Plan Review Details - Permit 15071022
Plan Review Stops For Permit 15071022
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-03-07 Cont ID  
Sent By jgomez Date 2016-03-07 Time 07:57 Rev Time 0.00
Received By jgomez Date 2016-03-07 Time 07:45 Sent To  
Notes
2016-03-07 08:04:16 
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-12-21 Cont ID  
Sent By jgomez Date 2015-12-17 Time 17:24 Rev Time 0.00
Received By jgomez Date 2015-12-17 Time 17:04 Sent To  
Notes
2015-12-17 17:29:51RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 NOTE: THE COMMENTS BELOW MAY BE APPROVED WITH PROVISO.
 REVISION FEES MAY APPLY. CONTRACTOR TO ADVICE IF
 PROVISO OPTION IS PREFERRED OR IF RE-SUBMITTING
 REQUIRED INFORMATION BEFORE ISSUING THE PERMIT.
  
  
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 811
 OF FBC-EXISTING BUILDING, 5TH EDITION (2014).
 NOTE: PLEASE COORDINATE ENERGY CALCULATIONS WITH PLANS
 SUBMITTED TO AVOID CONFLICTS OR DELAYS.
 (10/1/15 GOT CONFIRMATION FROM FRIEDERIKE MITTNER. THIS
 IS A CONTRIBUTING HISTORIC BUILDING. THEREFORE ENERGY
 CALCULATIONS ARE NOT REQUIRED.
 CALLED CONTRACTOR PAUL NEWMAN TO NOTIFY HIM ABOUT THE
 ENERGY CALCULATIONS).
  
 RESPONSE: ENERGY CALCULATIONS WERE SUBMITTED ANYWAY.
 ENERGY CALCULATIONS NEED NO TO BE SUBMITTED BECAUSE THE
 HOUSE A A TRUE CONTRIBUTING HISTORIC HOUSE. IF
 CONTRACTOR WANTS TO SUBMITTED THEM, THEN THEY NEED TO
 BE CORRECT. REVISE THE FOLLOWING:
 A) REVISE ITEM #1. THIS IS EXISTING BUILDING NOT NEW
 CONSTRUCTION. SEC. R101.5.1.1.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 B) REVISE ITEM #10. R-VALUE TO MATCH PLANS. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) REVISE THE ROOF TYPE SHOWN ON PAGE 2 OF 4. SEE PLANS
 AND REVISE AS REQUIRED. THE ROOF TYPE IS NOT HIP. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 D) CLARIFY WHY THE CEILING R-VALUE ON PAGE 2 OF 4 IS
 0.1. SEE ITEM #10 ON COVER PAGE AND ARCHITECTURAL
 PLANS. REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.2
 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 E) DOOR ORIENTATION ON PAGE 3 OF 4 IS INCORRECT. SEE
 PLANS/SURVEY AND REVIEW AS REQUIRED. SEC. R101.5.1.1.2
 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 F) WINDOWS ORIENTATION ON PAGE 3 OF 4 IS INCORRECT. SEE
 PLANS AND SURVEY AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 G) COMPLETE THE AIR BARRIER AND INSULATION INSPECTION
 SHEET. SEC R405.4.2 OF FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014)
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON-THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING
 THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) PROPOSED ROOF SHINGLES AS SPECIFIED ON THE
 ARCHITECT'S PLANS.
  
 RESPONSE: PRODUCT APPROVAL WAS NOT SUBMITTED.
  
 B) EXTERIOR SWING DOOR THAT MATCHES DOOR #2 SPECIFIED
 BY THE ARCHITECT. AND NEED TO PROVIDE PRODUCT APPROVAL
 FOR THE CURRENT CODE VERSION 2014. FL15210-R4 SUBMITTED
 IS FOR 2010 CODE VERSION.
  
 RESPONSE: PRODUCT APPROVAL WAS NOT SUBMITTED.
  
 3- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. COORDINATE WITH ITEM #1 ABOVE AND REVISE
 VALUATION AS REQUIRED.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-22 Cont ID  
Sent By jgomez Date 2015-09-22 Time 11:28 Rev Time 0.00
Received By jgomez Date 2015-09-22 Time 07:56 Sent To  
Notes
2015-09-22 11:30:05RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC-5TH EDITION (2014).
  
 1- SCOPE OF WORK IS NOT CLEAR. THERE ARE TWO DIFFERENT
 SETS OF PLANS WITH TWO DIFFERENT DESIGN PROFESSIONALS
 (ONE ARCHITECT AND ONE ENGINEER) AND SCOPE OF WORK IS
 NOT CLEAR. ALSO, THERE IS A PERMIT APPLICATION FOR
 INTERIOR DEMOLITION FOR WHICH THE SCOPE OF WORK WAS NOT
 CLEAR EITHER. A PRE-INSPECTION IS REQUESTED AT THIS
 TIME TO HELP DETERMINE THE ACTUAL SCOPE OF WORK. THEN,
 PROVIDE ONLY ONE COMPLETE SET OF PLANS THAT DESCRIBES
 ALL THE SCOPE OF WORK TO BE PERFORMED AND PROVIDE
 COMPLETE EVALUATION AS REQUIRED BY SEC. 606.2.2.1 OF
 FBC-EXISTING BUILDING, 5TH EDITION (2014). SEC. 107.2.1
 CITY AMENDMENTS.
 NOTE: ALL STRUCTURAL CONNECTORS SPECIFIED FOR THE
 WALLS, INCLUDING THE GABLE END WALLS NEED TO BE
 DESIGNED TO TRANSFER ALL LOADS AS REQUIRED BY SEC.
 R601.2 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 2- ARCHITECT'S SET OF PLANS SUBMITTED. (THIS WAS THE
 SET OF PLANS THAT WAS REVIEWED. IT REFERENCES THE
 CURRENT CODE IN EFFECT AND LOOKS MORE COMPLETE).
 A) THE ADDRESS SHOWN ON THE TITLE BLOCK IS INCORRECT.
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) THERE IS A CONFLICT WITH THE INFORMATION SHOWN ON
 THE TYPICAL WALL SECTION AND THE INFORMATION SHOWN ON
 THE STRUCTURAL WOOD NOTES. WALL SECTION CALLS FOR
 ICYNENE INSULATION, WHILE STRUCTURAL NOTES CALL FOR 20"
 X 7" SOFFIT VENTS. REVISE AS REQUIRED TO COMPLY WITH
 SEC. R806 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 CLARIFY IF DESIGNING A VENTED OR UNVENTED ATTIC.
  
 C) IF USING ICYNENE, THEN PROVIDE CURRENT ICC
 EVALUATION REPORT SHOWING COMPLIANCE WITH SEC. R316.
 ICC ESR-3210 REPORT SUBMITTED IS EXPIRED AND IS FOR
 ANOTHER TYPE OF INSULATION NOT ICYNENE AS SPECIFIED BY
 THE ARCHITECT. IN ADDITION IT WAS REVIEWED/APPROVED BY
 ANOTHER ENGINEER WHICH DOESN'T HAVE ANY RESPONSIBILITY
 IN THIS PROJECT.
  
 D) DESIGN PRESSURES FOR OPENINGS: REVISE THE DISTANCE
 FROM THE CORNERS FOR ZONE 4 AND 5. NOTE "A" ON FIGURE
 R301.2(7) REQUIRES THE DISTANCE TO BE 4 FEET IN ALL
 CASES NOT 3 FEET . REVISE AS REQUIRED.
  
 3- ENGINEER'S SET OF PLANS WAS NOT REVIEWED. IT DIDN'T
 REFERENCED THE CURRENT CODE IN EFFECT AND IS MISSING A
 LOT OF INFORMATION THE ARCHITECTURAL PLANS ARE
 PROVIDING. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 811
 OF FBC-EXISTING BUILDING, 5TH EDITION (2014).
 NOTE: PLEASE COORDINATE ENERGY CALCULATIONS WITH PLANS
 SUBMITTED TO AVOID CONFLICTS OR DELAYS.
 (10/1/15 GOT CONFIRMATION FROM FRIEDERIKE MITTNER. THIS
 IS A CONTRIBUTING HISTORIC BUILDING. THEREFORE ENERGY
 CALCULATIONS ARE NOT REQUIRED.
 CALLED CONTRACTOR PAUL NEWMAN TO NOTIFY HIM ABOUT THE
 ENERGY CALCULATIONS).
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) PROPOSED ROOF SHINGLES AS SPECIFIED ON THE
 ARCHITECT'S PLANS.
  
 B) EXTERIOR SWING DOOR THAT MATCHES DOOR #2 SPECIFIED
 BY THE ARCHITECT. AND NEED TO PROVIDE PRODUCT APPROVAL
 FOR THE CURRENT CODE VERSION 2014. FL15210-R4 SUBMITTED
 IS FOR 2010 CODE VERSION.
  
 C) SINGLE HUNG WINDOWS. INFORMATION SUBMITTED DOESN'T
 HAVE THE FLORIDA PRODUCT APPROVAL NUMBER. PROVIDE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO
 DRAWINGS SUBMITTED AND MAKE SURE THE PRODUCT APPROVAL
 IS FOR THE 2014 CODE VERSION.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR DESIGN
 PROFESSIONAL TO LIST THE FLORIDA PRODUCT APPROVAL
 NUMBER NEXT TO THE SPECIFIED CONNECTOR.
  
 6- DESIGN PROFESSIONAL OF RECORD TO APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 7- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. COORDINATE WITH ITEM #1 ABOVE AND REVISE
 VALUATION AS REQUIRED.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2016-03-29 Cont ID  
Sent By albarran Date 2016-03-29 Time 09:27 Rev Time 0.00
Received By albarran Date 2016-03-29 Time 09:12 Sent To I
Notes
2016-03-29 09:28:07OCEAN ELECTRIC BROUGHT IN THE REQUIRED DOCUMENTATION
 AND PERMIT WAS APPROVED.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2016-03-23 Cont ID  
Sent By albarran Date 2016-03-23 Time 14:46 Rev Time 0.00
Received By albarran Date 2016-03-23 Time 14:26 Sent To  
Notes
2016-03-23 15:48:135TH ELECTRICAL REVIEW NOTES FOR REVISION #:15071022
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 THOUGH I SPOKE WITH MR. KERRY THE GC AND EXPLAINED TO
 HIM WHAT WAS REQUIRED (I READ VERBATIM THE WORDING OF
 THE PREVIOUS REVIEW (#4 SINCE THERE HAVE BEEN MANY
 DIFFERENT OPTIONS BROUGHT TO THE TABLE FOR
 DISCUSSION/APPROVAL, I DO NOT KNOW WHICH IS THE ONE
 ACCEPTED. THEREFORE I ASKED FOR A SITE SPECIFIC DRAWING
 OF WHAT IS THERE NOW AS WELL AS AN INDICATION OF WHAT
 IS TO BE THE PROPOSED FINISHED PRODUCT. THESE DRAWINGS
 ARE TO BE SUBMITTED FOR APPROVAL AND ISSUANCE OF
 ELECTRICAL PERMIT. )) WE AGREED ON WHAT WAS TO BE DONE.
 YESTERDAY SOMEONE CAME TO THE OFFICE TO SUBMIT A SINGLE
 RISER DIAGRAM THAT INCLUDES ONLY PART OF THE SERVICE
 WITH NO SITE PLAN OR SCOPE OF WORK. LOAD CALCS ARE
 REQUIRED AS WELL. PER WPB CITY AMENDMENTS TO THE FBC
 THE SCOPE OF WORK ALONG WITH THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DRAWING SHALL APPEAR ON
 THE PLANS WITH THE ADDRESS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2016-03-21 Cont ID  
Sent By jgomez Date 2016-03-21 Time 14:21 Rev Time 0.00
Received By albarran Date 2016-03-21 Time 13:37 Sent To  
Notes
2016-03-21 14:19:34TODAY I SPOKE W/KERRY THE NEW GC ON THE JOB TO DISCUSS
 HOW TO PROCEED. SINCE THERE HAVE BEEN MANY DIFFERENT
 OPTIONS BROUGHT TO THE TABLE FOR DISCUSSION, I DO NOT
 KNOW WHICH IS THE ONE ACCEPTED. THEREFORE I ASKED FOR A
 SITE SPECIFIC DRAWING OF WHAT IS THERE NOW AS WELL AS
 AN INDICATION OF WHAT IS TO BE THE PROPOSED FINISHED
 PRODUCT. THESE DRAWINGS ARE TO BE SUBMITTED FOR
 APPROVAL AND ISSUANCE OF ELECTRICAL PERMIT.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-01-14 Cont ID  
Sent By albarran Date 2016-01-14 Time 16:05 Rev Time 0.00
Received By albarran Date 2016-01-14 Time 15:10 Sent To  
Notes
2016-01-14 15:38:05YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED
 DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL
 REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED
 BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO
 SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE
 REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION
 OF ANY PREVIOUS COMMENTS.
  
 1. YOU SHALL PROVIDE A SITE PLAN INDICATING THE
 LOCATION OF THE MAIN SERVICE TO THE RESIDENCE. THOUGH
 ZONING HAS PERMITTED THE SECOND METER, BOTH FPL & THE
 NATIONAL ELECTRICAL CODE RESTRICT THE DROPS TO ONE PER
 LOT. IT IS NOT MY INTENT TO DESIGN YOUR SERVICE, BUT I
 CAN RECOMMEND THAT YOU MODIFY THE EXISTING SERVICE AND
 ADD A TWO GANG METER SOCKET WITH A MAIN FOR THE COTTAGE
 AND PROCEED FROM THERE TO THE REAR PANEL. PLEASE MAKE
 CERTAIN TO INCLUDE A PROPER GROUND FOR THE DETACHED
 STRUCTURE.
 2. A LAUNDRY CIRCUIT WILL NOT BE REQUIRED FOR THE
 COTTAGE UNLESS IT IS TO BE A SEPARATE DWELLING.
 THEREFORE, IF METERED SEPARATELY, A LAUNDRY CIRCUIT
 SHALL BE PROVIDED.
 3. PER FBC-R 303.9, YOU SHALL PROVIDE HEAT CAPABLE OF
 MAINTAINING 68 DEGREES F, THREE FT. ABOVE THE FLOOR
 ETC. REVISE YOUR HVAC AND LOAD CALCS ACCORDINGLY.
 5. CORRECT YOUR LOAD CALCS TO INCLUDE THE REQUIRED HEAT
 AND LAUNDRY CIRCUIT IF APPLICABLE. FIGURE THE LOADS AS
 PER NEC 220.83.
  
 THE REST CAN BE ADDRESSED WITH NOTES ON THE PLANS.
 4. NEC 406.12 REQUIRES THAT ALL 15 & 20 AMP NON?LOCKING
 RECEPTACLES IN DWELLING UNITS BE TAMPER?RESISTANT.
 6. NEC 314.27(A)(2), CEILING OUTLET BOXES SHALL BE
 LISTED TO SUPPORT A MINIMUM OF 50LBS.
 7. NEC 314.27(C) REQUIRES THAT CEILING BOXES USED TO
 SUPPORT CEILING FANS BE LISTED AND MARKED FOR THE
 PURPOSE.
 8. NEC 406.12 REQUIRES THAT 15 & 20 AMP RECEPTACLES IN
 WET LOCATIONS (OUTDOORS) BE LISTED WEATHER RESISTANT,
 "WR".
 9. FBC-R SECTION 314 REQUIRES THAT YOU INSTALL SMOKE
 DETECTORS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE?SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-12-28 Cont ID  
Sent By albarran Date 2015-12-28 Time 14:19 Rev Time 0.00
Received By albarran Date 2015-12-28 Time 13:49 Sent To I
Notes
2015-12-28 14:52:41YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED
 DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL
 REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED
 BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO
 SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE
 REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION
 OF ANY PREVIOUS COMMENTS.
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE
 EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE) AND THE
 FBC, (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF
 WEST PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL.
 0- YOU FAILED TO PROVIDE A RESPONSE LETTER ADDRESSING
 THE ELECTRICAL DEFICIENCIES.
 1- YOU SHALL PROVIDE THE REQUESTED SITE PLAN MARKED
 WITH THE LOCATION OF THE ELECTRICAL SERVICE DROP, THE
 EXISTING SERVICE EQUIPMENT AND ANY PROPOSED NEW WORK TO
 THE SERVICE AND/OR EQUIPMENT. INCLUDE ALL SERVICE
 DISCONNECTS AS WELL. THIS IS TO ASCERTAIN COMPLIANCE
 WITH NEC 230.2
 2- NOT REQUIRED FOR THE COTTAGE.
 3? 5 SATISFACTORILY ADDRESSED.
 6? 9 YOU FAILED TO ADDRESS THE NOTED DEFICIENCIES.
 CORRECT THE PLANS ACCORDINGLY
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-09-16 Cont ID  
Sent By albarran Date 2015-09-16 Time 16:10 Rev Time 0.00
Received By albarran Date 2015-09-16 Time 14:22 Sent To  
Notes
2015-09-16 16:13:04PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. YOU SHALL PROVIDE A SITE PLAN INDICATING THE
 LOCATION OF THE MAIN SERVICE TO THE RESIDENCE. THOUGH
 ZONING HAS PERMITTED THE SECOND METER, NEC 230.2 ONLY
 PERMITS A SINGLE SERVICE PER STRUCTURE, AND FPL WILL
 GENERALLY ONLY HAVE A SINGLE DROP PER PROPERTY.
 2. WHETHER YOU USE IT OR NOT, NEC 210.11(C) & 210.52(F)
 REQUIRE THAT YOU HAVE A DEDICATED LAUNDRY CIRCUIT.
 PROVIDE ONE ACCORDINGLY.
 3. PER FBC-R 303.9, YOU SHALL PROVIDE HEAT CAPABLE OF
 MAINTAINING 68?F THREE FT. ABOVE THE FLOOR ETC. REVISE
 YOUR HVAC AND LOAD CALCS ACCORDINGLY.
 4. NEC 406.12, REQUIRES THAT ALL 15 & 20 AMP
 NON-LOCKING RECEPTACLES IN DWELLING UNITS BE
 TAMPER-RESISTANT.
 5. CORRECT YOUR LOAD CALCS TO MATCH PANEL SCHEDULE.
 FIGURE THE LOADS AS PER NEC 220.83.
 6. NEC 314.27(A)(2), CEILING OUTLET BOXES SHALL BE
 LISTED TO SUPPORT A MINIMUM OF 50LBS.
 7. NEC 314.27(C), REQUIRES THAT CEILING BOXES USED TO
 SUPPORT CEILING FANS BE LISTED AND MARKED FOR THE
 PURPOSE.
 8. NEC 406.12, REQUIRES THAT 15 & 20 AMP RECEPTACLES IN
 WET LOCATIONS (OUTDOORS) BE LISTED WEATHER RESISTANT,
 ?WR?.
 9. FBC-R SECTION 314, REQUIRES THAT YOU INSTALL SMOKE
 DETECTORS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-12-11 Cont ID  
Sent By fmittner Date 2015-12-11 Time 15:02 Rev Time 0.00
Received By fmittner Date 2015-12-11 Time 15:02 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-08-21 Cont ID  
Sent By fmittner Date 2015-08-21 Time 16:36 Rev Time 0.00
Received By fmittner Date 2015-08-21 Time 16:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-03-29 Cont ID  
Sent By albarran Date 2016-03-29 Time 09:28 Rev Time 0.00
Received By albarran Date 2016-03-22 Time 11:17 Sent To  
Notes
2016-03-29 09:29:273/29/16 PASSED ELECTRICAL REVIEW AS NOTED. OCEAN
 ELECTRIC WAITED FOR PERMIT. SENT FILE TO SP. MA
2016-03-22 11:18:12RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-22 Cont ID  
Sent By lmarchan Date 2016-03-22 Time 11:17 Rev Time 0.00
Received By lmarchan Date 2016-02-08 Time 14:37 Sent To  
Notes
2016-02-08 14:38:02RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-12 Cont ID  
Sent By skennedy Date 2015-12-28 Time 15:22 Rev Time 0.00
Received By skennedy Date 2015-12-02 Time 10:20 Sent To  
Notes
2015-12-02 10:21:01R02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-22 Cont ID  
Sent By jgomez Date 2015-09-22 Time 13:37 Rev Time 0.00
Received By jgomez Date 2015-07-27 Time 14:31 Sent To  
Notes
2015-08-12 08:04:57R05

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-03-07 Cont ID  
Sent By jgomez Date 2016-03-07 Time 09:40 Rev Time 0.00
Received By jgomez Date 2016-03-07 Time 09:40 Sent To E
Notes
2016-03-07 09:50:50 
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-12-21 Cont ID  
Sent By jgomez Date 2015-12-21 Time 12:55 Rev Time 0.00
Received By jgomez Date 2015-12-21 Time 12:55 Sent To E
Notes
2015-12-21 13:05:56 
 RESIDENTIAL (R3) ALTERATION, SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 NOTE: THE COMMENTS BELOW MAY BE APPROVED WITH PROVISO.
 REVISION FEES MAY APPLY. CONTRACTOR TO ADVICE IF
 PROVISO OPTION IS PREFERRED OR IF RE-SUBMITTING
 REQUIRED INFORMATION BEFORE ISSUING THE PERMIT.
  
 1- REVISE THE EQUIPMENT SIZING CALCULATIONS.
 A) WINDOW ORIENTATION IS INCORRECT. SEE PLANS AND
 SURVEY AND REVISE AS REQUIRED. CALCULATIONS NEED TO BE
 DONE FOR THE ACTUAL ORIENTATION OF THE BUILDING AS
 REQUIRED BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 B) CENTRAL UNIT SPECIFIED ON PAGE 3 IS OVERSIZED. THIS
 IS NOT ALLOWED BY SEC. R403.6.1.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 2- PROVIDE A/C PLAN WITH THE FOLLOWING INFORMATION:
 A) NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) EQUIPMENT LOCATION, MANUFACTURER AND MODEL NUMBER.
 SEC. 107.3.5.3(10) CITY AMENDMENTS.
 NOTE: EQUIPMENT TO MATCH EQUIPMENT SIZING CALCULATIONS
 AND ENERGY CALCULATIONS SUBMITTED.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSIGN EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-09-22 Cont ID  
Sent By jgomez Date 2015-09-22 Time 13:37 Rev Time 0.00
Received By jgomez Date 2015-09-22 Time 13:37 Sent To  
Notes
2015-09-22 13:44:15RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC-5TH EDITION (2014).
  
 1- PROVIDE HEATING AND COOLING EQUIPMENT SIZING
 CALCULATIONS SHOWING COMPLIANCE WITH ALL THE
 REQUIREMENTS OF SEC. R403.6.1 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-12-08 Cont ID  
Sent By tklarge Date 2015-12-08 Time 06:14 Rev Time 0.00
Received By tklarge Date 2015-12-08 Time 05:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-09-17 Cont ID  
Sent By tklarge Date 2015-08-03 Time 06:20 Rev Time 0.00
Received By tklarge Date 2015-08-03 Time 06:11 Sent To  
Notes
2015-09-17 06:56:29THERE IS A SET OF PLANS IN THE SUBMITTAL PACKAGE FOR
 1409 GEORGIA AVENUE AND ANOTHER SET OF PLANS WITH AN
 ADDRESS OF 1401 GEORGIA AVENUE. CLARIFY.

Review Stop Z ZONING
Rev No 2 Status P Date 2015-12-11 Cont ID  
Sent By fmittner Date 2015-12-11 Time 15:01 Rev Time 0.00
Received By fmittner Date 2015-12-11 Time 15:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-08-21 Cont ID  
Sent By fmittner Date 2015-08-21 Time 16:36 Rev Time 0.00
Received By fmittner Date 2015-08-21 Time 16:36 Sent To  
Notes
***NONE***