| 2015-08-05 18:22:24 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 / 2008 NEC |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY ELECTRICAL |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT TWO SETS OF ELECTRICAL PLANS THAT ARE DRAWN |
| | TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER OR |
| | OTHER ACCEPTABLE MEDIUM WITH CONTRAST, CLARITY AND |
| | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. FBC 107.1 & |
| | 107.2.1.4 |
| | |
| | 2) SPECIFY THE LOCATION OF THE ELECTRIC METER AND |
| | SERVICE EQUIPMENT DISCONNECT. FBC 107.2.1 & NEC 230.70 |
| | |
| | 3) NEC 210.52 (C) (1) - A RECEPTACLE OUTLET SHALL BE |
| | INSTALLED AT EACH WALL COUNTERTOP SPACE 12 INCHES OR |
| | WIDER SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN |
| | 2 FEET MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET |
| | IN THAT SPACE. |
| | |
| | 4) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH |
| | CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE |
| | OUTLETS. THIS CIRCUIT SHALL HAVE NO OTHER OUTLETS. |
| | |
| | 5) A SEPARATE PERMIT IS REQUIRED FOR THE TEMPORARY |
| | ELECTRIC SERVICE. REMOVE THE TEMPORARY SERVICE DRAWING |
| | FROM THE PLANS. FBC 107.2.1 |
| | |
| | 6) NEC 220.40 - PROVIDE ACCURATE ELECTRICAL LOAD |
| | CALCULATIONS. |
| | |
| | 7) NEC 406.8 - OUTDOOR RECEPTACLES ARE REQUIRED TO BE |
| | WEATHER PROOF. |
| | |
| | 8) FBC 107.2.1 - SPECIFY THE LOCATIONS OF THE TWO AIR |
| | HANDLER UNITS ON THE PLANS AND SHOW COMPLIANCE WITH NEC |
| | 110.32(B) FOR REQUIRED PERMANENT LADDERS TO PROVIDE |
| | SAFE ACCESS TO EQUIPMENT INSTALLED IN ATTICS. |
| | |
| | 9) FBC 107.2.1 - SPECIFY THE LOCATION OF THE WATER |
| | HEATER ON THE PLANS AND THE DISCONNECT REQUIRED BY NEC |
| | 422.31. |
| | |
| | 10) NEC 210.52(D) AT LEAST ONE GFCI PROTECTED |
| | RECEPTACLE OUTLET IS REQUIRED IN THE BATHROOM AT |
| | BEDROOM #1. |
| | |
| | 11) NEC 250.50 - BOND ALL GROUNDING ELECTRODES THAT ARE |
| | PRESENT. |
| | |
| | 12) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL |
| | BE PROVIDED. |
| | |
| | 13) NEC 250.104(B) THE GAS PIPING IS REQUIRED TO BE |
| | BONDED. |
| | |
| | 14) A SEPARATE PERMIT, APPLICATION AND REVIEW IS |
| | REQUIRED FOR GAS. IF THE APPLIANCES ARE INTENDED TO BE |
| | GAS THEY SHOULD BE SPECIFIED ON THE PLANS AS SUCH. FBC |
| | 107.2.1 |
| | |
| | |
| | |
| | |
| | |