| 2015-09-03 14:41:58 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | |
| | YOUR FAILURE TO PROVIDE THE REQUIRED LOAD CALCS, |
| | PROMPTED ME TO SEEK THE INFORMATION ON MY OWN. IN GOING |
| | OVER YOUR SUBMITTAL AND THE NUMBERS THEREIN I NOTICED |
| | THE FOLLOWING: |
| | |
| | 1. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD), |
| | INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR RTU |
| | AHU-1 OTHERWISE KNOWN ON THE PANEL SCHEDULE AS OA-1 |
| | INDICATES 70AMP. PANEL GL2 CIRCUITS 38/40/42 SHOW TO |
| | HAVE A 90 AMP DEVICE. |
| | THE KVA/KW INDICATED ON THE FORM IS 27 YET THE LOAD ON |
| | THE PANEL PER THE SCHEDULE IS ONLY 11.92. CORRECT THE |
| | PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO MATCH AND |
| | ADJUST YOUR CONDUCTORS ACCORDINGLY. |
| | 2. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD), |
| | INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR RTU |
| | AHU-2 OTHERWISE KNOWN ON THE PANEL SCHEDULE AS OA-2 |
| | INDICATES 70AMP. PANEL LP2A CIRCUITS 20/22/24 SHOW TO |
| | HAVE A 90 AMP DEVICE. |
| | THE KVA/KW INDICATED ON THE FORM IS 27 YET THE LOAD ON |
| | THE PANEL PER THE SCHEDULE IS ONLY 11.92. CORRECT THE |
| | PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO MATCH AND |
| | ADJUST YOUR CONDUCTORS ACCORDINGLY. |
| | 3. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD), |
| | INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR RTU |
| | AHU-3 OTHERWISE KNOWN ON THE PANEL SCHEDULE AS OA-3 |
| | INDICATES 70AMP. PANEL SP CIRCUITS 1/3/5 SHOW TO HAVE A |
| | 70 AMP DEVICE. (OK) |
| | THE KVA/KW INDICATED ON THE FORM IS 27 YET THE LOAD ON |
| | THE PANEL PER THE SCHEDULE IS ONLY 11.92. CORRECT THE |
| | PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO MATCH AND |
| | ADJUST YOUR CONDUCTORS ACCORDINGLY. |
| | 4. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD), |
| | INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR RTU |
| | AHU-4 OTHERWISE KNOWN ON THE PANEL SCHEDULE AS OA-4 |
| | INDICATES 70AMP. PANEL SP CIRCUITS 2/4/6 SHOW TO HAVE A |
| | 70 AMP DEVICE. (OK) |
| | THE KVA/KW INDICATED ON THE FORM IS 27 YET THE LOAD ON |
| | THE PANEL PER THE SCHEDULE IS ONLY 11.92. CORRECT THE |
| | PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO MATCH AND |
| | ADJUST YOUR CONDUCTORS ACCORDINGLY. |
| | 5. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD), |
| | INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR CW |
| | AHU-1, OTHERWISE KNOWN ON THE PANEL SCHEDULE AS AHU-1 |
| | INDICATES 30AMP. PANEL GDA CIRCUITS 7/9/11 SHOW TO HAVE |
| | A 40 AMP DEVICE. |
| | THOUGH THERE IS NO KVA LOAD INDICATED ON THE FORM, FROM |
| | THE FLC (FULL LOAD CURRENT) IT IS EASILY VISIBLE THAT |
| | IT IS NOT THE 6.3 INDICATED ON THE PANEL SCHEDULE. |
| | CORRECT THE PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO |
| | MATCH AND ADJUST YOUR CONDUCTORS ACCORDINGLY. |
| | 6. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD), |
| | INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR CW |
| | AHU-2, OTHERWISE KNOWN ON THE PANEL SCHEDULE AS AHU-2 |
| | INDICATES 40AMP. PANEL GDA CIRCUITS 13/15/17 SHOW TO |
| | HAVE A 50 AMP DEVICE. |
| | THOUGH THERE IS NO KVA LOAD INDICATED ON THE FORM, FROM |
| | THE FLC (FULL LOAD CURRENT) IT IS EASILY VISIBLE THAT |
| | IT IS NOT THE 8.3 INDICATED ON THE PANEL SCHEDULE. |
| | CORRECT THE PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO |
| | MATCH AND ADJUST YOUR CONDUCTORS ACCORDINGLY. |
| | 7. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD), |
| | INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR CW |
| | AHU-3, OTHERWISE KNOWN ON THE PANEL SCHEDULE AS AHU-3 |
| | INDICATES 30AMP. PANEL GDA CIRCUITS 14/16/18 SHOW TO |
| | HAVE A 25 AMP DEVICE. |
| | THOUGH THERE IS NO KVA LOAD INDICATED ON THE FORM, FROM |
| | THE FLC (FULL LOAD CURRENT) IT IS EASILY VISIBLE THAT |
| | IT IS NOT THE 6.3 INDICATED ON THE PANEL SCHEDULE. |
| | CORRECT THE PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO |
| | MATCH AND ADJUST YOUR CONDUCTORS ACCORDINGLY. |
| | 8. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD), |
| | INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR CW |
| | AHU-4, OTHERWISE KNOWN ON THE PANEL SCHEDULE AS AHU-4 |
| | INDICATES 20AMP. PANEL GDA CIRCUITS 7/9/11 SHOW TO HAVE |
| | A 25 AMP DEVICE. |
| | THOUGH THERE IS NO KVA LOAD INDICATED ON THE FORM, FROM |
| | THE FLC (FULL LOAD CURRENT) IT IS EASILY VISIBLE THAT |
| | IT IS NOT THE 3.72 INDICATED ON THE PANEL SCHEDULE. |
| | CORRECT THE PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO |
| | MATCH AND ADJUST YOUR CONDUCTORS ACCORDINGLY. |
| | 9. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD), |
| | INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR CW |
| | AHU-5, OTHERWISE KNOWN ON THE PANEL SCHEDULE AS AHU-5 |
| | INDICATES 40AMP. PANEL CDP CIRCUITS 8/10/12 SHOW TO |
| | HAVE A 50 AMP DEVICE. |
| | THOUGH THERE IS NO KVA LOAD INDICATED ON THE FORM, FROM |
| | THE FLC (FULL LOAD CURRENT) IT IS EASILY VISIBLE THAT |
| | IT IS NOT THE 7.17INDICATED ON THE PANEL SCHEDULE. |
| | CORRECT THE PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO |
| | MATCH AND ADJUST YOUR CONDUCTORS ACCORDINGLY. |
| | 10. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD), |
| | INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR CW |
| | AHU-6, OTHERWISE KNOWN ON THE PANEL SCHEDULE AS AHU-6 |
| | INDICATES 40AMP. PANEL GDA CIRCUITS 19/21/23 SHOW TO |
| | HAVE A 50 AMP DEVICE. |
| | THOUGH THERE IS NO KVA LOAD INDICATED ON THE FORM, FROM |
| | THE FLC (FULL LOAD CURRENT) IT IS EASILY VISIBLE THAT |
| | IT IS NOT THE 8.4 INDICATED ON THE PANEL SCHEDULE. |
| | CORRECT THE PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO |
| | MATCH AND ADJUST YOUR CONDUCTORS ACCORDINGLY. |
| | 11. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD), |
| | INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR CW |
| | AHU-7, OTHERWISE KNOWN ON THE PANEL SCHEDULE AS AHU-7 |
| | INDICATES 30AMP. PANEL CDP CIRCUITS 1/3/5 SHOW TO HAVE |
| | A 40 AMP DEVICE. |
| | THOUGH THERE IS NO KVA LOAD INDICATED ON THE FORM, FROM |
| | THE FLC (FULL LOAD CURRENT) IT IS EASILY VISIBLE THAT |
| | IT IS NOT THE 5.57 INDICATED ON THE PANEL SCHEDULE. |
| | CORRECT THE PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO |
| | MATCH AND ADJUST YOUR CONDUCTORS ACCORDINGLY. |
| | 12. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD), |
| | INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR CW |
| | AHU-8, OTHERWISE KNOWN ON THE PANEL SCHEDULE AS AHU-8 |
| | INDICATES 20AMP. PANEL CDP CIRCUITS 2/4/6 SHOW TO HAVE |
| | A 40 AMP DEVICE. |
| | THOUGH THERE IS NO KVA LOAD INDICATED ON THE FORM, FROM |
| | THE FLC (FULL LOAD CURRENT) IT IS EASILY VISIBLE THAT |
| | IT IS NOT THE 3.72 INDICATED ON THE PANEL SCHEDULE. |
| | CORRECT THE PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO |
| | MATCH AND ADJUST YOUR CONDUCTORS ACCORDINGLY. |
| | EVERYTHING INDICATED ABOVE HAS A BEARING ON THE ACTUAL |
| | LOADS AND CONDUCTOR APPLICATION. REVISE THE PLANS AND |
| | THE LOAD CALCULATIONS TO MATCH. CORRECT THE CONDUCTORS |
| | ACCORDINGLY AND RESUBMIT. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |