| 2015-07-27 09:30:19 | RESIDENTIAL (R2) ALTERATION. BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- SOUND INSULATION MATERIAL SUBMITTED: |
| | A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE |
| | DEVELOPED TEST DONE IN ACCORDANCE WITH ASTM E 84 OR UL |
| | 723 AS REQUIRED BY SEC. 720.1 OF FBC 5TH EDITION |
| | (2014). |
| | |
| | B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS |
| | (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS |
| | REQUIRED BY SEC. 1207.2 OF FBC 5TH EDITION (2014). |
| | |
| | NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE |
| | ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT |
| | ACOUSTICAL CEILING. |
| | |
| | C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS |
| | (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS |
| | REQUIRED BY SEC. 1207.3 OF FBC 5TH EDITION (2014). |
| | |
| | NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE |
| | ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT |
| | ACOUSTICAL CEILING. |
| | |
| | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND |
| | CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC. |
| | 109.3 CITY AMENDMENTS. NOTE: PROVIDE COPY OF SIGNED |
| | CONTRACT FOR ALL SCOPE OF WORK TO BE DONE. AND PROVIDE |
| | SKETCH SHOWING AREAS TO HAVE NEW FLOORING AND |
| | DIMENSIONS OF ROOMS. ALSO, SPECIFY TYPE OF FLOORING TO |
| | BE INSTALLED. |
| | |
| | 3- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713 F.S. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |