Plan Review Details - Permit 15070750
Plan Review Stops For Permit 15070750
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-23 Cont ID  
Sent By jwitmer Date 2015-09-23 Time 12:01 Rev Time 0.00
Received By jwitmer Date 2015-09-23 Time 11:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-05 Cont ID  
Sent By jwitmer Date 2015-08-05 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2015-08-05 Time 07:15 Sent To  
Notes
2015-08-05 07:48:22BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15070750
 ADD: 905 N. DIXIE HWY.
 CONT: FLORIDA VENT, INC.
 TEL: (954)294-2793
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUG. 05/2015
 ACTION: DENIED
  
 1) SHEET 1 OF 3 SHOWS THE INSTALATION OF ROOF TOP
 INTAKE AND EXHAUST FANS. THE PLANS SHOW CURB DETAILS
 BUT NO PRODUCT APPROVALS AND FASTENING FOR THE CURB TO
 THE ROOF NOR FROM THE CURB TO FAN UNITS. 2014 FBC-B
 1609.6.4.4.1 COMPONENTS AND CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS ROOF
 TOP INTAKE AND EXHAUST FANS
  
  
 2) 2014 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-10-09 Cont ID  
Sent By ppetty Date 2015-10-09 Time 08:02 Rev Time 0.00
Received By ppetty Date 2015-10-09 Time 07:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-24 Cont ID  
Sent By wjolin Date 2015-09-24 Time 11:33 Rev Time 0.00
Received By wjolin Date 2015-09-24 Time 11:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-07-23 Cont ID  
Sent By Lindow Date 2015-07-21 Time   Rev Time 0.00
Received By wjolin Date 2015-07-21 Time   Sent To M
Notes
2015-07-23 14:28:42HOOD SUPPRESSION PLANS NOT SUBMITTED. WILL NEED
 SEPARATE PERMIT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-11-05 Cont ID  
Sent By skennedy Date 2015-11-05 Time 16:07 Rev Time 0.00
Received By skennedy Date 2015-10-28 Time 09:38 Sent To  
Notes
2015-10-30 09:39:12RESUB ROUTED TO AAPONTE VIA SGRAHAM'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-09 Cont ID  
Sent By ppetty Date 2015-10-09 Time 08:02 Rev Time 0.00
Received By ppetty Date 2015-08-28 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-05 Cont ID  
Sent By   Date 2015-08-05 Time   Rev Time 0.00
Received By cpuell Date 2015-07-20 Time 13:24 Sent To  
Notes
2015-07-23 16:14:26B25
2015-07-20 13:24:43FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-10-19 Cont ID  
Sent By ccole Date 2015-10-19 Time 15:03 Rev Time 0.00
Received By ccole Date 2015-10-19 Time 15:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-08-31 Cont ID  
Sent By ccole Date 2015-08-31 Time 16:18 Rev Time 0.00
Received By ccole Date 2015-08-31 Time 16:18 Sent To  
Notes
2015-08-31 16:46:282ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070750
 8/31/15
  
 1) THE FLORIDA BUILDING CODE FIFTH EDITION (2014)
 MECHANICAL WENT INTO EFFECT ON JUNE 30, 2015: PLEASE
 UPDATE THE 2010 CODE REFERENCE ON SHEET 1, AND UPDATE
 THE PLANS TO BE IN COMPLIANCE.
 2. THE COMBUSTION AIR CALCULATION SHOWN ON SHEET 1 IS
 INCORRECT. PLEASE REVIEW SECTIONS 304.9 & 304.9.3
 FBC-14 FUEL GAS.
 304.9: MECHANICAL COMBUSTION AIR SUPPLY. WHERE ALL
 COMBUSTION AIR IS PROVIDED BY A MECHANICAL AIR SUPPLY
 SYSTEM, THE COMBUSTION AIR SHALL BE SUPPLIED FROM THE
 OUTDOORS AT A RATE NOT LESS THAN 0.35 CUBIC FEET PER
 MINUTE PER 1,000 BTU/H (0.034 M3/MIN PER KW) OF TOTAL
 INPUT RATING OF ALL APPLIANCES LOCATED WITHIN THE
 SPACE.
 304.9.3: COMBINED COMBUSTION AIR AND VENTILATION AIR
 SYSTEM. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR.
 PLEASE REVISE THE PLANS TO SHOW COMPLIANCE.
 3) REVIEW SECTION 508.11 FBC-14 MECHANICAL: MAKE AIR
 TEMPERATURE.
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10
 DEGREES F (6 DEGREES C) EXCEPT WHERE THE ADDED HEATING
 AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE
 CAPACITY OF THE HVAC SYSTEM.
 GIVEN THE FACT THAT THE DRYBULB TEMPERATURE FOR WEST
 PALM BEACH IS 90 DEGREES, PLEASE INDICATE HOW WILL THE
 SUPPLY AIR WILL BE COOLED TO MEET THIS CODE
 REQUIREMENT.
 4) PLEASE PLACE A NOTE ON THE PLAN INDICATING THAT THE
 GAS APPLIANCES AND GAS PIPING WILL BE DONE UNDER A
 SEPARATE PERMIT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-23 Cont ID  
Sent By wjolin Date 2015-07-23 Time 14:28 Rev Time 0.00
Received By ccole Date 2015-07-23 Time 14:09 Sent To  
Notes
2015-07-23 14:16:371ST REVIEW: FBC 2014 MECHANICAL
  
 1) THE CITY OF WEST PALM BEACH BUILDING DIVISION
 REQUIRES FIRE SUPPRESSION PLANS TO BE SUBMITTED WITH
 KITCHEN GREASE HOOD PLANS. PLEASE SUBMIT THE PLANS AND
 SPECIFICATIONS, AND SUB-PERMIT APPLICATION.
 2) THE HOOD SECTION DRAWING ON SHEET 1 INDICATES GAS
 APPLIANCES: PROVIDE A GAS PIPING PLAN, A GAS ISOMETRIC
 DRAWING, AND SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE GAS-FIRED APPLIANCES.
 3) INDICATE HOW COMBUSTION AIR IS BEING PROVIDED TO THE
 GAS APPLIANCES- REFER TO SECTION 304 FBC-14 FUEL GAS.
 PLEASE INCLUDE CALCULATIONS TO VERIFY COMPLIANCE WITH
 WHICHEVER METHOD IS CHOSEN.
 4) PROVIDE A DIMENSIONED FRONT SECTION VIEW OF THE HOOD
 INDICATING THE MINIMUM 6" HOOD OVERHANG OF THE
 APPLIANCES ON ALL OPEN SIDES OF THE HOOD, AND THE
 MAXIMUM 4' DISTANCE BETWEEN THE FRONT LOWER LIP OF THE
 HOOD AND THE COOKING SURFACES OF THE APPLIANCES.
 5) THE PLAN INDICATES A 3" CLEARANCE BETWEEN THE BACK
 OF THE HOOD AND THE EXISTING WALL- REFER TO SECTION
 507.9 (EXCEPTION) AND VERIFY THAT THE WALL IS OF
 NON-COMBUSTIBLE CONSTRUCTION, AND THE STAINLESS STEEL
 WALL PANELS ARE EXTENDING NOT LESS THAN 18" IN ALL
 DIRECTIONS OF THE HOOD.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE THERMAL
 CERAMICS GREASE DUCT WRAP.
 7) SHOW THE LOCATIONS OF REQUIRED CLEANOUTS ON THE TWO
 GREASE DUCTS AND PROVIDE DETAILS FOR INSTALLATION-
 REFER TO SECTION 506.3.8 ITEMS 1-8 FBC-14 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status N Date 2015-11-05 Cont ID  
Sent By aaponte Date 2015-11-05 Time 16:05 Rev Time 0.00
Received By aaponte Date 2015-11-05 Time 16:05 Sent To  
Notes
2015-11-05 16:05:29PLEASE SUBMIT SEPARATE PERMIT FOR THE SCREENING OF THE
 MECHANICAL EQUIPMENT.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-10-16 Cont ID  
Sent By aaponte Date 2015-09-25 Time 15:50 Rev Time 0.00
Received By aaponte Date 2015-09-25 Time 15:50 Sent To  
Notes
2015-09-25 15:53:45PROVISO: NEW MECHANICAL EQUIPMENT SHALL BE SCREENED
 FROM VIEW BY A WALL OR LOUVER AS TALL AS THE PROPOSED
 EQUIPEMENT. FINAL CO SHALL NOT BE ISSUED UNTIL
 SCREENING IS INSTALLED.