Plan Review Details - Permit 15070660
Plan Review Stops For Permit 15070660
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-09-03 Cont ID  
Sent By ppetty Date 2015-09-03 Time 09:38 Rev Time 0.00
Received By ppetty Date 2015-09-03 Time 09:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-08-26 Cont ID  
Sent By albarran Date 2015-08-26 Time 10:27 Rev Time 0.00
Received By albarran Date 2015-08-26 Time 09:58 Sent To I
Notes
2015-08-26 10:59:58PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. PER OUR PREVIOUS TELEPHONE CONVERSATION, MAINTAINING
 THE PATIENT BED IN EXISTING ROOM 7 WILL EXCEED THE 16
 BED LIMIT FOR MAINTAINING THE CURRENT CLASSIFICATION.
 BEING THAT THIS BED IS IN THE STAFF OFFICE, IT SHALL BE
 LABELED ACCORDINGLY OR REMOVED TO MAINTAIN THE SIXTEEN
 PATIENT BED LIMIT.
 2. THROUGH OUT YOUR ELECTRICAL NOTES YOU CONTINUE TO
 QUOTE NON APPLICABLE AND OUTDATED CODES AND SECTIONS.
 THE APPLICABLE CODES ARE: FFPC 2012 EDITION, NFPA 70
 (NEC) 2011, NFPA 72 2010 AND THE FBC-B 5TH EDITION 2014
 (MAKE A NOTE OF THIS AS THEY APPLY TO ALL FUTURE
 PERMITS)
 3. WITH THESE NEW CODES COME A CHANGE IN REQUIREMENTS
 AS WELL AS THE APPLICABLE SECTIONS. FOR EXAMPLE YOUR
 NOTE 25 WHICH REFERS TO THE LABEL OF THE OCPD IN THE
 2007 EDITION IT DOES APPEAR IN SECTION 4.4.1.4.2.2, BUT
 THIS NOW APPEARS IN SECTION 10.5.5.2.2 OF THE 2010. DO
 YOUR RESEARCH.
 4. YOU WILL HAVE TO REVIEW AND CORRECT ALL YOUR NOTES
 ACCORDINGLY.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-11 Cont ID  
Sent By albarran Date 2015-08-11 Time 13:32 Rev Time 0.00
Received By albarran Date 2015-08-11 Time 08:29 Sent To I
Notes
2015-08-11 13:40:19PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. THE BREAK POINT BETWEEN R4 OCCUPANCY & AN I1
 OCCUPANCY CLASSIFICATION REQUIRING MUCH MORE
 RESTRICTIVE FIRE ALARM SYSTEM IS 16 BEDS. THE SUBMITTED
 PLANS REFLECT 17 BEDS. PLEASE VERIFY AS THERE IS A
 GREAT DIFFERENCE IN THE REQUIREMENTS.
 2. A MANUAL PULL STATION SHALL BE PLACED NO MORE THAN
 20? AND WITHIN 5 ? OF THE KITCHEN DOOR.
 3. A SMOKE DETECTOR IS MISSING FROM ROOM 5
 4. INDICATE ON THE PLANS THE DESIGNATED OCCUPANCY
 CLASSIFICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  
2015-08-11 10:05:47WAITING TO SPEAK W/RICK FOR CLARIFICATION. THE BED
 COUNT AS SUBMITTED CRATES A CHANGE IN OCCUPANCY
 CLASSIFICATION WHICH NEED S TO BE ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-31 Cont ID  
Sent By pleduc Date 2015-08-31 Time   Rev Time 0.00
Received By pleduc Date 2015-08-31 Time 09:29 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-09-03 Cont ID  
Sent By ppetty Date 2015-09-03 Time 09:38 Rev Time 0.00
Received By ppetty Date 2015-08-28 Time 12:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-26 Cont ID  
Sent By albarran Date 2015-08-26 Time 11:00 Rev Time 0.00
Received By albarran Date 2015-08-25 Time 15:51 Sent To  
Notes
2015-08-26 11:01:338/26/15 - FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL AND PHONE CALL. SENT TO SMALL DENIED
 BIN "A". MA
2015-08-25 15:51:53RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-11 Cont ID  
Sent By albarran Date 2015-08-11 Time 13:42 Rev Time 0.00
Received By albarran Date 2015-07-16 Time 12:42 Sent To  
Notes
2015-08-11 13:45:298/11/145 - FAILED ELECTRICAL REVIEW AS NOTED. SPOKE
 W/RICK GUSTAFSON ON THE ISSUES AND HE WILL RESUBMIT.
 SENT TO SMALL DENIED BIN "A". MA
2015-07-16 12:42:35ROUTED TO ELECTRICAL INBOX