| 2015-10-26 10:44:09 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | TO RESOLVE EXPIRED PERMITS, SUBMIT APPLICATIONS AT THE |
| | BUILDING DIVISION. SUBMIT A RECORDS RESEARCH REQUEST |
| | WITH EACH ONE TO OBTAIN THE PLANS REQUIRED. |
| | |
| | 1. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS. |
| | ALSO INCLUDE THE FOLLOWING INFORMATION: |
| | |
| | A. IF THE WINDOW IS LOCATED IN A BEDROOM, NOTE EXISTING |
| | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR |
| | BEDROOMS, FBC R310, FBC EB 704.1. THE CLEAR OPENING |
| | CANNOT BE REDUCED BY MORE THAN 5%. |
| | |
| | TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION |
| | NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN |
| | HEIGHT: |
| | |
| | STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS |
| | - AWNING, CASEMENT, SINGLE HUNG? |
| | |
| | STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE. |
| | CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE |
| | WINDOW IS FULLY OPEN. |
| | |
| | STATE WHAT THE PROPOSED CLEAR OPENING DIMENSIONS ARE. |
| | THIS CAN BE OBTAINED FROM THE MANUFACTURER. |
| | |
| | B. IMPACT PROTECTION REQUIRED,FBC1609.1.2, FBC R |
| | 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS |
| | ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE |
| | (AVAILABLE IN THE LOBBY AND AT: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/SCHEDULE_FOR_INSTALLATION.PDF |
| | |
| | IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 706.4, |
| | PROVIDE CALCULATIONS. |
| | |
| | 3. A STOP WORK ORDER VIOLATION HAS BEEN ISSUED FOR THIS |
| | PROPERTY. APPLICATION SHOULD ADDRESS THE VIOLATION, |
| | WHICH WAS FOR AN ADDITION INCLUDING WINDOWS. |
| | |
| | 4. FROM PREVIOUS LIST: CONTRACTOR WAS UNDER AN |
| | AGREEMENT 1.5 YEARS AGO TO RESOLVE FIVE EXPIRED PERMITS |
| | A MONTH. RATHER THAN ADDRESSING FIVE A MONTH, SEVERAL |
| | MORE PERMITS ARE NOW IN EXPIRED STATUS. BASED ON THE |
| | CONTRACTOR'S AGREEMENT, ALL EXPIRED PERMITS SHOULD BE |
| | RESOLVED AT THIS TIME. THIS IS NOT THE CASE. |
| | |
| | LICENSE U-17813 HAS 36 EXPIRED PERMITS, 5 REVOKED |
| | (RESOLVED EXPIRED PERMITS) |
| | |
| | LICENSE U-20912 HAS 18 EXPIRED PERMITS (THREE HAVE |
| | EXPIRED SINCE CONTRACTOR'S AGREEMENT TO RESOLVE OLD |
| | EXPIRED PERMITS0, 7 REVOKED). |
| | |
| | CONTRACTOR HAS 56 EXPIRED PERMITS. FAILURE TO RESOLVE |
| | THESE PERMITS WILL RESULT IN A COMPLAINT BEING FILED |
| | AGAINST CONTRACTOR. DUE TO THE FAILURE TO FOLLOW |
| | THROUGH ON THE AGREEMENT, AND THE ISSUE OF ADDITIONAL |
| | PERMITS EXPIRING DURING AFTER CONTRACTOR AGREED TO |
| | RESOLVE EXPIRED PERMITS, CONTRACTOR IS TO RESOLVE AT |
| | LEAST HALF OF THE EXPIRED PERMITS WITHIN 30 DAYS, AND |
| | SUBSTANTIALLY ALL OF THE PERMITS WITHIN 60 DAYS. |
| | |
| | ISSUANCE OF THIS PERMIT (15070876) IS UNRELATED TO |
| | COMMENT #3. THIS PERMIT CAN BE ISSUED TO THIS |
| | CONTRACTOR AFTER COMMENTS ARE ADDRESSED. FAILURE TO |
| | RESOLVE EXPIRED PERMITS WILL RESULT IN A COMPLAINT |
| | AGAINST CONTRACTOR, EVEN IF THIS PERMIT IS ISSUED TO A |
| | DIFFERENT CONTRACTOR. |
| | |
| | |