Plan Review Details - Permit 15071060
Plan Review Stops For Permit 15071060
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-08-06 Cont ID  
Sent By albarran Date 2015-08-06 Time 12:54 Rev Time 0.00
Received By albarran Date 2015-08-06 Time 12:54 Sent To I
Notes
2015-08-06 12:56:11I DISCUSSED THIS WITH WESLEY JOLIN; HE EXPLAINED THAT
 THOUGHT IT HAD BEEN LABELED AS A FIRE ALARM ON THE
 PLANS, THE INTENT OF THIS INSTALLATION IS JUST TO
 MONITOR THE SPRINKLER SYSTEM. THEREFORE A SINGLE
 NOTIFICATION DEVICE IS ADEQUATE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-05 Cont ID  
Sent By albarran Date 2015-08-05 Time 18:27 Rev Time 0.00
Received By albarran Date 2015-08-05 Time 16:10 Sent To I
Notes
2015-08-05 18:15:55ACCORDING TO NFPA 72 TABLE 18.5.4.3.1(A) ADDITIONAL
 NOTIFICATION APPLIANCES ARE REQUIRED. THE ADDITIONAL
 APPLIANCE WILL AFFECT THE RISER DIAGRAM AS WELL AS ALL
 YOUR CALULATIONS,

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-07-31 Cont ID  
Sent By Lindow Date 2015-07-31 Time   Rev Time  
Received By   Date 2015-07-31 Time   Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-06 Cont ID  
Sent By albarran Date 2015-08-05 Time 18:27 Rev Time 0.00
Received By albarran Date 2015-07-29 Time 10:18 Sent To  
Notes
2015-08-06 12:58:098/6/15 - COMPLETED THE EXPEDITED REVIEW AS REQUESTED.
 ELECTRICAL APPROVED AS NOTED. CONTRACTOR NOTIFIED VIA
 PHONE CALL. SENT TO SMALL READY BIN "A". MA
2015-07-29 10:19:32FIRE BOX