Plan Review Details - Permit 15070555
Plan Review Stops For Permit 15070555
Review Stop E ELECTRICAL
Rev No 3 Status N Date 2015-09-22 Cont ID  
Sent By albarran Date 2015-09-22 Time 08:54 Rev Time 0.00
Received By albarran Date 2015-09-22 Time 08:02 Sent To  
Notes
2015-09-22 08:57:27ONCE AGAIN I RECEIVED AN INCOMPLETE SUBMITTAL FOR THE
 ELECTRIC. IN GOING THROUGH THE HISTORY I NOTICED THAT
 DH HAD PREVIOUSLY APPROVED THIS UNDER A SEPARATE
 PPERMIT. I RESEARCHED THAT PERMIT TO FIND IT IS THE
 ELECTRICAL PERMIT FOR THIS SAME INSTALLATION THEREFORE
 EN ELECTRICAL REVIEW AND SUBSEQUENT DENIAL ON THIS
 PERMIT IS NOT WARRANTED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-08-24 Cont ID  
Sent By dharvey Date 2015-08-24 Time 15:28 Rev Time 0.00
Received By dharvey Date 2015-08-24 Time 15:28 Sent To  
Notes
2015-08-24 15:29:09REVIEWED UNDER 15080577

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-10 Cont ID  
Sent By albarran Date 2015-08-10 Time 17:51 Rev Time 0.00
Received By albarran Date   Time   Sent To I
Notes
2015-08-10 17:59:22YOU SHALL PROVIDE AN ELECTRICAL PAGE COMPLYING WITH ALL
 THE REQUIREMENTS OF SECTION 440 OF THE 2011 EDITION OF
 THE NEC. THIS SHEET SHALL INCLUDE LOAD CALCULATIONS AND
 WIRING DETAIL.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-09-22 Cont ID  
Sent By ccole Date 2015-09-22 Time 09:01 Rev Time 0.00
Received By albarran Date 2015-09-17 Time 13:48 Sent To  
Notes
2015-09-22 09:16:019/22/15 - ELECTRICAL REVIEW WAS PASSED UNDER SEPARATE
 PERMIT (15080577). CONTRACTOR NOTIFIED VIA EMAIL. SENT
 TO SMALL DENIED BIN "H". MA
2015-09-17 13:49:09ROUTED TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-26 Cont ID  
Sent By ccole Date 2015-08-26 Time 12:41 Rev Time 0.00
Received By ccole Date 2015-08-25 Time 10:44 Sent To  
Notes
2015-08-25 10:45:04RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-10 Cont ID  
Sent By albarran Date 2015-08-10 Time 18:00 Rev Time 0.00
Received By albarran Date 2015-07-14 Time 16:11 Sent To  
Notes
2015-08-10 18:03:298/10/15 - FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "H". MA
2015-07-14 16:13:46MECH BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-09-22 Cont ID  
Sent By ccole Date 2015-09-22 Time 09:01 Rev Time 0.00
Received By ccole Date 2015-09-21 Time 10:05 Sent To  
Notes
2015-09-21 10:07:04MECHANICAL PROVISO
 PERMIT #15070555
 09/21/15
  
 SITE SPECIFIC WIND LOAD ENGINEERING FOR TIE DOWN OF THE
 CONDENSER UNIT SHALL BE ON-SITE AT TIME OF INSPECTION-
 SECTION 301.15 FBC-14 MECHANICAL.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-08-26 Cont ID  
Sent By ccole Date 2015-08-26 Time 12:19 Rev Time 0.00
Received By ccole Date 2015-08-26 Time 12:19 Sent To  
Notes
2015-08-26 12:34:412ND REVIEW: FBC 2014 MECHANICAL
  
 1) PLEASE PROVIDE THE SENSIBLE COOLING CAPACITY OF THE
 LIEBERT SYSTEM ON THE AC SCHEDULE IN ORDER FOR THE SCOP
 TO BE VERIFED- REFER TO TABLE C403.2.3(10) FBC-14
 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-17 Cont ID  
Sent By ccole Date 2015-07-17 Time 14:04 Rev Time 0.00
Received By ccole Date 2015-07-17 Time 14:04 Sent To  
Notes
2015-07-17 16:10:051ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070555
  
 1) PROVIDE COOLING AND HEATING LOAD CALCULATIONS FOR
 THE NEW AC SYSTEM IN ACCORDANCE WITH ACCA MANUAL N OR
 THE ACCA/ASHRAE STANDARD 183- SECTION C403.2.1 FBC
 FIFTH EDITION 2014 ENERGY CONSERVATION CODE.
 2) DUCT SMOKE DETECTORS SHALL BE INSTALLED IN THE
 RETURN DUCT OF THE NEW AHU, AND THE RETURN DUCTS OF THE
 EXISTING AHU'S- REFER TO SECTIONS 606.2.1 & 606.2.2
 FBC- 2014 MECHANICAL. SHOW THE LOCATIONS OF THE DEVICES
 ON THE PLANS AND INDICATE HOW THEY WILL BE SUPERVISED
 PER SECTION 606.4.1.
 3) INDICATE THE TYPE AND DIAMETER OF THE CONDENSATE
 PIPE PER TABLE 307.2.2, AND PROVIDE DETAILS FOR
 SECONDARY DISPOSAL: A) PAN DIMENSIONS, DEPTH, AND GAGE
 OF STEEL. B) TYPE AND SIZE OF PAN DRAIN PIPE AND
 TERMINATION LOCATION- REFER TO SECTION 307.2.3 FOR
 ADDITIONAL INFORMATION.
 4) THE SCOPE OF WORK NOTE #1 ON THE CONTRACT INDICATES
 A 12X24 FT. MOUNTING PAD FOR THE CONDENSER, HOWEVER THE
 PLAN INDICATES A 4X34 FT. PAD: PLEASE CLARIFY AND
 PROVIDE STRUCTURAL DETAILS FOR THE PAD, AND WIND LOAD
 TIE DOWN ENGINEERING FOR MOUNTING THE CONDENSER TO THE
 PAD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-09-17 Cont ID  
Sent By sgraham Date 2015-09-17 Time 14:44 Rev Time 0.00
Received By sgraham Date 2015-09-17 Time 14:44 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-07-21 Cont ID  
Sent By sgraham Date 2015-07-21 Time 11:24 Rev Time 0.00
Received By sgraham Date 2015-07-21 Time 11:24 Sent To E
Notes
***NONE***