Plan Review Details - Permit 15080008
Plan Review Stops For Permit 15080008
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2015-12-21 Cont ID  
Sent By rbrown Date 2015-12-21 Time 13:03 Rev Time 0.00
Received By rbrown Date 2015-12-21 Time 13:02 Sent To  
Notes
2015-12-21 13:05:25PER SYBILLE WELTER, ART IN PUBLIC PLACES (AIPP)
 COORDINATOR, THE THE DEVELOPER HAS SUBMITTED THE
 REQUIRED ART ASSESSMENT APPLICATION INCLUDING ESCROWED
 FUNDS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-09-25 Cont ID  
Sent By shill Date 2015-09-25 Time 17:16 Rev Time 0.00
Received By shill Date 2015-09-25 Time 17:16 Sent To  
Notes
2015-09-25 17:03:16****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PROVISO, FLOOR PLANS NOT REVIEWED AT THIS TIME. WHEN
 SUBMITTING FULL BUILDING PLANS, LIFE SAFETY PLANS TO
 INCLUDE COMPLIANCE WITH FBC 5TH ED. ACCESSIBILITY
 SECTION 207.
  
 PROVISO, PERMIT IS ISSUED AT CONTRACTOR'S RISK (PHASED
 CONSTRUCTION FBC 105.13).
  
 PROVISO, SEPARATE PERMITS REQUIRED FOR LANDSCAPING,
 PARKING LOT STRIPING AND LIGHTING, SIGNS, SEPARATE
 STRUCTURES.
  
 PROVISO, ON THE PLAN, REFERENCE IS MADE TO EIFS AND
 POLYSTYRENE. NOTE THAT THIS IS A TYPE II NONCOMBUSTIBLE
 BUILDING AND ALL MATERIALS WILL BE IN COMPLIANCE WITH
 FBC 602.2, 603. ANY EXCEPTIONS SHOULD BE INCORPORATED
 INTO THE PLAN (WHEN BUILDING PLANS ARE SUBMITTED).
  
 PROVISO, STAIRS NOT INCLUDED IN SCOPE. STRUCTURAL
 SHEETS WERE SUBMITTED 2ND REVIEW BUT DIMENSIONS TO SHOW
 COMPLIANCE WITH FBC 1009 WERE NOT PROVIDED. CONTRACTOR
 MAY SUBMIT A REVISION TO INCORPORATE THIS INTO SCOPE.
  
 PROVISO, POLYSTYRENE IS SPECIFIED (SEE DETAIL 7 S415
 AND OTHER LOCATIONS). PER ARCHITECT, THIS IS NOT
 INCLUDED IN THE SCOPE OF THIS PERMIT. FBC 602, 603
 PROVIDE PRODUCT DATA REGARDING COMBUSTIBILITY WHEN
 SUBMITTING THE FULL BUILDING PERMIT.
  
 PROVISO, SPECIFICATION PACKAGE NOT REVIEWED. PLANS ARE
 TO DEMONSTRATE CODE COMPLIANCE INDEPENDENTLY OF THIS
 DOCUMENT.
  
 PROVISO, BUILDING TYPE IIA REQUIRES 1 HR STRUCTURAL
 FRAME; COMPLIANCE WITH FBC 704 REQUIRED.
  
 ADVISORY ONLY, PRODUCT APPROVALS WILL BE REQUIRED FOR
 COMPONENTS AND CLADDING. THEY ARE REQUIRED TO BE
 SUBMITTED, AFTER DESIGNER OF RECORD REVIEW, PRIOR TO
 INSTALLATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-22 Cont ID  
Sent By shill Date 2015-09-22 Time 17:47 Rev Time 0.00
Received By shill Date 2015-09-22 Time 17:47 Sent To  
Notes
2015-09-22 17:48:08****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PROVISO, FLOOR PLANS NOT REVIEWED AT THIS TIME.
  
 PROVISO, PERMIT IS ISSUED AT CONTRACTOR'S RISK (PHASED
 CONSTRUCTION FBC 105.13).
  
 PROVISO, SEPARATE PERMITS REQUIRED FOR LANDSCAPING,
 PARKING LOT STRIPING AND LIGHTING, SIGNS, SEPARATE
 STRUCTURES.
  
 PROVISO, ON THE PLAN, REFERENCE IS MADE TO EIFS AND
 POLYSTYRENE. NOTE THAT THIS IS A TYPE II NONCOMBUSTIBLE
 BUILDING AND ALL MATERIALS WILL BE IN COMPLIANCE WITH
 FBC 602.2, 603. ANY EXCEPTIONS SHOULD BE INCORPORATED
 INTO THE PLAN (WHEN BUILDING PLANS ARE SUBMITTED).
  
 PROVISO, STAIRS NOT INCLUDED IN SCOPE. STRUCTURAL
 SHEETS WERE SUBMITTED 2ND REVIEW BUT DIMENSIONS TO SHOW
 COMPLIANCE WITH FBC 1009 WERE NOT PROVIDED. SUBMIT A
 REVISION TO INCORPORATE THIS INTO SCOPE.
  
 PROVISO, POLYSTYRENE IS SPECIFIED (SEE DETAIL 7 S415
 AND OTHER LOCATIONS). PER ARCHITECT, THIS IS NOT
 INCLUDED IN THE SCOPE OF THIS PERMIT. FBC 602, 603
 PROVIDE PRODUCT DATA REGARDING COMBUSTIBILITY WHEN
 SUBMITTING THE FULL BUILDING PERMIT.
  
 PROVISO, SPECIFICATION PACKAGE NOT REVIEWED. PLANS ARE
 TO DEMONSTRATE CODE COMPLIANCE INDEPENDENTLY OF THIS
 DOCUMENT.
  
 ADVISORY ONLY, PRODUCT APPROVALS WILL BE REQUIRED FOR
 COMPONENTS AND CLADDING. THEY ARE REQUIRED TO BE
 SUBMITTED, AFTER DESIGNER OF RECORD REVIEW, PRIOR TO
 INSTALLATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-19 Cont ID  
Sent By shill Date 2015-08-19 Time 10:40 Rev Time 0.00
Received By shill Date 2015-08-18 Time 07:09 Sent To  
Notes
2015-08-19 09:33:14****CORRECTIONS****
 REVISED 8/28/15
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE THRESHOLD REVIEW. THRESHOLD INSPECTION PLAN AND
 OTHER REQUESTED DOCUMENTS ARE TO BE APPROVED PRIOR TO
 PERMIT ISSUANCE.
  
 ALL PLANS PROVIDED BY ARCHITECT AND ENGINEER(S) ARE TO
 INCLUDE THE STATEMENT PER FLORIDA STATUTE 553.79(7)(D):
  
 THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT CONSISTENT WITH
 THE FLORIDA STATUTE REQUIREMENT FS 553.79(7)(D):
 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS CHAPTER AND CHAPTER 633.
  
 2. SEE IMPACT REVIEW. BEFORE A PERMIT TO CONSTRUCT MAY
 BE ISSUED, AN IMPACT FEE ASSESSMENT BY PALM BEACH
 COUNTY IS REQUIRED. THE ACTUAL PERMIT SET OF PLANS MUST
 BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID
 PROVIDED. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3. SEE FS471, FS 481. A CERTIFICATE OF AUTHORIZATION IS
 REQUIRED TO PRACTICE ARCHITECTURE OR ENGINEERING
 THROUGH A COMPANY.
  
 COMMENT FOR ALL DESIGN PROFESSIONALS EXCEPT KIMLEY HORN
 AND CODE CONSULTANTS; THE CERTIFICATE OF AUTHORIZATION
 IS TO BE ON EACH SHEET (INCORPORATED INTO THE TITLE
 BLOCK), FAC61G15 23.002, FS471, FS481.
  
 COMMENT FOR HOBBS & BLACK; SEND LICENSE NUMBER WHEN
 AVAILABLE (SEE PROVISO).
  
 COMMENT FOR E&S CONSTRUCTION ENGINEERING (PLUMBING
 ENGINEER), SEND LICENSE NUMBER WHEN AVAILABLE (SEE
 PROVISO).
  
 THIS COMMENT WAS SENT TO WHITING TURNER AND RH VIA
 EMAIL ON 8.19.15.
  
 4. AT THE LOCATION OF THE SEAL, ALL SHEETS, THIS AREA
 IS NOTED ON THE PLAN AS A CONSULTANT. PLEASE REMOVE
 THIS LANGUAGE AS IT APPEARS THAT THE PLANS PROVIDED
 HAVE BEEN DESIGNED BY THE DESIGN PROFESSIONALS TAKING
 RESPONSIBILITY FOR THE PLANS, FS471, FS481. OR, CLARIFY
 USE OF THE WORD CONSULTANT ON THE PLANS AS APPLICABLE
 TO THIS STRUCTURE.
  
 5. GOVERNING CODE CHANGED TO FLORIDA BUILDING CODE 5TH
 EDITION (OR FBC 2014) ON JUNE 31, 2015; REVISE BUILDING
 CODE DATA (SHEET A003), STRUCTURAL CALCS, S002, AND
 OTHER SHEETS AS APPLICABLE. SHEET S102, NOTES INCLUDES
 REFERENCES TO FBC 2012, PLEASE REVISE.
  
 6. FOR A FOUNDATION PERMIT, ENOUGH INFORMATION TO
 DEMONSTRATE CODE COMPLIANCE REGARDING THE PROPOSED
 BUILDING IS REQUIRED. A003 IS NOTED FOR REFERENCE ONLY,
 BUT THIS SHEET IS REQUIRED, FBC TABLE 503. A050 SHOWS
 THE LOCATION OF THE PROPOSED CONSTRUCTION IN RELATION
 TO THE LOT LINES, FBC TABLE 602. THESE TWO SHEETS ARE
 REQUIRED FOR A FOUNDATION AND STRUCTURE PERMIT.
  
 7. SEE STRUCTURAL CALCS. THIS DOCUMENT REFERENCES ACI
 318 08; THE STANDARD SHOULD BE ACI 318 11. AISC 360
 SHOULD REFERENCE 2010 (NOT 2005), SEE FBC CHAPTER 35.
 REVISE ANY OTHER STANDARDS AS APPLICABLE.
  
 8. REVISED TO BE A PROVISO ITEM (POLYSTYRENE NOT
 INCLUDED IN SCOPE OF THIS PERMIT).
  
 PROVISO ITEMS (INFORMATIONAL OR TO BE ADDRESSED AT A
 FUTURE DATE)
  
 PROVISO, FLOOR PLANS NOT REVIEWED AT THIS TIME.
  
 PROVISO, PERMIT IS ISSUED AT CONTRACTOR'S RISK (PHASED
 CONSTRUCTION FBC 105.13).
  
 PROVISO, SEPARATE PERMITS REQUIRED FOR LANDSCAPING,
 PARKING LOT STRIPING AND LIGHTING, SIGNS, SEPARATE
 STRUCTURES.
  
 PROVISO, ON THE PLAN, REFERENCE IS MADE TO EIFS AND
 POLYSTYRENE. NOTE THAT THIS IS A TYPE II NONCOMBUSTIBLE
 BUILDING AND ALL MATERIALS WILL BE IN COMPLIANCE WITH
 FBC 602.2, 603. ANY EXCEPTIONS SHOULD BE INCORPORATED
 INTO THE PLAN (WHEN BUILDING PLANS ARE SUBMITTED).
  
 PROVISO, PROVIDE ARCHITECT BUSINESS LICENSE NUMBER WHEN
 AVAILABLE; ISSUED AT CONTRACTOR'S RISK AND REQUIRED
 PRIOR TO C.O.
 PROVISO, PROVIDE PLUMBING ENGINEER'S BUSINESS LICENSE
 NUMBER WHEN AVAILABLE; ISSUED AT CONTRACTOR'S RISK AND
 REQUIRED PRIOR TO C.O.
  
 PROVISO, POLYSTYRENE IS SPECIFIED (SEE DETAIL 7 S415
 AND OTHER LOCATIONS). PER ARCHITECT, THIS IS NOT
 INCLUDED IN THE SCOPE OF THIS PERMIT. FBC 602, 603
 PROVIDE PRODUCT DATA REGARDING COMBUSTIBILITY WHEN
 SUBMITTING THE FULL BUILDING PERMIT.
  
 ADVISORY ONLY, PRODUCT APPROVALS WILL BE REQUIRED FOR
 COMPONENTS AND CLADDING. THEY ARE REQUIRED TO BE
 SUBMITTED, AFTER DESIGNER OF RECORD REVIEW, PRIOR TO
 INSTALLATION.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-09-21 Cont ID  
Sent By skennedy Date 2015-09-21 Time 13:07 Rev Time 0.00
Received By skennedy Date 2015-09-21 Time 13:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-09-01 Cont ID  
Sent By skennedy Date 2015-09-01 Time 15:34 Rev Time 0.00
Received By skennedy Date 2015-09-01 Time 15:34 Sent To  
Notes
2015-09-01 15:37:35CODE: 2011 EDITION OF THE NEC, 2014/5TH EDITION OF THE
 FBC
 1ST ELECTRICAL PLAN REVIEW FOUNDATION ONLY
 ACTION: DENIED
  
 THERE ARE INSUFFICIENT ELECTRICAL PLANS OR
 SPECIFICATIONS INCLUDED WITH THIS SUBMITTAL. REVISE
 YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) AS A FOUNDATION ONLY REVIEW THE MINIMUM PLAN REVIEW
 CRITERIA SHALL INCLUDE BUT NOT BE LIMITED TO AN
 ELECTRICAL GOUNDING ELECTRODE SYSTEM DESIGN DETAIL PER
 THE NEC ARTICLE 250. SEE NEC 250.30(7) AND 250.50 AND
 250.52
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-09-02 Cont ID  
Sent By cranford Date 2015-09-02 Time 09:49 Rev Time 0.00
Received By cranford Date 2015-09-02 Time 09:22 Sent To  
Notes
2015-09-02 09:49:31LAND STABILIZATION AND EROSION CONTROL BONDS RECEIVED
 AND IN EDS SAFE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-12 Cont ID  
Sent By wjolin Date 2015-08-12 Time 14:37 Rev Time 0.00
Received By wjolin Date 2015-08-12 Time 13:24 Sent To  
Notes
2015-08-12 13:52:12560 OKEECHOBEE BOULEVARD
 PERMIT #15080008
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **PERMIT FOR STRUCTURAL SHELL ONLY - SEPARATE PERMIT
 NEEDED FOR INTERIOR DESIGN**
  
  
 SHEET C3.00: RELOCATE THE NEW FIRE HYDRANT AND FIRE
 DEPARTMENT CONNECTION TO THE NEW FIRE LANE EAST OF THE
 BUILDING.
  
 SHEET C5.00 & FP-101: PER NFPA 24 SECTION 6.2.1, ALL
 CONNECTIONS TO PRIVATE FIRE SERVICE MAINS FOR FIRE
 PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH
 ONE OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 CONSTRUCTION TRAILERS: TEMPORARY CONSTRUCTION TRAILERS
 OR MODULAR BUILDINGS WILL REQUIRE A PERMIT AND
 COMPLIANCE WITH THE FOLLOWING:
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-29 Cont ID  
Sent By lmarchan Date 2015-09-29 Time 10:49 Rev Time 0.00
Received By lmarchan Date 2015-09-17 Time 13:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-08 Cont ID  
Sent By shill Date 2015-09-08 Time 07:43 Rev Time 0.00
Received By shill Date 2015-08-07 Time 15:04 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-10-01 Cont ID  
Sent By shill Date 2015-10-01 Time 11:54 Rev Time 0.00
Received By shill Date 2015-10-01 Time 11:54 Sent To  
Notes
2015-10-01 11:55:31MU 201519031 PAID 51,593 SF
 PLAN HAS BEEN REVISED TO 52,300 SF. PER WILLIE SWOPE,
 THE IMPACT FEE RE-ASSESSMENT CAN BE DONE PRIOR TO
 ISSUANCE OF BUILDING PERMIT. OK TO ISSUE
 FOUNDATION/SUPERSTRUCTURE PERMIT AT THIS TIME
  
 PER EMAIL 10/1/15
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-09-22 Cont ID  
Sent By shill Date 2015-09-22 Time 12:14 Rev Time 0.00
Received By shill Date 2015-09-09 Time 09:20 Sent To  
Notes
2015-09-22 12:14:33MU-2015-019031-0000
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-08-19 Cont ID  
Sent By shill Date 2015-08-19 Time 10:39 Rev Time 0.00
Received By shill Date 2015-08-19 Time 10:39 Sent To  
Notes
2015-08-19 10:40:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE ISSUED, AN IMPACT
 FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID PROVIDED. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 THIS CAN BE DONE AT ANY POINT IN THE PLAN REVIEW
 PROCESS.
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-09-29 Cont ID  
Sent By tklarge Date 2015-09-29 Time 10:47 Rev Time 0.00
Received By tklarge Date 2015-09-29 Time 04:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-08-26 Cont ID  
Sent By tklarge Date 2015-08-26 Time 06:49 Rev Time 0.00
Received By tklarge Date 2015-08-19 Time 05:01 Sent To  
Notes
2015-08-24 09:27:111) SHT. 003 A-003 - SUBMIT THE OCCUPANT LOAD FOR EACH
 FLOOR IN ACCORDANCE WITH TABLE 1004.1.2 OF THE 2014
 FBC-BUILDING.
 2) SHT.003 A-003 - APPLICABLE CODES BOX - THE PLAN
 REFERS TO THE 2010 FBC AND OTHER CODE REFERENCES (2009
 PLUMBING CODE, 2008 NEC, ETC.). THIS PLAN FALLS UNDER
 THE 2014 (5TH EDITION) OF THE FBC. REVISE THE NOTES TO
 REFLECT THE CURRENT CODE APPLICABLE TTO THIS PROJECT.
 3) SHT.008 A-050 - THE FOUNTAINS SHALL BE UNDER A
 SEPARATE PERMIT. A SEPARATE PERMIT APPLICATION AND
 PLANS SHALL BE SUBMITTED FOR REVIEW AND APPROVAL. WPB
 AMEND. TO FBC SEC. 105.1.
 4) THERE ARE SHEETS IN THIS SUBMITTAL PACKAGE THAT ARE
 MARKED "FOR REFERENCE ONLY" AND ALSO "NOT FOR
 CONSTRUCTION". CLARIFY.
 5) THE PLANS SHOW SANITARY FACILITIES LOCATED ON THE
 FIRST AND FOURTH LEVELS. THIS DOES NOT COMPLY WITH 2014
 FBC-PLUMBING SEC.403.3.3.THE REQUIRED PUBLIC AND
 EMPLOYEE TOILET FACILITIES SHALL BE LOCATED NOT MORE
 THAN ONE STORY ABOVE OR BELOW THE SPACE REQUIRED TO BE
 PROVIDED WITH TOILET FACILITIES, AND THE PATH OF TRAVEL
 TO SUCH FACILITIES SHALL NOT EXCEED A DISTANCE OF 500
 FEET.
 6) SHT.013 A-105 - SUBMIT A ROOF DRAINAGE RISER DIAGRAM
 AND STORM DRAINAGE CALCULATIONS. THE CALCULATIONS SHALL
 INCLUDE ONE-HALF THE AREA OF ANY VERTICAL WALL THAT
 DIVERTS RAINWATER TO THE ROOF AND ALSO ANY SLOPED ROOF
 THAT DIVERTS RAINWATER TO A FLAT ROOF. 2014
 FBC-PLUMBING SEC.1106.4.ALSO, SUBMIT A SECTION DETAIL
 OF THE ROOF GUTTER. GUTTERS SHALL BE SIZED PER TABLE
 1106.6.
 7) SHT.012 A-104 - SUBMIT A DETAIL FOR THE ROOF DRAINS
 AND THE OVERFLOW DRAINS WPB AMEND. TO FBC SEC. 107.2.1.
 8) SHT.161 P-100 - 5" HORIZONTAL STORM DRAIN AT GRID
 LINE B-3 IS SHOWN AS DRAINING AN AREA OF 2780 SQ.
 FT.THE MAXIMUM SQUARE FOOTAGE THAT CAN BE DRAINED BY A
 5" HORIZONTAL LINE IS 2672 SQ. FT. COMPLY WITH TABLE
 1106.3.
 9) SHT.161 P-100 - 4" STORMWATER RISER NEAR GRID LINE
 B-5 IS SHOWN DRAINING 4090 SQ. FT.AND THE MAXIMUM
 SQUARE FOOTAGE PER TABLE 1106.2 (1) IS 3680 FOR A 4"
 VERTICAL CONDUCTOR.
 10) SHT.161 P-100 - 4" STORMWATER RISER NEAR GRID LINE
 "D" BETWEEN 5 & 6 - IS DRAINING 3770 SQ. FT. - THE
 MAXIMUM SQUARE FOOTAGE THAT CAN BE DRAINED BY A 4"
 VERTICAL LINE IS 3680 SQ. FT.PER TABLE 1106.2 (1).
 11) SHT.161 P-100 - THE PLAN SHOWS A 6" SANITARY LINE
 WITH NO CONTINUATION POINT. SEE GRID LINE "E" BETWEEN 5
 & 6. SEE ALSO 6" LINE BETWEEN GRID LINES D & E AND 5-6.
 12) THE DISCHARGE FROM THE SUMP PUMP SHALL BE
 INDIRECTLY CONNECTED TO THE PLUMBING SYSTEM PER THE
 2014 FBC-PLUMBING AND ALSO COMPLY WITH FPC SEC.1003.4.
 13) SHOW THE LOCATION OF THE GREASE TRAPS ON THE
 ARCHITECTURAL SITE PLAN.WPB AMEND. TO FBC SEC. 107.2.1.
 14) SUBMIT GREASE TRAP CALCULATIONS IN ACCORDANCE WITH
 2014 FBC-PLUMBING SEC.1003.3.4.
 15) INDICATE CONTINUATION POINT OF 14" SW & 6" SANITARY
 AT GRIDLINE "E" BETWEEN 4-5.
 16) DETAILS ON REMOTE ALARM TO BE SUBMITTED IN BUILDOUT
 PLANS.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-09-29 Cont ID  
Sent By lmarchan Date 2015-09-29 Time 14:35 Rev Time 0.00
Received By lmarchan Date 2015-09-29 Time 14:35 Sent To  
Notes
2015-09-29 14:35:35DIGITAL SIGNATURES APPROVED PER SKENNEDY, PLANS
 DIGITALLY SIGNED AND SEALED.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2015-09-28 Cont ID  
Sent By kconrad Date 2015-09-28 Time 11:43 Rev Time 0.00
Received By kconrad Date 2015-09-28 Time 11:43 Sent To I
Notes
2015-09-28 11:45:43PROVISO:
  
  
 PLEASE SUBMIT RESUME AND SIGNED SPECIAL INSPECTOR
 AGREEMENT FOR A SECONDARY BUILDING INSPECTOR FOR THE
 PROJECT.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2015-09-29 Cont ID  
Sent By shill Date 2015-09-29 Time 10:12 Rev Time 0.00
Received By shill Date 2015-09-19 Time 14:41 Sent To  
Notes
2015-09-29 10:14:22OK W/PROVISO
 PER KEN CONRAD
 AT LEAST ONE ADDITIONAL INSPECTOR REQUIRED IN THE EVENT
 THAT THE PRIMARY INSPECTOR IS UNAVAILABLE
 SUBMIT FOR APPROVAL
  
  
  
2015-09-19 14:54:55SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PENDING APPROVAL FROM KEN CONRAD
  
 TWO SETS OF THE THRESHOLD DOCUMENTS HAVE BEEN ROUTED TO
 KEN CONRAD FOR FINAL APPROVAL.
 ONE SET ON SH DESK
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2015-08-19 Cont ID  
Sent By shill Date 2015-08-19 Time 09:03 Rev Time 0.00
Received By shill Date 2015-08-19 Time 09:03 Sent To  
Notes
2015-08-19 09:18:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. A COPY OF THE SPECIAL INSPECTOR AGREEMENT AND POLICY
 WERE SENT VIA EMAIL TO JUSTIN MENENDEZ AND HENRY SHAWAH
 AT WHITING-TURNER.
  
 1A) THRESHOLD INSPECTION PLAN HAS BEEN FORWARDED TO KEN
 CONRAD FOR REVIEW. 109.3.6.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM STRUCTURAL
 INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A
 (WRITTEN/ TYPED) STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE INSPECTION COMPANY &
 THRESHOLD INSPECTOR WILL NEED TO FILL OUT THE SPECIAL
 INSPECTOR AGREEMENT FORMS AND RESUBMIT TO THE CITY FOR
 REVIEW PRIOR TO PERMIT ISSUANCE. CONTACT KEN CONRAD
 MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT
 (561)805-6666 FOR FURTHER INFORMATION
  
 PLEASE SUBMIT THE SPECIAL INSPECTOR AGREEMENT WITH ALL
 APPLICABLE NOTARIZED SIGNATURES.
  
 1C) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT CONSISTENT
 WITH THE FLORIDA STATUTE REQUIREMENT FS 553.79(7)(D):
  
 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS CHAPTER AND CHAPTER 633.
  
 THIS STATEMENT IS NOT INCLUDED ON ANY SHEETS WHICH WERE
 SPOT CHECKED (VARIOUS A AND S SHEETS).
  
 1D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 1E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 2. DOCUMENTS PREPARED BY AN ENGINEER ARE TO INCLUDE THE
 CERTIFICATE OF AUTHORIZATION FOR THE ENGINEERING
 COMPANY (29684), FS471, FAC61G15-23.002.
  
 YOU MAY ALSO SEE THIS REQUIREMENT AT WWW.FBPE.ORG
 (LEGAL, LAWS AND RULES).
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-09-25 Cont ID  
Sent By eschneid Date 2015-09-25 Time 15:38 Rev Time 2.00
Received By eschneid Date 2015-09-23 Time 09:53 Sent To  
Notes
2015-09-23 10:04:02PASSED
  
 1. THE DETAILS FOR THE FOLLOWING ITEMS HAVE BEEN
 REVIEWED BY PLANNING STAFF FOR COMPLIANCE WITH RES. NO.
 206-15 AND HAVE BEEN ADDRESSED IN A SATISFACTORY MANNER
 TO ISSUE THIS PERMIT. A FINAL FULL REVIEW WILL BE
 CONDUCTED WHEN THE PLANS ARE SUBMITTED FOR THE INTERIOR
 BUILDOUT AND THEY SHALL CONFORM TO THE DRAWINGS
 SUBMITTED TO PLANNING STAFF FOR PERLIMINARY REVIEW.
 A. PROVIDE AT LEAST ONE SHOWER AND CHANGING FACILITY
 WITHIN THE BUILDING MEETING BOTH BUILDING CODE AND
 PLANNING DIVISION REQUIREMENTS. NOTE: A SEAT FOR
 CHANGING USE SHALL BE ADDED.
 B. SHOW MERCHANDISE WINDOW DISPLAYS IN AS MANY OF THE
 GROUND LEVEL GLAZED OPENINGS AS POSSIBLE.
  
 2. SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR THE
 FOLLOWING ITEMS THAT ARE EXTERIOR TO THE BUILDING:
  
 A. AWNINGS
 B. PARKING LOT STRIPING
 C. LANDSCAPE
 D. FOUNTAINS
 E. SITE LIGHTING
 F. HARDSCAPE
 G. BICYCLE RACKS
 H. WALLS AND GATES
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-08-20 Cont ID  
Sent By eschneid Date 2015-08-20 Time 08:42 Rev Time 6.00
Received By eschneid Date 2015-08-19 Time 13:31 Sent To  
Notes
2015-08-19 15:46:45FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES:
  
 1. THE STEEL SUPERSTRUCTURE IS VERTICAL CONSTRUCTION,
 SO IT TRIGGERS CONDITION NO. 1 OF RESOLUTION NO. 206-15
 LISTED BELOW:
  
 1) PRIOR TO THE APPROVAL OF A BUILDING PERMIT FOR
 VERTICAL CONSTRUCTION OF THE RESTORATION HARDWARE
 GALLERY, THE APPLICANT SHALL:
  
 A. PROVIDE AT LEAST ONE SHOWER AND CHANGING FACILITY
 WITHIN THE BUILDING MEETING BOTH BUILDING CODE AND
 PLANNING DIVISION REQUIREMENTS.
 B. SHOW MERCHANDISE WINDOW DISPLAYS IN AS MANY OF THE
 GROUND LEVEL GLAZED OPENINGS AS POSSIBLE.
  
 2. THE PLANS PROVIDED (FOR REFERENCE ONLY) DO NOT
 INCLUDE INFORMATION ON THE SHOWER AND CHANGING
 FACILITIES. THE CURRENT LAYOUT WITH NO SPECIFIC
 INFORMATION WAS NOT APPROVED AS MEETING THE REQUIREMENT
 BY THE PLANNING DIVISION DURING THE SITE PLAN APPROVAL
 PROCESS.
  
 3. THERE IS NO GLAZING SPECIFIC INFORMATION PROVIDED ON
 THE GLAZING OF THE WINDOWS ON THE GROUND LEVEL FOR
 STAFF TO VERIFY THE INTENT OF 1)B.
  
 4. THE BUILDING CONTAINS MORE SQUARE FOOTAGE THAN WAS
 APPROVED BY RESOLUTION NO. 206-15. A MINOR PLANNED
 DEVELOPMENT AMENDMENT TO REFLECT THE NEW SQUARE FOOTAGE
 IS REQUIRED PRIOR TO THE APPROVAL OF THE VERTICAL
 CONSTRUCTION. THE MINOR PLANNED DEVELOPMENT AMENDMENT
 SHALL SHOW WHERE THE BUILDING HAS GOTTEN LARGER AND THE
 IMPACT ON THE SITE LAYOUT, TO INCLUDE THE SETBACKS, THE
 LANDSCAPE, THE PARKING, ETC.
  
 5. THE ARCHITECTURE IS DIFFERENT THAN THE ONE APPROVED
 BY RESOLUTION NO. 206-15. A MINOR PLANNED DEVELOPMENT
 AMENDMENT TO REFLECT THE NEW ELEVATIONS IS REQUIRED.
  
 6. IN LIGHT OF THE TIMING TO ADDRESS THE COMMENTS
 ABOVE, IT MAY BE ADVANTAGEOUS TO REVISE THE SCOPE OF
 THIS PERMIT TO BE JUST FOR THE FOUNDATION TO GIVE
 YOURSELVES MORE TIME TO ADDRESS THE COMMENTS RELATED TO
 THE VERTICAL CONSTRUCTION.
  
 7. SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR THE
 FOLLOWING:
  
 A. AWNINGS
 B. PARKING LOT STRIPING
 C. LANDSCAPE
 D. FOUNTAINS
 E. SITE LIGHTING
 F. HARDSCAPE
 G. BICYCLE RACKS
 H. WALLS AND GATES
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
2015-08-17 11:17:028/17/15