| 2015-11-02 17:05:47 | BUILDING PLAN REVIEW |
| | REVISION: 15071219 |
| | PERMIT: 14110788 |
| | ADD: 418 25TH ST |
| | CONT: SOUTHERN COAST |
| | TEL: (561)584-8502 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE:MON. NOV. 02/ 2015 |
| | ACTION: DENIED. |
| | |
| | NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA |
| | STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A |
| | FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE |
| | REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO |
| | CORRECT A CODE VIOLATION. |
| | |
| | |
| | |
| | 1) THE SCOPE OF THE PROJECT HAS GREATLY INCREASE BUT |
| | THERE IS NO INCREASE IN VALUE. W P B ADMINISTRATIVE |
| | CODE 108.2 SCHEDULE OF PERMIT FEES. ON BUILDINGS, |
| | STRUCTURES, ELECTRICAL, GAS, MECHANICAL AND PLUMBING |
| | SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A FEE FOR |
| | EACH PERMIT SHALL BE PAID AS REQUIRED, IN ACCORDANCE |
| | WITH THE SCHEDULE ESTABLISHED BY THE APPLICABLE |
| | GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) PROVIO:. PRODUCT APPROVALS : 2010 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS & |
| | CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS, SWING & OVERHEAD DOORS. MISSING |
| | OVERHEAD DOOR. NO SHOP DRAWING STAMP OF APPROVAL FROM |
| | THE DESIGNER OF RECORD. |
| | (B) WINDOWS NO SHOP DRAWING STAMP OF APPROVAL FROM THE |
| | DESIGNER OF RECORD. |
| | (C) PANEL WALLS: STOREFRONTS,NO SHOP DRAWING STAMP OF |
| | APPROVAL FROM THE DESIGNER OF RECORD. |
| | (E) SHUTTERS (NOTE) THE 2ND FLOOR 1 HOUR FIRE RATED |
| | WINDOW WILL REQUIRE STORM SHUTTERS UNLESS THE WINDOW |
| | WAS TESTED AS A 1 HR. RATED WINDOW & LARGE MISSILE |
| | IMPACT TESTED WINDOW. MISSING SHUTTER PRODUCT APPROVAL. |
| | NO SHOP DRAWING STAMP OF APPROVAL FROM THE DESIGNER OF |
| | RECORD. |
| | |
| | 3) PROVISO. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 4) COMPLIED. SHEET A-2 & A-4 NEW RESTROOMS 102 & 106 |
| | WILL NEED TO SHOW COMPLIANCE WITH 2010 |
| | FBC-ACCESSIBILITY CODE 604.3.1 SIZE. CLEARANCE AROUND A |
| | WATER CLOSET SHALL BE 60 INCHES (1525 MM) MINIMUM |
| | MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES |
| | (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR |
| | WALL. |
| | |
| | 5) COMPLIED. |
| | |
| | 6) COMPLIED. SHEET S-2 NOTE G-1 INDICATES THE |
| | STRUCTURAL DESGIN IS TO THE 2014 FBC-B. NOTE THIS IS A |
| | REVISION TO A 2010 FBC PLAN, PLEASE CORRECT. |
| | |
| | 7) 2ND REQUEST!!!!!!!!!!!! WHEN RESUBMITTING PLANS |
| | PLEASE INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS |
| | & REPLACE ANY PAGES AS NECESSARY. THE PLANS NEED TO BE |
| | PULLED APART AND REASSEMBLED SO THE SHEETS ARE IN |
| | NUMERICAL ORDER!!!!!!!!!! |
| | |
| | 107.2.1.4 QUALITY OF BUILDING PLANS. . THE BUILDING |
| | OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, |
| | OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER |
| | TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. |
| | |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |