Plan Review Details - Permit 15080001
Plan Review Stops For Permit 15080001
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-09-04 Cont ID  
Sent By albarran Date 2015-09-02 Time 17:40 Rev Time 0.00
Received By albarran Date 2015-09-02 Time 16:22 Sent To I
Notes
2015-09-04 08:42:11ACCEPTED THE SIGNED & SEALED DRAWINGS.
2015-09-02 17:41:50THE PLANS WERE NOT CORRECT. I CONTACTED THE ENGINEER
 ABOUT SUBMITTING PDF. THE CONTRACTOR WILL BE SUBMITTING
 ELECTRONICALLY APPROVED COPIES OF PAGES FA-1 AND FA-2.
 UPON RECEIPT MAKE SURE THAT BOTH PAGES BEAR MY GREEN
 SIGN OF APPROVAL BEFORE TAKING THEM IN. IF THEY DO HAVE
 THE GREEN APPROVAL MARKINGS, HAVE THE CONTRACTOR WAIT
 AND COME SEE ME. DEPENDING ON WHAT I HEAR FROM FIRE, WE
 CAN ISSUE HIM HIS PERMIT AND HE CAN BE ON HIS MERRY
 WAY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-27 Cont ID  
Sent By albarran Date 2015-08-27 Time 19:33 Rev Time 0.00
Received By albarran Date 2015-08-27 Time 17:38 Sent To I
Notes
2015-08-27 19:45:34PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. CORRECT YOUR REFERENCED CODES AS FOLLOWS:
 A) FLORIDA FIRE PREVENTION CODE (FFPC) 2012 EDITION
 B) NFPA 1, 2012 EDITION
 C) NFPA 70, 2011 EDITION (NEC)
 D) NFPA 72, 2010 EDITION
 E) NFPA 101, 2012 EDITION
 F) FBC, 5TH EDITION 2014 (FLORIDA BLDG. CODE)
 2. WHEN MAKING REFERENCES TO SPECIFIC CODE SECTIONS,
 MAKE IT COUNT. PLEASE HELP ME FIND SECTION 760.61 OF
 THE 2011 NEC.
 3. AGAIN, I DON?T KNOW WHAT IS TO BE REPRESENTED IN
 CHAPTER 7 OF NFPA 72. PLEASE ASSIST.
 4. THE FIRE STOPPING MATERIAL PROPOSED FOR THE CABLES
 PENETRATING GYPSUM (DRYWALL) WALLS IS UNACCEPTABLE.
 ACCORDING TO NOTE 2 THIS PRODUCT INDICATES THE USE OF
 ALUMINUM CONDUCTORS
 5. YOUR SCOPE OF WORK AS INDICATED ON SHEET FA-01 FAILS
 TO INCLUDE ANY NOTIFICATION DEVICES.
 6. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATIONS
 SHALL BE MOUNTED WITHIN 5? OF THE EXIT. RELOCATE THAT
 OF THE RECEPTION AREA ACCORDINGLY.
 7. YOUR BATTERY CALC NUMBERS ARE INCORRECT, YET YOU
 ARRIVED AT THE CORRECT SUM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-03 Cont ID  
Sent By scaldero Date 2015-08-03 Time 11:56 Rev Time 0.00
Received By scaldero Date 2015-08-03 Time 11:56 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-27 Cont ID  
Sent By albarran Date 2015-09-04 Time 08:42 Rev Time 0.00
Received By albarran Date 2015-08-03 Time 08:26 Sent To  
Notes
2015-09-04 08:44:119/4/15 - PASSED ELECTRICAL REVIEW UPON SUBMITTAL OF
 PREVIOUSLY REVIEWED DRAWINGS AS INDICATED. CONTRACTOR
 WAITING OUT FRONT. GIVEN TO SUSAN FOR ISSUANCE.
2015-08-27 19:47:508/27/15 - FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "F". MA
2015-08-03 08:26:46ROUTED TO FIRE