Plan Review Details - Permit 15080078
Plan Review Stops For Permit 15080078
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-11-05 Cont ID  
Sent By jwitmer Date 2015-11-05 Time   Rev Time 0.00
Received By jwitmer Date 2015-11-05 Time 06:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-29 Cont ID  
Sent By jwitmer Date 2015-09-29 Time 13:46 Rev Time 0.00
Received By jwitmer Date 2015-09-29 Time 13:17 Sent To  
Notes
2015-09-29 13:25:33BUILDING PLAN REVIEW
 W. P. B. PERMIT:15080078
 ADD: 4209 LAKE AVE.
 CONT: BRITE FUTURE PLUMBING
 TEL: (954)577-3651
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2014 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. SEPT. 29/ 2015
 ACTION: DENIED
  
 ) NOTICE!!!!!!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
  
 1) COMPLIED.
  
 2)2ND REQUEST. IN REVIEWING THE PLUMBING COMMENTS AND
 THE PLUMBING PLAN REVIEWER GOING TO THE SITE FOUND WORK
 COMPLETED WITHOUT A PERMIT. PLUMBING COMMENT # 23
 INDICATES ON THE SOUTHEAST CORNER OF THE TENANT SPACE
 THE SOUTH WALL A STOREFRONT DOOR WAS REMOVED AND
 REPLACED WITH A STOREFRONT GLASS PANEL. PALM BEACH
 COUNTY PICTOMETRY/ BING STILL SHOWS A STOREFRONT DOOR
 IN THE LOCATION OF THE NEW STOREFRONT GLASS PANEL.
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (B) WINDOWS
  
 3) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4)2ND REQUEST. PLEASE PROVIDE THE WIND DESIGN CRITERIA:
 2014 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 5-6) COMPLIED.
  
 7) 2ND REVIEW. THE VALUE STATED ON THE PERMIT
 APPLICATION IS EMBARRASSING LOW!!!! PLEASE CORRECT
 VALUE. 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 8) 2ND REVIEW. WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-21 Cont ID  
Sent By jwitmer Date 2015-08-21 Time 12:26 Rev Time 0.00
Received By jwitmer Date 2015-08-21 Time 08:01 Sent To  
Notes
2015-08-21 11:34:43 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT:15080078
 ADD: 4209 LAKE AVE.
 CONT: BRITE FUTURE PLUMBING
 TEL: (954)577-3651
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. AUGUST 21/ 2015
 ACTION: DENIED
  
 1) THE ARCHITECTURAL, MECH. ELEC. & PLUMB. SHEETS SHOW
 THE DESIGNER OF RECORD AS EDWARD J. KRANZ, P. E. #
 49453. NOTE THE PLANS ARE NOT SIGNED NOR SEALED.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 EFFECTIVE DATE 05/06/2009
 (2)(A) EVERY SHEET OF PLANS AND PRINTS WHICH MUST BE
 SEALED UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL
 BE SEALED, SIGNED AND DATED BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.
  
 2) IN REVIEWING THE PLUMBING COMMENTS AND THE PLUMBING
 PLAN REVIEWER GOING TO THE SITE FOUND WORK COMPLETED
 WITHOUT A PERMIT. PLUMBING COMMENT # 23 INDICATES ON
 THE SOUTHEAST CORNER OF THE TENANT SPACE THE SOUTH WALL
 A STOREFRONT DOOR WAS REMOVED AND REPLACED WITH A
 STOREFRONT GLASS PANEL. PALM BEACH COUNTY PICTOMETRY/
 BING STILL SHOWS A STOREFRONT DOOR IN THE LOCATION OF
 THE NEW STOREFRONT GLASS PANEL.
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (B) WINDOWS
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) PLEASE PROVIDE THE WIND DESIGN CRITERIA: 2014 FBC-B
 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF
 ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 5) SHEET M-1 SHOWS DRYER EXHAUST DETAILS WITH A ROOF
 TOP ENCLOSURE BUT HTERE IS NO DESIGN CRITERIA FOR THE
 STRUCTURE HOW IT WILL MEET THE ROOF TOP WIND NOR IS
 THERE INFORMATION AS TO HOW IT WILL BE ANCHORED TO THE
 ROOF FRAMING MEMBERS TO RESIST THE MOMENT OF OVER
 TURNING ? 107.2.1.3. ADDITIONAL INFORMATION IS
 REQUIRED. FBC-B 1609.8 ROOFTOP STRUCTURES AND
 EQUIPMENT.
  
 6) NEITHER THE MECHANICAL OR STRUCTURAL SHEETS SHOW HOW
 THE EXHAUST VENTS ARE TO BE CUT THROUGH THE ROOF AND
 ANCHORED TO RESIST THE MOMENT OF OVER TURNING.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 7) THE VALUE STATED ON THE PERMIT APPLICATION IS
 EMBARRASSING LOW!!!! PLEASE CORRECT VALUE. 108.3*
 BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2015-09-03 Cont ID  
Sent By skennedy Date 2015-09-03 Time 15:14 Rev Time 0.00
Received By skennedy Date 2015-09-03 Time 15:14 Sent To  
Notes
2015-09-03 15:15:32ALL ELECTRICAL WORK SHOWN IS EXISTING.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-22 Cont ID  
Sent By Lindow Date 2015-09-22 Time   Rev Time 0.00
Received By   Date 2015-09-22 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-18 Cont ID  
Sent By Lindow Date 2015-08-18 Time   Rev Time 0.00
Received By rlindow Date 2015-08-18 Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2015-10-22 Cont ID  
Sent By tklarge Date 2015-10-22 Time 07:59 Rev Time 0.00
Received By tklarge Date 2015-10-22 Time 06:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-11-05 Cont ID  
Sent By jwitmer Date 2015-11-05 Time 07:03 Rev Time 0.00
Received By jwitmer Date 2015-10-21 Time 11:47 Sent To  
Notes
2015-10-21 11:47:25SENT TO TKL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-21 Cont ID  
Sent By skennedy Date 2015-10-06 Time 11:04 Rev Time 0.00
Received By skennedy Date 2015-09-15 Time 14:24 Sent To  
Notes
2015-09-15 14:25:00B15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-05 Cont ID  
Sent By tklarge Date 2015-09-05 Time 03:02 Rev Time 0.00
Received By tklarge Date 2015-08-04 Time 11:04 Sent To  
Notes
2015-08-12 13:50:20B02
2015-08-04 11:05:35ROUTED TO PLUMBING $5000 & UNDER
2015-08-04 11:04:39ROUTED TO PLUMBING

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-09-25 Cont ID  
Sent By ccole Date 2015-09-25 Time 12:40 Rev Time 0.00
Received By ccole Date 2015-09-25 Time 12:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-06 Cont ID  
Sent By ccole Date 2015-08-06 Time 12:24 Rev Time 0.00
Received By ccole Date 2015-08-06 Time 12:24 Sent To  
Notes
2015-08-06 13:17:041ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080078
 8/6/15
  
 1) REFER TO SECTION 501 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE THE LEVEL OF ALTERATION ON THE PLAN (1, 2,
 OR 3).
 2) REFER TO SECTION 809.1 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE A VENTILATION CALCULATION IN COMPLIANCE
 WITH TABLE 403.3 FBC--14 MECHANICAL. LAUNDRIES ARE
 REQUIRED TO HAVE FRESH AIR PROVIDED MECHANICALLY AT A
 RATE OF 7.5 CFM PER OCCUPANT AND 0.06 CFM'S PER SQ. FT.
 PROVIDE A TABLE ON THE PLAN SHOWING THE REQUIRED AIR
 AND THE PROVIDED, AND INDICATE HOW THE AIR IS BEING
 PROVIDED- VIA THE EXISTING SYSTEM, MODIFIED SYSTEM, OR
 NEW SYSTEM?
 3) PROVIDE THE MAKE AND MODEL NUMBERS OF THE NEW GAS
 DRYERS ON THE PLAN, AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS REVIEWED
 AND APPROVED BY THE DESIGN PROFESSIONAL OF RECORD-
 REFER TO SECTION 613.1 FBC-14 FUEL GAS.
 4) PLEASE NOTE THAT ADDITIONAL COMMENTS MAY FOLLOW
 AFTER THE DRYER SPECS HAVE BEEN SUBMITTED FOR REVIEW.
 AS STATED BEFORE THE DESIGN PROFESSIONAL OF RECORD
 SHALL REVIEW THE DOCUMENTS, AND VERIFY THAT THE
 EXISTING MAKEUP AIR AND EXHAUST SYSTEMS ARE ADEQUATELY
 SIZED AND MEET THE SPECIFIED CRITERIA FOR USE WITH THE
 NEW DRYERS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-10-22 Cont ID  
Sent By tklarge Date 2015-10-22 Time 06:47 Rev Time 0.00
Received By tklarge Date 2015-10-22 Time 05:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-09-26 Cont ID  
Sent By tklarge Date 2015-09-26 Time 07:53 Rev Time 0.00
Received By tklarge Date 2015-09-26 Time 05:56 Sent To  
Notes
2015-09-26 07:40:301) I AM CHALLENGING THE VALUE OF THE PROJECT. THE COST
 OF THE WASHERS AND DRYERS SHALL BE INCLUDED IN THE
 VALUATION ALONG WITH ALL OTHER NEW EQUIPMENT AND LABOR.
 WPB AMEND. TO FBC SEC. 109.3.SUBMIT A DETAILED,
 QUANTITY ESTIMATE AND/OR BONA FIDE SIGNED CONTRACT FOR
 THE TOTAL COSTOF THIS PROJECT FOR REVIEW. 2ND REQUEST.
 2) CLEARLY IDENTIFY AND SHOW THE LOCATION OF ALL
 STEP-DOWN GAS REGULATORS FOR THE GAS SYSTEM. SINCE THIS
 IS BEING DESIGNED AS A 2 PSI GAS SYSTEM THE GAS PIPING
 SHALL EITHER HAVE STEP-DOWN REGULATORS LOCATED AT EACH
 APPLIANCE OR THE REGULATORS SHALL BE LOCATED TO MEET
 THE GAS CODE FOR PIPE SIZING. THE ONE REGULATOR
 DOWNSTREAM OF THE GAS METER IS NOT SUFFICIENT.THE
 SYMBOLS ON EACH GAS SUPPLY UPSTREAM OF THE GAS COCK ARE
 NOT IDENTIFIED SO IT IS DIFFICULT TO ESTABLISH
 COMPLIANCE WITH THE GAS CODE.2ND REQUEST.
 3) THE WALL AROUND THE DRYERS IN THE SOUTH AREA IS NOT
 AN EXISTING WALL. I SAW IT MYSELF AND IT WAS
 CONSTRUCTED OF NEW METAL STUDS AND DRYWALL. THIS SHALL
 BE INCLUDED IN THE SCOPE OF WORK AND VALUE FOR THIS
 PROJECT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-08-06 Cont ID  
Sent By tklarge Date 2015-08-06 Time 11:40 Rev Time 0.00
Received By tklarge Date 2015-08-06 Time 08:37 Sent To  
Notes
2015-08-06 10:02:131) SHT. A-1 - THE APPLICABLE CODES FOR THIS PROJECT ARE
 THE 5TH EDITION OF THE FLORIDA BUILDING CODE (2014).
 REVISE THE NOTE ON THE PLAN.
 2) SUBMIT THE MANUFACTURER'S SPECIFICATION SHEETS FOR
 THE GAS DRYERS AND A COPY OF THE INSTALLATION
 MANUAL.THE DRYERS SHALL BE LISTED AND LABELED PER THE
 FBC 5TH ED.FUEL GAS CODE SEC. 301.3.
 3) THE PLANS SHALL BE SIGNED AND SEALED BY THE SESIGN
 PROFESSIONAL OF RECORD PER THE FL. ADMIN. CODE
 61G15-23.002.
 4) INDICATE THE LEVEL OF ALTERATION OF THIS PROJECT ON
 THE PLANS IN ACCORDANCE WITH THE 2014 FBC EXISTING
 BUILDING CODE SEC. 301.1, 501.5.
 5) INDICATE THE DISTANCE ABOVE THE ROOF OF THE DRYER
 EXHAUST. THE EXHAUST SHALL COMPLY WITH 2014 FBC-FUEL
 GAS SEC.503.7.3. THE DRYER VENTS APPEAR TO BE SINGLE
 WALL VENTS.
 6) THE PENETRATION OF THE PIPE PASSING THROUGH THE ROOF
 SHALL COMPLY WITH THE 2014 FBC FUEL GAS SEC.503.7.5. IF
 THE EXISTING INSTALLATION IN NOT COMPLIANT IT SHALL BE
 CORRECTED. IF THE ROOF IS CONSTRUCTED OF COMBUSTIBLE
 MATERIAL A NON- COMBUSTIBLE, NON-VENTILATING THIMBLE
 SHALL BE USED.
 7) CLEARANCES OF SINGLE WALL METAL PIPE TO COMBUSTIBLE
 MATERIAL SHALL COMPLY WITH 2014 FBC-FUEL GAS
 SEC.503.7.8 & TABLE 503.10.5.
 8) WHERE TWO OR MORE APPLIANCES ARE CONNECTED TO A
 COMMON VENT, THE VENT SHALL BE SIZED IN ACCORDANCE WITH
 THE FGC SEC. 504.
 9) SEDIMENT TRAPS ARE REQD. ON THE GAS PIPING
 CONNECTIONS TO THE DRYERS PER THE 2014 FGC SEC.408.4.
 10) SHT. M-1 - IDENTIFY THE PIECE OF EQUIPMENT AND ITS
 FUNCTION THAT IS LABELED HCN080KYFX. SUBMIT MANUF.
 SPECIFICATIONS/INSTALL MANUAL. WPB AMEND. TO FBC SEC.
 107.2.1.
 11) WASHING MACHINES AND CLOTHES DRYERS SHALL COMPLY
 WITH THE 2014 FBC-ACCESSIBILITY SECS.309 & 611. SUBMIT
 AN ELEVATION DETAIL SHOWING COMPLIANCE.
 12) THE ARCHITECTURAL AND PLUMBING PLANS SHOW 12
 WASHING MACHINES BUT THERE ARE 14 DRAIN OUTLETS SHOWN
 ON THE PLUMBING RISER.CLARIFY.
 13) SHT. P-2 - THE PLAN REFERS TO THE 2009
 INTERNATIONAL FUEL GAS CODE. THE CODE IN EFFECT IS THE
 5TH EDITION (2014) OF THE FBC. REVISE THE NOTE.
 14) THE GAS TABLE REFERENCED ON SHT. P-2 IS INCORRECT.
 REVISE THE NOTE TO READ THE CORRECT TABLE IN THE 2014
 FUEL GAS CODE.
 15) THE GAS SYSTEM IS UNDERSIZED FOR A SYSTEM THAT IS 2
 PSI WITH A 1.0 PSI DROP. THE GAS MAIN SHALL BE 1 1/2
 INCHES FROM THE OUTLET OF THE GAS METER UP TO THE
 BOILER BRANCH AND CAN REDUCE DOWN TO 1 1/4 INCHES AFTER
 PICKING UP THE BOILER.
 16) SHOW THE LOCATION OF ALL STEP-DOWN REGULATORS FOR
 THE EQUIPMENT ON THE GAS RISER.
 17) THE COMBUSTION AIR CALCULATIONS ON SHT. M-1
 INDICATE THREE EXISTING COMBUSTION AIR DUCTS SIZED 28 X
 38, 40 X 40 & 28 X 28 BUT THE PLANS ONLY SHOW ONE DUCT
 SIZED 72 X 30. IS THE 72 X 30 MAKE UP AIR FOR THE
 VENTILATION SYSTEM OR IS IT FOR COMBUSTION AIR FOR THE
 DRYERS. CLARIFY.
 18) THE COMBUSTION AIR CALCULATION YOU ARE USING TO
 DETERMINE THE REQUIRED AMOUNT OF COMBUSTION AIR FOR THE
 DRYER AREA NORTH IS BASED ON THE USE OF HORIZONTAL
 DUCTS ONLY TO THE OUTDOORS. THE ONLY DUCT SHOWN IS
 PARTIALLY HORIZONTAL AND PARTIALLY VERTICAL. HOW DID
 YOU ARRIVE AT THE USE OF THIS CALCULATION? SHOW THE
 LOCATION OF THE EXISTING COMBUSTION AIR DUCTS AND
 CLEARLY SHOW HOW COMBUSTION AIR IS BEING INTRODUCED
 INTO THE STRUCTURE . WPB AMEND. TO FBC SEC. 107.2.1.
 19) SHT. M-1 - SUBMIT MANUF. SPECS FOR THE FLUE FOR THE
 BOILER. WPB AMEND. TO FBC SEC. 107.3.5.1.5.
 20) SHT. M-1 - THE NOTE AT THE INTAKE AIR HOOD REFERS
 TO RECT.INTAKE HOOD DETAIL. THERE IS NO SUCH DETAIL ON
 THE PLANS. CLARIFY.
 21) SHT. M-1 - IDENTIFY THE DASHED LINE BOXES ON THE
 PLANS. ARE THESE THE MAKE UP AIR DUCTS? IF SO, INDICATE
 WHAT THEY ARE & THE DIMENSIONS OF EACH.
 22) SHT. P-2 - SUBMIT A LEGEND FOR THE KEYNOTES #7, #8,
 #9 & #10 ON THE GAS DRAWING. WPB AMEND. TO FBC SEC.
 107.3.5.1.5.
 23) THERE WAS AN EXISTING STOREFRONT DOOR ON THE SOUTH
 SIDE OF THIS UNIT THAT WAS REMOVED WITHOUT A PERMIT AND
 A STOREFRONT GLASS PANEL WAS INSTALLED IN ITS PLACE
 ALSO WITHOUT A PERMIT. THIS WORK SHALL BE INCLUDED IN
 THIS PERMIT. SUBMIT ALL REQUIRED INFORMATION AND
 DOCUMENTS FOR THIS WORK.
 24) AN NEW INTERIOR WALL WAS CONSTRUCTED AROUND THE
 DRYERS IN THE SOUTH AREA. SUBMIT COMPLETE PLANS FOR THE
 INTERIOR PARTITION.
 25) I AM CHALLENGING THE VALUE OF THE PROJECT. THE COST
 OF THE WASHERS AND DRYERS SHALL BE INCLUDED IN THE
 VALUATION AND ALL OTHER NEW EQUIPMENT AND LABOR. WPB
 AMEND. TO FBC SEC. 109.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-10-06 Cont ID  
Sent By sgraham Date 2015-10-06 Time 15:35 Rev Time 0.00
Received By sgraham Date 2015-10-06 Time 15:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-09-04 Cont ID  
Sent By sgraham Date 2015-09-04 Time 08:56 Rev Time 0.00
Received By sgraham Date 2015-09-04 Time 08:56 Sent To P
Notes
***NONE***