Plan Review Details - Permit 15071074
Plan Review Stops For Permit 15071074
Review Stop E ELECTRICAL
Rev No 2 Status N Date 2015-08-06 Cont ID  
Sent By albarran Date 2015-08-06 Time 11:54 Rev Time 0.00
Received By albarran Date 2015-08-06 Time 11:45 Sent To  
Notes
2015-08-06 11:56:04THIS REVIEW ENTRY IS DUE TO A DOCUMENT I RECEIVED FROM
 MR. KURT GREEFF VIA STRYKER ELECTRIC CHALLENGING THE
 PERMIT DENIAL. I FORWARDED THE EMAIL TO CHRIS COLE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-30 Cont ID  
Sent By albarran Date 2015-07-30 Time 12:12 Rev Time 0.00
Received By albarran Date 2015-07-30 Time 11:51 Sent To I
Notes
2015-07-30 12:18:50HAD THIS APPLICATION BEEN APPROVED BY MECHANICAL THE
 FOLLOWING COMMENTS COULD HAVE BEEN ADDRESS VIA
 PROVISOS, BUT SINCE THERE ARE MAJOR CORRECTIONS
 REQUIRED FOR THE MECHANICAL REVIEW. I DIDN'T THINK TO
 BE DAMAGING TO GET THE CORRECTIONS ADDRESSED ON THE
 SUBMITTAL.
  
 1. PER FBC STANDARDS THE ADDITION OF THIS UNIT TO THE
 GARAGE CONVERTS THE SPACE INTO CONDITIONED HABITABLE
 SPACE, WHICH MAY REQUIRE ADDITIONAL ITEMS SUCH AS HEAT
 AND PROPER OUTLET PLACEMENT.
 2. PER NEC 2011 SECTION 300.9, CONDUCTORS INSIDE OF ANY
 EXPOSED EXTERIOR RACEWAY SHALL BE LISTED FOR WET
 LOCATION.
 3. PER NEC 210.63, A SERVICE OUTLET IS REQUIRED WITHIN
 25' OF CONDENSING UNIT.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  
2015-07-30 10:15:34ROUTED TO ELECTRICAL/CC

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-30 Cont ID  
Sent By albarran Date 2015-07-30 Time 12:19 Rev Time 0.00
Received By albarran Date 2015-07-28 Time 16:20 Sent To  
Notes
2015-07-30 12:31:157/30/15 - FAILED ELECTRICAL REVIEW AS WELL AS THE
 MECHANICAL. CONTRACTOR NOTIFIED VIA EMAIL. SENT TO
 SMALL DENIED BIN "S". MA
2015-07-28 16:20:39ROUTED TO MECHANICAL $5000 & UNDER

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-30 Cont ID  
Sent By ccole Date 2015-07-30 Time 09:20 Rev Time 0.00
Received By ccole Date 2015-07-30 Time 09:20 Sent To  
Notes
2015-07-30 09:22:461ST REVIEW: FBC 2014 MECHANICAL
  
 1) PLEASE REFER TO SECTION R101.4.5 FBC-14 ENERGY
 CONSERVATION, CHANGE IN SPACE CONDITIONING:
 ANY NONCONDITIONED SPACE THAT IS ALTERED TO BECOME
 CONDITIONED SPACE SHALL BE REQUIRED TO BE BROUGHT INTO
 FULL COMPLIANCE WITH THIS CODE.
 REFER TO SECTION R101.5.1 COMPLIANCE MATERIALS.
 THE FLORIDA BUILDING COMMISSION SHALL APPROVE SPECIFIC
 COMPUTER SOFTWARE, WORKSHEETS, COMPLIANCE MANUALS AND
 OTHER SIMILAR MATERIALS THAT MEET THE INTENT OF THIS
 CODE. COMMISSION APPROVED CODE COMPLIANCE DEMONSTRATION
 FORMS CAN BE FOUND IN TABLE R101.5.1.
  
 TABLE R101.5.1 INDEX TO CODE COMPLIANCE
  
 FORM R402
 FLORIDA RESCHECK COMPUTER PRINTOUT
 FORM R405 (COMMISSION APPROVED SOFTWARE PRINTOUT)
 APPENDIX C
  
 R101.5.1.1 RESIDENTIAL BUILDINGS THREE STORIES OR LESS.
 R101.5.1.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE CODE OFFICIAL TO DEMONSTRATE
 CODE COMPLIANCE BY THIS METHOD. ALTERNATIVELY, A
 FLORIDA RESCHECK COMPUTER PRINTOUT MAY BE SUBMITTED TO
 DEMONSTRATE COMPLIANCE BY SECTIONS R402, R403 AND R404.
 R101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE)
 DEMONSTRATING THAT CODE COMPLIANCE HAS BEEN ACHIEVED
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL FOR
 COMPLIANCE BY SECTION R405.
  
 PLEASE CHOOSE EITHER THE PRESCRIPTIVE OR PERFORMANCE
 BASED COMPLIANCE PATH AS INDICATED ABOVE, AND SUBMIT
 THE COMPLIANCE FORMS IN DUPLICATE. PLEASE NOTE
 MODIFICATIONS TO THE GARAGE STRUCTURE, THERMAL
 ENVELOPE, AND MEP SYSTEMS MAY BE REQUIRED TO MEET
 COMPLIANCE, THEREFORE REVISED PLANS MUST BE SUBMITTED.
  
 2) THE SUBMITTED RHEEM DESIGN STAR AC LOAD CALCULATION
 PROGRAM IS INTENDED FOR USE WITH RHEEM PRODUCTS ONLY.
 PLEASE SUBMIT A SIZING CALCULATION IN ACCORDANCE WITH
 ACCA MANUAL J- REFER TO SECTION R403.6.1 FBC-14 ENERGY
 CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  