Plan Review Details - Permit 15080059
Plan Review Stops For Permit 15080059
Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-04 Cont ID  
Sent By skennedy Date 2015-08-04 Time 15:31 Rev Time 0.00
Received By skennedy Date 2015-08-04 Time 15:31 Sent To  
Notes
2015-08-04 15:34:591ST REVIEW: FBC 2010/2008 NEC
  
 THE PROVIDED LOAD CALCULATION INDICATES A CALCULATED
 DEMAND OF 222 AMPS YET ONLY A 200AMP PANEL IS PROVIDED.
  
 ALSO PER FBC 107 PROVIDE A PANEL SCHEULE FOR THE 60AMP
 SUB PANEL AND INFORMATION AS TO WHAT IT IS FEEDING.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cpuell Date 2015-12-08 Time 13:59 Sent To  
Notes
2015-12-09 14:00:22GIVEN TO SKENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-04 Cont ID  
Sent By skennedy Date 2015-08-04 Time 15:35 Rev Time 0.00
Received By skennedy Date 2015-08-03 Time 09:10 Sent To  
Notes
2015-08-04 09:11:10REVISION ROUTED TO SKENNEDY

Review Stop P PLUMBING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-08-04 Cont ID  
Sent By skennedy Date 2015-08-04 Time 15:31 Rev Time 0.00
Received By skennedy Date 2015-08-04 Time 15:31 Sent To  
Notes
***NONE***