| 2015-07-13 09:56:45 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY ELECTRIC |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION 402.4.5 |
| | RECESSED LIGHTING. |
| | RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL |
| | ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED AND UNCONDITIONED SPACES. |
| | |
| | 2) NEC 240.24(A) & (B) PANELS SHALL BE READILY |
| | ACCESSIBLE AND EACH OCCUPANT SHALL HAVE READY ACCESS. |
| | SPECIFY THE LOCATIONS OF THE PANELS AND METER ON THE |
| | ELECTRICAL FLOOR PLAN. |
| | |
| | 3) FBC-R 315.1 - PROVIDE CARBON MONOXIDE ALARMS WITHIN |
| | 10 FEET OF EACH SLEEPING ROOM. |
| | |
| | 4) NEC 210.52(A) - (H) OUTLET SPACING, IT APPEARS SOME |
| | POINTS ALONG THE WALL EXCEED 6' FROM AN OUTLET. |
| | |
| | 5) NEC 210.52 (C) (1) - A RECEPTACLE OUTLET SHALL BE |
| | INSTALLED AT EACH COUNTERTOP SPACE 12 INCHES OR WIDER |
| | SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 2 |
| | FEET MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN |
| | THAT SPACE. |
| | |
| | 6) NEC 210.8 (A)(6) RECEPTACLES SERVING COUNTERTOP |
| | SURFACES ARE REQUIRED TO BE GFCI PROTECTED. |
| | |
| | 7) R314.3.1 WHEN ALTERATIONS, REPAIRS OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. A SMOKE |
| | ALARM IS REQUIRED IN BOTH UPSTAIRS BEDROOMS. |
| | |
| | 8) NEC 210.12 (B) - OUTLETS ARE REQUIRED TO BE AFCI |
| | PROTECTED. |
| | |
| | 9) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE |
| | REQUIRED. |
| | |
| | 10) NEC 250.50 - BOND ALL GROUNDING ELECTRODES THAT ARE |
| | PRESENT. |
| | |
| | 11) NEC 250.104(B) THE GAS PIPING IS REQUIRED TO BE |
| | BONDED. |
| | |
| | 12) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL |
| | BE PROVIDED. |
| | |
| | 13) NEC 440.11 & 440.14 SHOW THE LOCATION OF THE |
| | REQUIRED A/C EQUIPMENT DISCONNECTING MEANS ON THE |
| | PLANS. |
| | |
| | |
| | |
| | |
| | |
| 2015-07-10 18:50:11 | ON RMCDOUGAL'S DESK |