Plan Review Details - Permit 15070655
Plan Review Stops For Permit 15070655
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-08-03 Cont ID  
Sent By cranford Date 2015-08-03 Time 15:39 Rev Time 0.00
Received By cranford Date 2015-08-03 Time 15:25 Sent To  
Notes
2015-08-03 15:39:14AS-BUILTS TO BE PROVIDED PRIOR TO FINAL INSPECTION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-07-30 Cont ID  
Sent By scaldero Date 2015-07-30 Time 09:30 Rev Time 0.00
Received By scaldero Date 2015-07-29 Time 14:15 Sent To M
Notes
2015-07-30 09:30:53PERMIT # 15070655
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THIS PLAN HAS BEEN APPROVED PROVISO WITH COMMENTS:
  
 ***VERIFICATION NEEDED THAT THE POST-INDICATOR VALVE
 COMPLIES WITH THE REQUIREMENTS OF NFPA CHAPTER 13, AS
 EXPLAINED IN THE ANNEX:
 A.8.16.1.3 OUTSIDE CONTROL VALVES ARE SUGGESTED IN THE
 FOLLOWING ORDER OF PREFERENCE:
 (1) LISTED INDICATING VALVES AT EACH CONNECTION INTO
 THE BUILDING AT LEAST 40 FT (12.2 M) FROM BUILDINGS IF
 SPACE PERMITS
 (2) CONTROL VALVES INSTALLED IN A CUTOFF STAIR TOWER OR
 VALVE ROOM ACCESSIBLE FROM OUTSIDE
 (3) VALVES LOCATED IN RISERS WITH INDICATING POSTS
 ARRANGED FOR OUTSIDE OPERATION
 (4) KEY-OPERATED VALVES IN EACH CONNECTION INTO THE
 BUILDING
 POST-INDICATOR VALVES SHOULD BE LOCATED NOT LESS THAN
 40 FT (12.2 M) FROM BUILDINGS. WHEN POST-INDICATOR
 VALVES CANNOT BE PLACED AT THIS DISTANCE, THEY ARE
 PERMITTED TO BE LOCATED CLOSER, OR WALL POST-INDICATOR
 VALVES CAN BE USED, PROVIDED THEY ARE SET IN LOCATIONS
 BY BLANK WALLS WHERE THE POSSIBILITY OF INJURY BY
 FALLING WALLS IS UNLIKELY AND FROM WHICH PEOPLE ARE NOT
 LIKELY TO BE DRIVEN BY SMOKE OR HEAT. USUALLY, IN
 CROWDED PLANT YARDS, THEY CAN BE PLACED BESIDE LOW
 BUILDINGS, NEAR BRICK STAIR TOWERS, OR AT ANGLES FORMED
 BY SUBSTANTIAL BRICK WALLS THAT ARE NOT LIKELY TO FALL.
  
 ****PLACEMENT OF THE FDC NEXT TO THE HYDRANT IS TO BE
 REVIEWED TO ENSURE THAT IT WILL NOT IMPEDED THE USE OF
 THE HYDRANT FOR FIRE FIGHTING TACTICS AND/OR WATER FLOW
 TESTING.
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-03 Cont ID  
Sent By cranford Date 2015-08-03 Time 15:40 Rev Time 0.00
Received By cranford Date 2015-07-16 Time 09:45 Sent To  
Notes
2015-07-16 09:45:56ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-07-31 Cont ID  
Sent By ccole Date 2015-07-31 Time 14:48 Rev Time 0.00
Received By ccole Date 2015-07-31 Time 14:48 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved