Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-12-18 Cont ID  
Sent By jwitmer Date 2015-12-18 Time 16:16 Rev Time 0.00
Received By jwitmer Date 2015-12-18 Time 14:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-11-02 Cont ID  
Sent By jwitmer Date 2015-11-02 Time 17:22 Rev Time 0.00
Received By jwitmer Date 2015-11-02 Time 16:22 Sent To  
Notes
2015-11-02 17:05:47BUILDING PLAN REVIEW
 REVISION: 15071219
 PERMIT: 14110788
 ADD: 418 25TH ST
 CONT: SOUTHERN COAST
 TEL: (561)584-8502
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE:MON. NOV. 02/ 2015
 ACTION: DENIED.
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
  
  
 1) THE SCOPE OF THE PROJECT HAS GREATLY INCREASE BUT
 THERE IS NO INCREASE IN VALUE. W P B ADMINISTRATIVE
 CODE 108.2 SCHEDULE OF PERMIT FEES. ON BUILDINGS,
 STRUCTURES, ELECTRICAL, GAS, MECHANICAL AND PLUMBING
 SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A FEE FOR
 EACH PERMIT SHALL BE PAID AS REQUIRED, IN ACCORDANCE
 WITH THE SCHEDULE ESTABLISHED BY THE APPLICABLE
 GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) PROVIO:. PRODUCT APPROVALS : 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, SWING & OVERHEAD DOORS. MISSING
 OVERHEAD DOOR. NO SHOP DRAWING STAMP OF APPROVAL FROM
 THE DESIGNER OF RECORD.
 (B) WINDOWS NO SHOP DRAWING STAMP OF APPROVAL FROM THE
 DESIGNER OF RECORD.
 (C) PANEL WALLS: STOREFRONTS,NO SHOP DRAWING STAMP OF
 APPROVAL FROM THE DESIGNER OF RECORD.
 (E) SHUTTERS (NOTE) THE 2ND FLOOR 1 HOUR FIRE RATED
 WINDOW WILL REQUIRE STORM SHUTTERS UNLESS THE WINDOW
 WAS TESTED AS A 1 HR. RATED WINDOW & LARGE MISSILE
 IMPACT TESTED WINDOW. MISSING SHUTTER PRODUCT APPROVAL.
 NO SHOP DRAWING STAMP OF APPROVAL FROM THE DESIGNER OF
 RECORD.
  
 3) PROVISO. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4) COMPLIED. SHEET A-2 & A-4 NEW RESTROOMS 102 & 106
 WILL NEED TO SHOW COMPLIANCE WITH 2010
 FBC-ACCESSIBILITY CODE 604.3.1 SIZE. CLEARANCE AROUND A
 WATER CLOSET SHALL BE 60 INCHES (1525 MM) MINIMUM
 MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES
 (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL.
  
 5) COMPLIED.
  
 6) COMPLIED. SHEET S-2 NOTE G-1 INDICATES THE
 STRUCTURAL DESGIN IS TO THE 2014 FBC-B. NOTE THIS IS A
 REVISION TO A 2010 FBC PLAN, PLEASE CORRECT.
  
 7) 2ND REQUEST!!!!!!!!!!!! WHEN RESUBMITTING PLANS
 PLEASE INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS
 & REPLACE ANY PAGES AS NECESSARY. THE PLANS NEED TO BE
 PULLED APART AND REASSEMBLED SO THE SHEETS ARE IN
 NUMERICAL ORDER!!!!!!!!!!
  
 107.2.1.4 QUALITY OF BUILDING PLANS. . THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-06 Cont ID  
Sent By jwitmer Date 2015-08-06 Time 12:31 Rev Time  
Received By jwitmer Date 2015-08-06 Time 11:30 Sent To  
Notes
2015-08-06 12:31:00BUILDING PLAN REVIEW
 REVISION: 15071219
 PERMIT: 14110788
 ADD: 418 25TH ST
 CONT: SOUTHERN COAST
 TEL: (561)584-8502
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:THURS. AUG.06/ 2015
 ACTION: DENIED.
  
 1) THE SCOPE OF THE PROJECT HAS GREATLY INCREASE BUT
 THERE IS NO INCREASE IN VALUE. W P B ADMINISTRATIVE
 CODE 108.2 SCHEDULE OF PERMIT FEES. ON BUILDINGS,
 STRUCTURES, ELECTRICAL, GAS, MECHANICAL AND PLUMBING
 SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A FEE FOR
 EACH PERMIT SHALL BE PAID AS REQUIRED, IN ACCORDANCE
 WITH THE SCHEDULE ESTABLISHED BY THE APPLICABLE
 GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) PRODUCT APPROVALS : 2010 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, SWING & OVERHEAD DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS,
 (E) SHUTTERS (NOTE) THE 2ND FLOOR 1 HOUR FIRE RATED
 WINDOW WILL REQUIRE STORM SHUTTERS UNLESS THE WINDOW
 WAS TESTED AS A 1 HR. RATED WINDOW & LARGE MISSILE
 IMPACT TESTED WINDOW.
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) SHEET A-2 & A-4 NEW RESTROOMS 102 & 106 WILL NEED TO
 SHOW COMPLIANCE WITH 2010 FBC-ACCESSIBILITY CODE
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 5) SHEET A-4 DETAIL # 1 INDICATES NEW METAL LOUVERED
 AWNING, THERE HAS BEEN NO DESIGN CRITERIA SUBMITTED FOR
 WIND DESIGN. IS THIS AWNING A FOLDING TYPE, OR RIGID,
 TYPE OF MATERIAL IT IS TO BE METAL FRAME AND LOUVER?
 PLEASE ALSO PROVIDE WHERE THE PROPERTY LINE IS LOCATED
 IN REGUARDS TO THE BUILDING.
  
 5A)FBC-B 3202.2.3 AWNINGS.
 THE VERTICAL CLEARANCE FROM THE PUBLIC RIGHT-OF-WAY TO
 THE LOWEST PART OF ANY AWNING, INCLUDING VALANCES,
 SHALL BE NOT LESS THAN 7 FEET (2134 MM).
  
 5B) FBC-B 3202.3 ENCROACHMENTS 8 FEET OR MORE ABOVE
 GRADE.
 ENCROACHMENTS 8 FEET (2438 MM) OR MORE ABOVE GRADE
 SHALL COMPLY WITH SECTIONS 3202.3.1 THROUGH 3202.3.4.
  
 5C) FBC-B 3105.4.2.2
 THE WIND DESIGN LOADS FOR ANY FABRIC OR MEMBRANE
 COVERED STRUCTURE DESIGNED WITH A PERMANENT OR
 NONREMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON THE
 FOLLOWING CRITERIA:
 1. MINIMUM WIND SPEED VELOCITY AS REQUIRED IN CHAPTER
 16, USING FIGURE 1609C.
 2. EXPOSURE B, C OR D AS DEFINED IN CHAPTER 16.
  
 6) SHEET S-2 NOTE G-1 INDICATES THE STRUCTURAL DESGIN
 IS TO THE 2014 FBC-B. NOTE THIS IS A REVISION TO A 2010
 FBC PLAN, PLEASE CORRECT.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-11-09 Cont ID  
Sent By ppetty Date 2015-11-09 Time 09:14 Rev Time 0.00
Received By ppetty Date 2015-11-09 Time 09:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-31 Cont ID  
Sent By ppetty Date 2015-08-31 Time 11:54 Rev Time 0.00
Received By ppetty Date 2015-08-31 Time 11:42 Sent To  
Notes
2015-08-31 11:53:48210.11-C-1,210.12-B,220.52,R314.3.1
 561-644-7305
 PHIL PETTY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-11-03 Cont ID  
Sent By scaldero Date 2015-11-03 Time 14:35 Rev Time 0.00
Received By scaldero Date 2015-11-03 Time 14:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-03 Cont ID  
Sent By scaldero Date 2015-08-03 Time 12:58 Rev Time 0.00
Received By scaldero Date 2015-08-03 Time 12:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-18 Cont ID  
Sent By jwitmer Date 2015-12-18 Time 16:16 Rev Time 0.00
Received By jwitmer Date 2015-12-16 Time 12:37 Sent To  
Notes
2015-12-17 12:37:41RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-09 Cont ID  
Sent By ppetty Date 2015-11-09 Time 09:15 Rev Time 0.00
Received By ppetty Date 2015-10-19 Time 13:33 Sent To  
Notes
2015-10-20 13:34:00B37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-02 Cont ID  
Sent By lmarchan Date 2015-08-31 Time 15:22 Rev Time 0.00
Received By lmarchan Date 2015-07-31 Time 14:13 Sent To  
Notes
2015-07-31 14:13:43B27

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-10-29 Cont ID  
Sent By ccole Date 2015-10-29 Time 11:54 Rev Time 0.00
Received By ccole Date 2015-10-29 Time 11:54 Sent To  
Notes
2015-10-29 11:58:15PROVISOS:
 PERMIT #15071219
 10/29/15
  
 1) SITE SPECIFIC WIND LOAD ENGINEERING FOR TIE-DOWN OF
 THE ROOFTOP AC UNITS AND STANDS SHALL BE SUBMITTED TO
 THE BUILDING DEPARTMENT AND APPROVED PRIOR TO 1ST
 INSPECTION.
 2) FL. PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S SHALL
 BE REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL OF
 RECORD AND SUBMITTED PRIOR TO 1ST INSPECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-07 Cont ID  
Sent By ccole Date 2015-08-07 Time 10:20 Rev Time 0.00
Received By ccole Date 2015-08-07 Time 10:20 Sent To  
Notes
2015-08-28 10:35:03SKENNEDY'S DESK
2015-08-07 10:53:501ST REVIEW: FBC 2010 MECHANICAL
 REVISION PERMIT #15071219
 MASTER #14110778
 8/7/15
  
 1) THE REVISED PLANS INDICATE NEW CONDITIONED OFFICE
 SPACES ON THE FIRST FLOOR INCLUDING THE ADDTION OF A
 NEW 3TON AC SYSTEM: SUBMIT REVISED ENERGY AND AC LOAD
 CALCULATIONS.
 2) REFER TO SECTION 301.12 FBC-10 MECHANICAL AND
 PROVIDE ENGINEERED STRUCTURAL DETAILS FOR SUPPORT AND
 ATTACHMENT OF THE AC CONDENSERS AND ROOF STANDS TO THE
 ROOF STRUCTURE. PLEASE ALSO SUBMIT A VALID FL. PRODUCT
 APPROVAL OR MIAMI-DADE NOA FOR THE ROOF STANDS REVIEWED
 AND APPROVED BY THE DESIGN PROFESSIONAL OF RECORD.
 3) REFER TO SECTION 304.11: THE NEW CONDENSERS WILL
 REQUIRE GUARDS IF WITHIN 10 FT. OF THE ROOF EDGE,
 UNLESS THE EXISTING PARAPET WALL HEIGHT IS MINIMUM 42"
 ABOVE THE ROOF LEVEL.
 4) SUBMIT PRODUCT APPROVALS OR NOA'S FOR THE RUSKIN
 LOUVERS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-10-28 Cont ID  
Sent By gjohnson Date 2015-10-28 Time 15:53 Rev Time 0.00
Received By gjohnson Date 2015-10-28 Time 15:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-08-01 Cont ID  
Sent By tklarge Date 2015-08-01 Time 06:07 Rev Time 0.00
Received By tklarge Date 2015-08-01 Time 05:34 Sent To  
Notes
2015-08-01 05:20:211) THE MINIMUM WIDTH OF THE TOILET ROOMS SHALL BE 85
 INCHES IF BUILT PERFECT. 86 INCHES ALLOWS FOR
 TOLERANCES. 2014 FBC-ACCESSIBILITY SECS.604.3 AND
 606.2.
 2) SHT. A-4 - ENLARGED TOILET ROOM SHOWS THE LAVATORY
 ENCROACHING INTO THE CLEAR FLOOR SPACEE FOR THE WATER
 CLOSET. THE LAVATORY CANNOT ENCROACH INTO THIS AREA.
 2014 FBC-ACCESSIBILITY SEC.604.3.
 3) SHOW THE MOUNTING HEIGHTS/DIMENSIONS OF ALL FIXTURES
 AND ITEMS LOCATED IN THE TOILET ROOM. COMPLY WITH 2014
 FBC CHAPTS.2 & 6.
 4) SUBMIT WATER AND SANITARY RISERS FOR THE FIRST AND
 SECOND FLOORS. FBC AMEND. TO FBC SEC. 107.3.5.1.3.
 5) SHOW ALL PIPE SIZES FOR THE SANITARY AND WATER
 RISERS.WPB AMEND. TO FBC SEC. 107.2.1.
 6) SIZE ALL CONDENSATE LINES. WPB AMEND. TO FBC SEC.
 107.2.1.
 7) SUBMIT A DETAIL FOR THE DRYWELL.WPB AMEND. TO FBC
 SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  