Plan Review Details - Permit 15070510
Plan Review Stops For Permit 15070510
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-11-05 Cont ID  
Sent By jwitmer Date 2015-11-05 Time 06:03 Rev Time 0.00
Received By jwitmer Date 2015-11-05 Time 05:26 Sent To  
Notes
2015-11-05 06:03:19BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15070570
 ADD: 3201 ELECTRONIC WAY
 CONT: CEDARS ELECTRO-MECHANICAL, INC.
 TEL: (561)588-4088
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. NOV. 05/2015
  
 ACTION: BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
  
 1) SHEET A-6 DETAIL # 3 SHOWS A NEW METAL EQUIPMENT
 SCREENING SYSTEM, SHEET S2 DETAIL # 6 NOTE, LOUVERED
 SCREEN BY ARCHITECTURAL LOUVERS OR APPROVED EQUAL.
 TO DATE NO MORE INFORMATION HAS BEEN GIVEN ,IF THIS IS
 A SERIES OF LOUVERS SUPPORTED BY PRODUCT APPROVALS OR
 IF THIS IS GOING TO BE AN ENGINEERED LOUVERED SCREEN.
 WILL NEED PRODUCT DESIGN, WIND DESIGN CRITERIA, PRODUCT
 APPROVALS OR ENGINEERING FOR THE LOUVERED SCREEN
 PORTION OF THIS PRODUCT.
 2014 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-04 Cont ID  
Sent By jwitmer Date 2015-08-04 Time 07:28 Rev Time 0.00
Received By jwitmer Date 2015-08-04 Time 06:03 Sent To  
Notes
2015-08-04 07:28:19BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15070570
 ADD: 3201 ELECTRONIC WAY
 CONT: CEDARS ELECTRO-MECHANICAL, INC.
 TEL: (561)588-4088
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 04/2015
 ACTION: DENIED
  
 1) SHEET A-6 DETAIL # 3 SHOWS THE UNIT AS A ROOFTOP
 UNIT ON CURB WHILE SHEET S-2 INDICATES THIS SAME UNIT
 TO BE ON A 4'-0" HIGH STAND. DISCREPANCY IN PLANS
 PLEASE REMOVR THE DETAILS THAT DO NOT PERTAIN TO THIS
 PROJECT. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) SHEET S-1 CU ATTACHMENT DETAIL TO CONCRETE SLAB DOES
 NOT PROVIDE HOW MANY FASTENERS PER ANCHOR AND WHAT TYPE
 OF FASTENERS. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-09-22 Cont ID  
Sent By albarran Date 2015-09-22 Time 13:41 Rev Time 0.00
Received By albarran Date   Time   Sent To  
Notes
2015-09-22 13:43:45THE SCOPE OF THIS PERMIT ENCOMPASSES 4 PHASES OF HVAC
 REPLACEMENT WORK. NOTES WERE MADE ADDRESSING THE PROPER
 CODE AND AS A REMINDER TO OBSERVE COMPLIANCE W/NEC
 210.63 THROUGHOUT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-07-29 Cont ID  
Sent By pleduc Date 2015-07-29 Time   Rev Time 0.00
Received By pleduc Date 2015-07-29 Time 13:26 Sent To  
Notes
2015-07-29 13:57:24THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1. PHASE 2 - SHEET M-502 INDICATES TEMPORAY A/C
 EQUIPMENT ENCROACHING ON A REQUIRED EXIT DOOR. THE
 EQUIPMENT SHALL NOT IMPEDE OCCUPANT EGRESS. EQUIPMENT
 SHALL BE MOVE AWAY FROM THE EXIT OPENING.
  
 2. PHASE 3 - SHEET M-501 INDICATES TEMPORAY A/C
 EQUIPMENT POSSIBLY ENCROACHING ON A REQUIRED EXIT DOOR.
 THE EQUIPMENT SHALL NOT IMPEDE OCCUPANT EGRESS.
 EQUIPMENT SHALL BE MOVE AWAY FROM THE EXIT OPENING.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-05 Cont ID  
Sent By jwitmer Date 2015-11-05 Time 06:03 Rev Time 0.00
Received By jwitmer Date 2015-10-29 Time 13:27 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-22 Cont ID  
Sent By albarran Date 2015-09-22 Time 13:44 Rev Time 0.00
Received By albarran Date 2015-07-14 Time 10:56 Sent To  
Notes
2015-09-22 13:52:269/22/15 - PASSED ELECTRICAL REVIEW BUT FAILED BLDG. &
 MECH. CONTRACTOR NOTIFIED OF STATUS VIA EMAIL. SENT TO
 LARGE DENIED BIN "C". MA

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-11-02 Cont ID  
Sent By jwitmer Date 2015-11-05 Time 06:03 Rev Time 0.00
Received By ccole Date 2015-11-02 Time 11:36 Sent To  
Notes
2015-11-02 11:39:05PERMIT #15070510
 11/2/15
 PROVISO:
  
 WIND LOAD ENGINEERING FOR TIE DOWN OF THE EXTERIOR
 DUCTS TO THE STANDS, AND FOR MOUNTING THE RTU TO THE
 CURB SHALL BE ON-SITE AT TIME OF INSPECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-18 Cont ID  
Sent By ccole Date 2015-08-18 Time 06:58 Rev Time 0.00
Received By ccole Date 2015-08-18 Time 06:58 Sent To  
Notes
2015-08-18 08:46:091ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070510
 PHASES 1-4
 8/18/15
  
 GENERAL COMMENTS PHASES 1-4:
  
 1) REFER TO SECTION 606.2.1 FBC-14 MECHANICAL: 606.2.1
 RETURN AIR SYSTEMS.
 SMOKE DETECTORS SHALL BE INSTALLED IN RETURN AIR
 SYSTEMS WITH A DESIGN CAPACITY GREATER THAN 2,000 CFM
 (0.9 M3/S) IN THE RETURN AIR DUCT OR PLENUM UPSTREAM OF
 ANY FILTERS, EXHAUST AIR CONNECTIONS, OUTDOOR AIR
 CONNECTIONS, OR DECONTAMINATION EQUIPMENT AND
 APPLIANCES. PLEASE CORRECT ALL PLANS INDICATING THE DS
 DETECTORS IN THE SUPPLY DUCTS.
 2) PROVIDE A SUBMITTAL PACKAGE THAT INCLUDES: A)
 CURRENT FLORIDA PRODUCT APPROVALS OR MIAMI-DADE NOA'S
 FOR THE AC STANDS, THE O/A AND EXHAUST LOUVERS. B)
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE VAV DIFFUSERS, THE DUCT SMOKE
 DETECTORS, THE FIRE DAMPERS, AND THE PLENUM-RATED PIPE
 INSULATIONS.
 3) PROVIDE THROUGH PENETRATION FIRESTOPPING DETAILS FOR
 PIPES PENETRATING THE RATED MECHANICAL ROOM WALLS.
 4) THE AREAS UNDER CONSTRUCTION SHALL ALSO BE PROVIDED
 WITH TEMPORARY HEAT IN ACCORDANCE WITH SECTION 309.1
 FBC-14 MECHANICAL. THE PORTABLE AC SCHEDULES ARE
 INDICATING COOLING ONLY.
 5) PLEASE REVIEW SECTION C408 FBC-14 ENERGY
 CONSERVATION: COMMISSIONING AND TESTING AND BALANCING
 OF THE SYSTEMS IS REQUIRED. PLEASE PROVIDE NOTES AND
 DETAILS ON THE PLANS TO VERIFY COMPLIANCE.
  
 PHASE-1:
 1) SHEET M-301, CU MOUNTING DETAIL: PROVIDE THE TYPE
 AND SIZE OF ANCHOR BOLTS FOR THE CABLES AND THE
 CHANNELS. INDICATE THE WIND LOAD DESIGN CRITERIA AND
 THE DESIGN PRESSURES- SECTION 301.15 FBC-14 MECHANICAL.
 2) M-501: INDICATE HOW THE TEMPORARY EXTERIOR DUCTS
 WILL BE SUPPORTED AND PROTECTED DURING CONSTRUCTION.
  
 PHASE-2:
 1) M-103: PROVIDE THE EQUIPMENT SCHEDULE FOR THE
 EXISTING RTU.
 2) M-201: MISSING FIRE DAMPER FOR THE 14X12 DUCT
 PENETRATING THE RATED MECHANICAL ROOM WALL ON THE SOUTH
 SIDE.
 3) M-301, CU MOUNTING DETAIL: PROVIDE THE TYPE AND SIZE
 OF ANCHOR BOLTS FOR THE CABLES AND THE CHANNELS.
 INDICATE THE WIND LOAD DESIGN CRITERIA AND THE DESIGN
 PRESSURES- SECTION 301.15 FBC-14 MECHANICAL.
 4) M-302: PROVIDE COMPLETE DETAILS FOR THE EXTERIOR
 DUCT INSTALLATION- TYPE AND GAUGE OF DUCT STEEL, TYPE
 AND R-VALUE OF DUCT INSULATION, SPACING OF DUCT
 SUPPORTS, AND TYPES AND SIZES OF ANCHOR BOLTS. INDICATE
 THE WIND LOAD DESIGN CRITERIA AND WIND PRESSURES.
 5) M-302: PROVIDE COMPLETE DETAILS FOR THE ROOF TOP
 EQUIPMENT MOUNTING DETAIL- STRUCTURAL DETAILS FOR THE
 SUPPORT BASE, ANCHORING AND FASTENING DETAILS FOR THE
 RTU AND THE BASE, WIND DESIGN CRITERIA AND PRESSURES.
 6) M-501: INDICATE HOW THE TEMPORARY EXTERIOR DUCTS
 WILL BE SUPPORTED AND PROTECTED DURING CONSTRUCTION.
  
 PHASE-3:
 1) M-201: PROVIDE ENGINEERED STRUCTURAL DETAILS FOR
 INSTALLATION OF THE O/A DUCT AND INLET.
 2) M-301, CU MOUNTING DETAIL: PROVIDE THE TYPE AND SIZE
 OF ANCHOR BOLTS FOR THE CABLES AND THE CHANNELS.
 INDICATE THE WIND LOAD DESIGN CRITERIA AND THE DESIGN
 PRESSURES- SECTION 301.15 FBC-14 MECHANICAL.
  
 PHASE-4:
 1) M-201: MISSING FIRE DAMPER FOR THE DUCT PENETRATING
 THE RATED AHU-4 MECHANICAL ROOM WALLS OVER THE DOUBLE
 DOORS.
 2) M-301, CU MOUNTING DETAIL: PROVIDE THE TYPE AND SIZE
 OF ANCHOR BOLTS FOR THE CABLES AND THE CHANNELS.
 INDICATE THE WIND LOAD DESIGN CRITERIA AND THE DESIGN
 PRESSURES- SECTION 301.15 FBC-14 MECHANICAL.
 3) M-501: INDICATE HOW THE TEMPORARY EXTERIOR DUCTS
 WILL BE SUPPORTED AND PROTECTED DURING CONSTRUCTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-08-03 Cont ID  
Sent By tklarge Date 2015-08-03 Time 05:34 Rev Time 0.00
Received By tklarge Date 2015-08-01 Time 08:49 Sent To  
Notes
***NONE***