Plan Review Details - Permit 15070942
Plan Review Stops For Permit 15070942
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-08-06 Cont ID  
Sent By jwitmer Date 2015-08-06 Time 13:05 Rev Time  
Received By jwitmer Date 2015-08-06 Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-10-16 Cont ID  
Sent By skennedy Date 2015-10-16 Time 13:04 Rev Time 0.00
Received By skennedy Date 2015-10-16 Time 12:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-21 Cont ID  
Sent By skennedy Date 2015-08-21 Time 13:38 Rev Time 0.00
Received By skennedy Date 2015-08-21 Time 13:38 Sent To  
Notes
2015-08-21 13:42:211ST REVIEW: FBC 2014 5TH ED. NEC 2011
  
 SHEET E-4 PLEASE IDENTIFY THE CONDUIT & CONDUCTOR TYPE
 AND SIZE FROM MDP TO PANEL DD, IDENTIFY GRND, VERIFY
 ADEQUATE CAPACITY FOR ADDED LOAD OF PANE DD..
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-23 Cont ID  
Sent By scaldero Date 2015-09-23 Time 15:45 Rev Time 0.00
Received By scaldero Date 2015-09-23 Time 15:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-07-30 Cont ID  
Sent By scaldero Date 2015-07-30 Time 17:06 Rev Time 0.00
Received By scaldero Date 2015-07-30 Time 16:58 Sent To  
Notes
2015-07-30 17:05:19PERMIT #15070942
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED:
 THE CURRENT LOCATION OF THE EGRESS PATH EXIT DOOR FOR
 THE DUNKIN DONUTS WORK AREA AND THE DOOR FOR THE
 RESTROOM OPEN INTO EACHOTHER, CREATING A POSSIBLE
 OBSTRUCTION FOR PERSONS ON BOTH SIDES. THIS
 CONFIGURATION NEEDS TO BE REVIEWED AND AN ALTERNATIVE
 OR SOLUTION PROVIDED.
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-10-29 Cont ID  
Sent By ccole Date 2015-10-29 Time 09:52 Rev Time 0.00
Received By ccole Date 2015-10-28 Time 14:59 Sent To  
Notes
2015-10-28 14:59:35RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-21 Cont ID  
Sent By tklarge Date 2015-10-21 Time 12:38 Rev Time 0.00
Received By tklarge Date 2015-10-19 Time 13:27 Sent To  
Notes
2015-10-20 13:27:56RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-16 Cont ID  
Sent By skennedy Date 2015-10-16 Time 13:04 Rev Time 0.00
Received By skennedy Date 2015-09-18 Time 11:15 Sent To  
Notes
2015-09-21 11:15:31B21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-21 Cont ID  
Sent By skennedy Date 2015-08-21 Time 13:42 Rev Time 0.00
Received By skennedy Date 2015-07-23 Time 07:59 Sent To  
Notes
2015-07-24 08:01:51B29

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-10-29 Cont ID  
Sent By ccole Date 2015-10-29 Time 09:53 Rev Time 0.00
Received By ccole Date 2015-10-29 Time 09:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-10-21 Cont ID  
Sent By ccole Date 2015-10-21 Time 06:58 Rev Time 0.00
Received By ccole Date 2015-10-21 Time 06:58 Sent To  
Notes
2015-10-21 07:02:253RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070942
 10/21/15
  
 1) M-1: THE REVISED AIR BALANCE SCHEDULE INDICATES A
 DEFICIENT AMOUNT OF O/A CFM'S FOR OCCUPANTS BASED ON
 THE REVISED O/A CALCULATIONS AND TABLE 403.3 FBC-14
 MECHANICAL- 675 CFM REQUIRED/550 PROVIDED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-10-06 Cont ID  
Sent By ccole Date 2015-10-06 Time 14:10 Rev Time 0.00
Received By ccole Date 2015-10-06 Time 13:57 Sent To  
Notes
2015-10-06 14:27:441ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070942
 10/6/15
  
 1) M-1: THE OUTSIDE AIR CALCULATIONS ARE NOT IN
 COMPLIANCE WITH ASHRAE 62.1 OR TABLE 403.3 FBC-14
 MECHANICAL. EACH TABLE REQUIRES A RATE OF 7.5 CFM PER
 OCCUPANT PLUS 0.18 CFM PER SQ. FT FOR CAFETERIA/FAST
 FOOD. PLEASE REVISE THE CALCULATIONS.
 2) M-1: THE AIR BALANCE SCHEDULE MUST INDICATE HOW MUCH
 OF THE O/A IS BEING PROVIDED FOR OCCUPANTS AND HOW MUCH
 FOR MAKE-UP AIR FOR THE EXHAUST SYSTEMS. PLEASE NOTE
 THAT MAKE UP AIR CFM'S SHALL BE APPROXIMATELLY EQUAL TO
 REQUIRED EXHAUST CFM'S- SECTION 508.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-18 Cont ID  
Sent By ccole Date 2015-08-18 Time 09:51 Rev Time 0.00
Received By ccole Date 2015-08-18 Time 09:51 Sent To  
Notes
2015-08-20 09:39:01ON SKENNEDY'S DESK
2015-08-18 09:55:271ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070942
 8/18/15
  
 1) REFER TO THE FBC-14 EXISITNG BUILDING CODE. PLEASE
 ADD THE CODE TO THE DESIGN CODES LIST ON SHEET CS-1 AND
 SEE SECTION 809.2- ALTERED EXISTING SYSTEMS.
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62.1. PLEASE PROVIDE AN OUTSIDE AIR
 CALCULATION AND SCHEDULE ON THE PLAN INDICATING THE
 REQUIRED O/A AND THE O/A PROVIDED.
 2) THE CITY OF WEST PALM BEACH DEVELOPMENT SERVICES
 DEPARTMENT REQUIRES A SEPARATE PERMIT FOR ALL KITCHEN
 HOOD INSTALLATIONS. PLEASE PLACE A NOTE ON THE PLANS
 ACCORDINGLY.
 IN REFERENCE TO THIS PERMIT SET OF PLANS IT IS
 NECESSARY TO INDICATE HOW MAKE-UP AIR IS BEING PROVIDED
 FOR THE NEW EXHAUST HOOD TO VERIFY PROPER AIR BALANCING
 WITHIN THE ALTERED SPACE- REFER TO SECTION 508 FBC-14
 MECHANICAL.
 508.1 MAKEUP AIR.
 MAKEUP AIR SHALL BE SUPPLIED DURING THE OPERATION OF
 COMMERCIAL KITCHEN EXHAUST SYSTEMS THAT ARE PROVIDED
 FOR COMMERCIAL COOKING APPLIANCES. THE AMOUNT OF MAKEUP
 AIR SUPPLIED TO THE BUILDING FROM ALL SOURCES SHALL BE
 APPROXIMATELY EQUAL TO THE AMOUNT OF EXHAUST AIR FOR
 ALL EXHAUST SYSTEMS FOR THE BUILDING. THE MAKEUP AIR
 SHALL NOT REDUCE THE EFFECTIVENESS OF THE EXHAUST
 SYSTEM. MAKEUP AIR SHALL BE PROVIDED BY GRAVITY OR
 MECHANICAL MEANS OR BOTH. MECHANICAL MAKEUP AIR SYSTEMS
 SHALL BE AUTOMATICALLY CONTROLLED TO START AND OPERATE
 SIMULTANEOUSLY WITH THE EXHAUST SYSTEM. MAKEUP AIR
 INTAKE OPENING LOCATIONS SHALL COMPLY WITH SECTION
 401.4.
 508.1.1 MAKEUP AIR TEMPERATURE.
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10
 DEGREES F (6 DEGREES C) EXCEPT WHERE THE ADDED HEATING
 AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE
 CAPACITY OF THE HVAC SYSTEM.
  
 PLEASE REVISE THE PLANS TO SHOW COMPLIANCE WITH THE
 CODE SECTIONS ABOVE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2015-10-29 Cont ID  
Sent By tklarge Date 2015-10-29 Time 06:48 Rev Time 0.00
Received By tklarge Date 2015-10-29 Time 06:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-10-21 Cont ID  
Sent By tklarge Date 2015-10-21 Time 12:37 Rev Time 0.00
Received By tklarge Date 2015-10-21 Time 11:41 Sent To  
Notes
2015-10-21 12:26:001) THE WATER RISER DIAGRAM ON SHT.P-2 SHALL SHOW ALL
 THE WATER PIPING TO ALL THE FIXTURES SHOWN ON SHT.P-3
 AND INCLUDE ALL THE PIPE SIZES, BOTH FILTRATION
 SYSTEMS, ETC. WPB AMEND. TO FBC SEC. 107.2.1.
 CLARIFY WHY THERE ARE TWO WATER RISER DIAGRAMS, ONE ON
 P-2 AND ONE ON P-3 AND NEITHER ONE MATCHES THE OTHER.
 SUBMIT ONE WATER RISER DIAGRAM SHOWING ALL THE
 FIXTURES/APPLIANCES CONNECTED THERETO OR SUPPLY BOTH
 WATER RISERS THAT CORRELATE.
 2) YOU HAVE SUBMITTED GREASE TRAP SIZING CALCULATIONS
 BASED ON 4 SEATS. WHERE ARE THE FOUR SEATS COMING FROM
 WHEN THERE ARE NO SEATS SHOWN ON THE PLANS? CLARIFY.
  
 PLEASE CALL ME TO DISCUSS THESE COMMENTS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-10-02 Cont ID  
Sent By tklarge Date 2015-10-02 Time 14:10 Rev Time 0.00
Received By tklarge Date 2015-10-02 Time 11:54 Sent To  
Notes
2015-10-02 14:08:451) THE WATER RISER DIAGRAM ON SHT.P-2 SHALL SHOW ALL
 THE WATER PIPING TO ALL THE FIXTURES SHOWN ON SHT.P-3
 AND INCLUDE ALL THE PIPE SIZES, BOOSTER PUMP, BOTH
 FILTRATION SYSTEMS, ETC. WPB AMEND. TO FBC SEC.
 107.2.1.
 2) SUBMIT SIZING CALCULATIONS TO ENSURE THAT THE
 EXISTING TANK HAS THE CAPACITY TO HANDLE THE ADDITIONAL
 GREASE WASTE. WPB AMEND. TO FBC SEC. 107.2.1., 2014
 FBC-PLUMBING SEC.1003.2. 2ND REQUEST.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-08-08 Cont ID  
Sent By tklarge Date 2015-08-08 Time 05:06 Rev Time 0.00
Received By tklarge Date 2015-08-08 Time 04:12 Sent To  
Notes
2015-08-08 04:58:451) INDICATE THE SIZE OF THE EXISTING GREASE TRAP AND
 SUBMIT SIZING CALCULATIONS TO ENSURE THAT THE EXISTING
 TANK HAS THE CAPACITY TO HANDLE THE ADDITIONAL GREASE
 WASTE. WPB AMEND. TO FBC SEC. 107.2.1., 2014
 FBC-PLUMBING SEC.1003.2.
 2) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 NE W EQUIPMENT USED FOR FOOD PREP/BEVERAGES/ICE CREAM,
 ETC. EQUIPMENT SHALL COMPLY WITH NSF.
 3) SHEETS K-1, K-2, K-3 APPEAR TO HAVE THE COLUMN
 HEADING MISSING. CLARIFY.
 4) SUBMIT A DETAIL FOR THE NEW GREASE WASTE CONNECTION
 TO THE EXISTIN GREASE INTERCEPTOR. COMPLY WITH FL.
 ADMIN. CODE RULE 64E-6 FOR REQUIREMENTS.
 5) THE WATER PIPE SIZES ON THE PIPNG DIAGRAM ON P-3 DO
 NOT CORRELATE WITH THE SIZES ON THE WATER RISER ON P-2.
 CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  