THE AIR BARRIER OF THE WALLS. IN THAT
 CASE, THE ROOF ASSEMBLY SHALL CONSTITUTE BOTH THE UPPER
 THERMAL ENVELOPE AND PRESSURE ENVELOPE OF THE BUILDING.
  
  
 6) NOTE # 12 INDICATE TO INSTALL EXIT AND EMERGENCY
 LIGHTING AS REQUIRED. PLEASE PROVIDE A LIFE SAFETY
 PLAN.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS:
 OCCUPANCY TYPE
 MINIMUM BUILDING TYPE
 FIRE SPREINKLERED OR NOT
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 EMERGENCY LIGHTING
 DERECTIONAL EXIT LIGHTS
 EXIT LIGHTS
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-09-23 Cont ID  
Sent By skennedy Date 2015-09-23 Time 10:07 Rev Time 0.00
Received By skennedy Date 2015-09-23 Time 10:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-09-10 Cont ID  
Sent By skennedy Date 2015-09-10 Time 15:06 Rev Time 0.00
Received By skennedy Date 2015-09-10 Time 15:06 Sent To  
Notes
2015-09-10 15:08:131ST REVIEW: FBC 2014 5TH ED. NEC 2011
  
 PLANS DO NOT MEET MINIMUM SUBMITTAL REQUIREMENTS:
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES& 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES& 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL, AND MAY REQUIRE ONLY ONE SET OF
 SUBMITTALS
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-14 Cont ID  
Sent By pleduc Date 2015-09-14 Time   Rev Time 0.00
Received By pleduc Date 2015-09-14 Time 13:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-08-17 Cont ID  
Sent By pleduc Date 2015-08-17 Time   Rev Time 0.00
Received By pleduc Date 2015-08-17 Time 14:52 Sent To  
Notes
2015-08-17 14:57:37THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS INSUFFICIENT DETAIL TO REVIEW AND/OR
 APPROVE THIS PROJECT.
  
 2) ALL CONSTRUCTION SHALL COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE, 5TH EDITION.
  
 3) REVIEW BUILDING COMMENTS AND RESUBMIT.
  
 4) BASED ON THE ABOVE ADDITIONAL COMMENTS MAY BE
 GENERATED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-01 Cont ID  
Sent By tklarge Date 2015-10-01 Time 08:38 Rev Time 0.00
Received By tklarge Date 2015-09-29 Time 16:00 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-23 Cont ID  
Sent By skennedy Date 2015-09-23 Time 10:07 Rev Time 0.00
Received By skennedy Date 2015-09-11 Time 14:57 Sent To  
Notes
2015-09-11 14:57:49B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-10 Cont ID  
Sent By skennedy Date 2015-09-10 Time 15:06 Rev Time 0.00
Received By skennedy Date 2015-08-07 Time 15:52 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-08-14 Cont ID  
Sent By jwitmer Date 2015-08-14 Time 07:26 Rev Time 0.00
Received By jwitmer Date 2015-08-14 Time 07:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-09-22 Cont ID  
Sent By ccole Date 2015-09-22 Time 09:30 Rev Time 0.00
Received By ccole Date 2015-09-22 Time 09:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-14 Cont ID  
Sent By ccole Date 2015-08-14 Time 10:15 Rev Time 0.00
Received By ccole Date 2015-08-14 Time 10:15 Sent To  
Notes
2015-08-14 10:18:571ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080079
 8/14/15
  
 1) THE SUBMITTED PLANS ARE NOT ACCEPTABLE: PLEASE
 REVIEW BUILDING PLAN REVIEW COMMENTS BY JWITMER-
 8/14/15, AND PROVIDE COMPREHENSIVE PLAN SETS SIGNED AND
 SEALED BY THE DESIGN PROFESSIONAL OF RECORD.
 2) THE REVISED PLANS SHALL INCLUDE MECHANICAL
 DEMOLITION AND MECHANICAL LAYOUT PLANS, DETAILS AND
 SPECIFICATIONS FOR A COMPLETE REVIEW.
 3) DESIGN CRITERIA: THE PROPOSED PROJECT SHALL BE IN
 COMPLIANCE WITH THE FBC-14 FLORIDA EXISTING BUILDING
 CODE. PLEASE PROVIDE THE LEVEL OF ALTERATION ON THE
 PLANS ALONG WITH A LIST OF CURRENT CODES AND STANDARDS
 USED IN THE DESIGN OF THE PROJECT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status N Date 2015-10-01 Cont ID  
Sent By tklarge Date 2015-10-01 Time 08:38 Rev Time 0.00
Received By tklarge Date 2015-10-01 Time 08:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-09-16 Cont ID  
Sent By gjohnson Date 2015-09-16 Time 16:04 Rev Time 0.00
Received By gjohnson Date 2015-09-16 Time 16:04 Sent To  
Notes
2015-09-16 16:17:12PLUMBING COMMENTS:
  
 1.PLAN INDICATES NO PLUMBING WORK BUT ON THE CONTRACT
 SCOPE OF WORK 4. + 5. INDICATE WORK IN SHOWER AND
 BATHROOM ARE YOU REPLACING SHOWER PANS . 8. INDICATES
 PLUMBING WORK PLEASE CLERIFY.
 PER WPB AMEND 107.2.1
 2.DUE TO THE CONFUSION ON THE PLANS A COMPREHENSIVE
 PLUMBING REVIEW CANNOT BE DONE AT THIS TIME. ADDITIONAL
 COMMENTS MAY BE GENERATED ON SUBSEQUENT REVIEWS
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-08-19 Cont ID  
Sent By tklarge Date 2015-08-19 Time 04:47 Rev Time 0.00
Received By tklarge Date 2015-08-19 Time 03:36 Sent To  
Notes
2015-08-19 04:02:011) THE SUBMITTED PLANS ARE COPIES. PER FL. ADMIN. CODE
 RULE 61G1-16.003 -PLANS, DOCUMENTS ETC. SHALL BE SIGNED
 AND SEALED BY THE DESIGN PROFESSIONAL .
 2) THE PLANS SHALL BE DRAWN TO A MINIMUM OF 1/8 INCH
 SCALE PER THE WPB AMEND. TO FBC SEC. 107.2.1.4.
 3) CLEARLY IDENTIFY THE AREAS ON THE PLANS WHERE THE
 REMODEL WORK IS BEING DONE.IS IT THE ENTIRE FLOOR?ARE
 ALL THE SHOWERS BEING REDONE:CLARIFY.
 4) INDICATE THE LEVEL OF WORK/WORK AREA PER
 FBC-EEXISTING BUILDING CODE SEC.501.2.
 5) THE PLANS SHOW A LAUNDRY AREA. WILL THERE BE ANY
 WRORK DONE IN THIS AREA? THERE IS ALSO GAS SHOWN IN
 THIS AREA. ARE THERE ANY CHANGES BEING MADE TO THE GAS
 SYSTEM?
 6) THE CONTRACT REFERS TO TWO SEPARATE BUILDINGS.
 CLEARLY SHOW THIS ON THE PLANS AND THE PERMIT
 APPLICATIONS.
 7) SUBMIT A SANITARY AND WATER RISER DIAGRAM TO REFLECT
 ANY CHANGES BEING MADE TO THE PLUMBING SYSTEM. WPB
 AMEND. TO FBC SEC
 DUE TO THE VAGUE NATURE OF THE PLANS, A COMPREHENSIVE
 REVIEW COULD NOT BE CONDUCTED AT THIS TIME AND
 THEREFORE, ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED ON SUBSEQUENT REVIEWS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  