Plan Review Details - Permit 15080058
| Plan Review Stops For Permit 15080058 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2015-08-07 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-08-07 |
Time |
15:51 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2015-08-07 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2015-08-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-08-07 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-08-06 |
Time |
14:54 |
Sent To |
B |
|
| Notes |
| 2015-08-06 15:15:42 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1. THERE IS INSUFFICIENT DETAIL PROVIDED TO REVIEW OR | | | APPROVE THE PROPOSED PROJECT. | | | | | | 2. PROVIDE A WRITTEN DISCRIPTION OR NOTE OUTLINING THE | | | INTENT OF THE PROJECT. ARE YOU CREATING A SEPARATE | | | OCCUPANCY FOR THE 2ND FLOOR AREA ? | | | | | | 3. PROVIDE ENTIRE BUILDING FOOTPRINT AND FLOORPLAN AND | | | CLOUD THE PROPOSED REVISIONS. | | | | | | 4. THE DOOR AT THE BOTTOM OF THE STAIRWELL SWINGS IN. | | | THIS IS AN EXIT ACCESS DOOR. WHAT IS THE OCCUPANCY LOAD | | | OF THE 2ND FL AREA TO ALLOWING THE DOOR TO SWING | | | AGAINST EGRESS. | | | | | | 5. PROVIDE A DOOR SCHEDUE INCLUDING EXIT HARDWARE. | | | | | | 6. REVIEW EXIT REQUIREMENTS OF NFPA CHAPTER 7 ENSURING | | | COMPLIANCE UPON LEAVING A PROTECTED ENCLOSED STAIRWEL / | | | EXIT PASSAGEWAY NEEDEDL. | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-08-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-08-07 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-08-03 |
Time |
09:02 |
Sent To |
FIRE |
|
| Notes |
|
|
|