Plan Review Details - Permit 15071158
| Plan Review Stops For Permit 15071158 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2015-08-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-08-18 |
Time |
07:24 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-08-18 |
Time |
07:24 |
Sent To |
|
|
| Notes |
| 2015-08-18 07:24:58 | PROVISO - MANUFACTURER TO SEND A COPY OF THE ASTM E 84 | | | TEST REPORT VIA EMAIL | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-08-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-08-10 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-08-10 |
Time |
15:58 |
Sent To |
|
|
| Notes |
| 2015-08-10 15:59:26 | PRODUCT PROPOSED HAS NOT BEEN TESTED ALONE OR WITH A | | | WOOD FLOOR; WAS TESTED WITH CERAMIC TILE. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-07-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-07-30 |
Time |
17:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-07-30 |
Time |
17:25 |
Sent To |
|
|
| Notes |
| 2015-07-30 17:26:59 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | [email protected] | | | | | | FBC FLORIDA BUILDING CODE 5TH EDITION 2014 | | | | | | TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED | | | | | | 1. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM | | | E 84 OR UL 723. | | | | | | THE PRODUCT PROPOSED IS ACOUSTICORK, THE FLAME SPREAD | | | TEST IS FOR BADGER CORK. | | | | | | IF THIS IS THE SAME PRODUCT, PROVIDE A LETTER ON | | | LETTERHEAD FROM THE MANUFACTURER STATING THE | | | RELATIONSHIP BETWEEN ACOUSTICORK AND BADGER CORK AND | | | ADDRESS THE ISSUE OF WHETHER THE PRODUCT ITSELF (RESIN | | | OR OTHER BONDING AGENTS) HAS CHANGED FROM THE PRODUCT | | | THAT WAS TESTED FOR FLAME SPREAD. | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-07-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-07-30 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-07-29 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2015-07-29 16:05:01 | ROUTED TO BLDG <5K |
|
|
|
Account Summary | Usage Policy | Privacy Policy